Metrel MI 3394 CE MultiTesterXA Electrical Safety Tester

Brand
Metrel
Model number
MI 3394

Electrical safety tester for CE testing of appliances, machines and switchboards in production: 5 kV AC / 6 kV DC hipot, continuity up to 25 A, insulation, leakage currents, discharge time and functional power test.

Price and availability on request

Request a quote

Sent with the product details: Metrel MI 3394 CE MultiTesterXA Electrical Safety Tester.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • High Voltage, programmed (AC/DC)
  • High Voltage, burn test (optional A 1560)
  • Continuity tests
  • Insulation resistance measurement
  • Substitute leakage current
  • Differential leakage current
  • Touch leakage current
  • PE-leakage current
  • Discharge time
  • Functional test (power P/S/Q, voltage, current, cos fi, frequency, ThdU, ThdI,PF)
  • Creation of structure with dedicated tests
  • PASS/FAIL evaluation of test results
  • Execution of all single tests
  • Programmable High Voltage (AC + DC) test
  • 4-wire continuity test

Specifications

HV test
HV AC (programmable 100 V - 5100 V, 10 V steps)0 ... 5.99 kV, ±⁠(3 % of reading); test current 0.0 ... 99.9 mA; output power 500 VA max
HV DC (programmable 500 V - 6000 V, 50 V steps)0 ... 6.99 kV, ±⁠(3 % of reading); test current 0.01 ... 9.99 mA
Continuity
Test currents 0.2 A, 4 A, 10 A, 25 A0.000 Ω ... 999 Ω; ±⁠(2 % of reading + 2 D) up to 1.999 Ω
Insulation
Insulation resistance Riso / Riso-S (50 V ... 1000 V)0.00 MΩ ... 199.9 MΩ; ±⁠(3 % of reading + 2 digits) up to 19.99 MΩ at 250 V ... 1000 V
Leakage
Differential / PE / touch leakage current0.00 mA ... 19.99 mA; ±⁠(3 % of reading + 5 digits)
Substitute leakage current Isub / Isub-S0.00 mA ... 19.99 mA; open circuit voltage <50 V a.c.
Discharging time
Discharging time / residual voltage0.0 ... 9.9 s / 0 ... 550 V; ±⁠(5 % of reading + 3 digits)
Functional test
Power P / S / Q, PF, THD, U, Iup to 3.70 kVA, ±⁠(5 % of reading); current 0 mA ... 16.00 A; voltage 0.1 V ... 264 V
General
Power supply110 V / 230 V AC, 50 Hz / 60 Hz
Overvoltage categoryCAT II / 300 V, CAT II / 600 V (DISCH1 / DISCH2 only)
HV output5 kV a.c. / 6 kV d.c., double insulation
Communication4 x RS232, 1 x USB, 1 x Bluetooth
Dimensions (w×h×d) / weight43.5 cm x 29.2 cm x 15.5 cm / 17 kg
Ordering
Sets on Metrel's siteMI 3394 ST (standard set, supplied), MI 3394 EU (Euro set), MI 3394 LN (Line set), MI 3394 LB (Lab set)
Supplied with
MI 3394 Standard setMI 3394 Instrument CE MultiTesterXA; HV measurement set 5m-without conclusion (S 2073); 2x A 1076 Test cable, BLK/RED, 2.5m, 2.5mm2/0.75mm2; 1x A 1710 Test lead, Red, 1.5m, 2.5mm2; 1x A 1370 Test lead, Red, 2.5m, 0.75mm2; 1x A 1369 Test lead, Black, 2.5m, 0.75mm2; 2x Crocodile clip, Black (A 1013); 3x Crocodile clip, Red (A 1064); Test cable, Black, 2m, 0.75mm2 (A 1079); 1x A 1493 Power cable, 2m, 3x1.5mm2; RS232 communication cable (A 1017); USB cable L=1m (A 1727); Soft carrying bag Size: XXL

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.