Metrel MI 3340 AlphaEE XA Electrical Equipment Safety Tester
- Brand
- Metrel
- Model number
- MI 3340
- Category
- Electrical Safety Testers
Touch-screen appliance and equipment tester to EN 50678 / EN 50699: continuity, insulation at 50 ... 500 V, substitute, differential, touch and PE leakage, power, PRCD, RCD and EV cable (IC-CPD) tests; Li-ion, Bluetooth.
Price and availability on request
Key features
- EN 50678 / EN 50699
- Visual inspections
- Auto test (Continuity + Insulation resistance + Alternative leakage)
- Continuity of protective earth 200mA
- Insulation Resistance (Riso, Riso-S) 50V, 100V, 250V, 500V
- Protective conductor current (Direct, Residual, Alternative)
- Touch leakage current (Direct, Alternative)
- Leakage current produced by a floating input, PE current (Direct, Residual)
- Leakage current produced by a floating input, Touch current (Direct)
- Leaks & Power (Itou, Idiff, P, S, Q, PF, THDu, THDi, CosØ, I, U)
- Point to Point Leakage current (Direct)
- Power (P, S, Q, PF, THDu, THDi, CosØ, I, U)
- PRCD test, (2 pole, 3 pole, K/ Di (varistor), S (3-pole)), S+
- PRCD test (PE conductor, Open conductor, PE probe)
- RCD test (type A, AC, B, B+, F)
- IC-CPD test (EV-RCD, PE conductor)
- Voltage, SELV/PELV
- Socket test
- Polarity / Active polarity test
- EVSE Diagnostic test
- Clamp current;*
- Functional inspections
Specifications
| Continuity (200 mA) | 0.00 Ω ... 1999 Ω; ±(2 % of reading + 2 D) up to 19.99 Ω |
|---|
| Insulation resistance Riso, Riso-S (50 V, 100 V, 250 V, 500 V) | 0.00 MΩ ... 199.9 MΩ; ±(3 % of reading + 2 D) up to 19.99 MΩ |
|---|
| Substitute leakage current | 0.00 mA ... 19.99 mA; ±(3 % of reading + 3 D) up to 1.99 mA |
|---|---|
| Differential, PE, touch leakage current | 0.000 mA ... 19.99 mA; ±(3 % of reading + 3 D) up to 1.999 mA |
| Floating input leakage (Ifi) | 0.000 mA ... 19.99 mA |
| P, S, Q, PF, THDu, THDi | P 0 W ... 3.70 kW; ±(5 % of reading + 5 D) |
|---|
| Trip-out time | 0 ms ... 300 ms (½xI∆N, I∆N), 0 ms ... 40 ms (5xI∆N); ± 3 ms |
|---|---|
| Trip-out current | 0.2x I∆N ... 2.2x I∆N; ± 0.1x I∆N |
| RCD types | A, AC, B, B+, F; PRCD 2 pole, 3 pole, K/Di, S, S+ |
| IC-CPD / EV RCD test | PE conductor, trip-out time and current |
|---|
| Voltage | 0.0 V ... 264 V |
|---|
| Mains supply | 115 V / 230 V a.c., 50 Hz / 60 Hz |
|---|---|
| Overvoltage category | CAT II / 300V |
| Degree of protection | IP 40 / IP 20 (mains test socket) |
| Display | Colour TFT display, 4.3 inch, 480 x 272 pixels |
| Bluetooth | Class 1 |
| Dimensions (w×h×d) / weight | 15 cm × 8 cm × 28 cm / 1.7 kg |
| MI 3340 Standard set | Instrument MI 3340 AlphaEE XA; 2x A 1493 Power cable, 2m, 3x1.5mm2; 1x A 1340 Test lead, Black, 1.5m, 2.5mm2; Test probe, Black (A 1014); Crocodile clip, Black (A 1013); Soft padded carrying bag Size: M (A 1289); USB cable TypeA/B (A 1727); Calibration certificate; Short instruction manual; Instruction manual; Metrel ES Manager BASIC Licence |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.