Metrel MI 3325 MultiServicerXD Machine and Switchboard Safety Tester

Brand
Metrel
Model number
MI 3325

Rugged machine, switchboard and appliance safety tester to IEC/EN 60204-1 and 61439-1: 5.1 kV AC hipot, 4-wire continuity up to 25 A, insulation, loop / line impedance, RCD, leakage and discharge time.

Price and availability on request

Request a quote

Sent with the product details: Metrel MI 3325 MultiServicerXD Machine and Switchboard Safety Tester.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Continuity (2-wire & 4-wire), 0.2 A, 4 A, 10 A, 25 A + voltage drop @ 10 A
  • HV AC, HV AC programmable 100 V - 5100 V
  • Insulation resistance (Riso, Riso-S) 50 V, 100 V, 250 V, 500 V, 1000 V (DC)
  • Sub-leakage current, (Isub, Isub-S) 110 V (AC), 230 V (AC)
  • Z loop – fault loop impedance and prospective fault current (Ipsc, Ulpe, Uc(P))
  • Zs rcd – fault loop impedance and prospective fault current in system with RCD (Ipsc, pe, Uc(P))
  • Z line – line impedance and prospective short-circuit current (Ipsc, Uln)
  • Functional test (power P/S/Q, voltage, current, cos fi, frequency, ThdU, ThdI, PF)
  • Touch leakage current
  • RCD testing (RCD Uc, RCD t, RCD I)
  • Differential leakage current
  • PE leakage current
  • Polarity
  • Clamp current
  • Voltage, Frequency, phase rotation
  • Varistor test
  • Voltage drop
  • Discharging time
  • Touch screen: high resolution colour touch screen, 4.3” TFT
  • Double manipulation: keyboard and touch screen enable the user to control the instrument in any manner they like
  • Pre-defined AUTOSEQUENCE®s: enable the user simple and quick execution of test sequence for the chosen device
  • Support for RCD testing: A, AC, B, B+ and F RCDs

Specifications

HV test
HV AC programmable100 V - 5100 V (5.1 kV @ 250 VA)
Continuity
2-wire and 4-wireTest current 0.2 A, 4 A, 10 A, 25 A; voltage drop @ 10 A
Insulation
Insulation resistance (Riso, Riso-S)50 V, 100 V, 250 V, 500 V, 1000 V (DC)
Leakage
Sub-leakage current (Isub, Isub-S)110 V (AC), 230 V (AC)
Touch, differential and PE leakage currentIncluded
Impedance
Z loop, Zs rcd, Z lineIpsc, Ulpe, Uc(P), Uln; built-in fuse tables
RCD
RCD testing (Uc, t, I)Types A, AC, B, B+ and F
Functional test
Functional testPower P/S/Q, voltage, current, cos fi, frequency, ThdU, ThdI, PF
Other
Other testsPolarity, clamp current, voltage, frequency, phase rotation, varistor test, voltage drop, discharging time
General
SystemsTT, TN, IT and 115 V supply systems
DisplayHigh resolution colour touch screen, 4.3" TFT
Communication / memory4 RS232, USB, Ethernet and Bluetooth / microSD, 8 GB, expandable to 32 GB
Dimensions (w x h x l) / mass420 x 325 x 180 mm / 13.3 kg
Supplied with
MI 3325 Standard setInstrument MI 3325 MultiServicerXD; 1x A 1601 HV test lead, Red, 1.5m, 5kV; Cap, Red (A 1386); 1x A 1602 HV test lead, Blue, 1.5m, 5kV; 1x A 1773 HV Crocodile, Red, mini; 2x A 1493 Power cable, 2m, 3x1.5mm2; Test cable, Brown, 1.5m, 0.75mm2 (A 1599); Test cable, 1.5m, 0.75mm2 (A 1053); Test cable, BLK/GRN/BLU, 3m, 1.5mm2 (A 1677); 1x A 1076 Test cable, BLK/RED, 2.5m, 2.5mm2/0.75mm2, 2 pcs; 1x A 1710 Test lead, Red, 1.5m, 2.5mm2; Test probe, Red (A 1016); Test probe, Black (A 1014); Test probe, G

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.