Key features

  • Live Transformer’s Impedance Measurement with Four Wire Test
  • Hi-precision Short Circuit Current evaluation with Calculated Hot factor
  • 3-wire test of PE (RPE function) without extension lead conductor
  • Autotest insulation function between L-N, N-PE and L-PE (R ISO ALL function)
  • 4 wire continuity test
  • Insulation resistance with DC voltage from 50 V to 2500 V and PI, DAR calculation
  • Varistor test
  • Continuity of PE conductors with 200 mA DC test current with polarity change
  • Continuity of PE conductors with 7 mA test current without RCD tripping
  • 2-wire and 3-wire loop impedance (L-PE) measurement with Trip Lock RCD function
  • Touch voltage / Contact voltage measurement with external P/S probe
  • 2-wire and 3-wire high-current loop impedance (L-PE) measurement
  • 3-wire loop impedance (L-PE) measurement with Trip Lock RCD function
  • 1-phase / 3-phase TRMS voltage and frequency measurements
  • Line, loop and RCD measurements at frequency range 16 ... 400 Hz
  • Phase sequence
  • Power and THD measurement (up to the 12th harmonic)
  • RCD testing (general and selective, type AC, A, F, B, B+, MI RCD, EV RCD, PRCD, PRCD-K, PRCD-S)
  • Earth resistance (3-wire and 2-clamps method)
  • Specific earth resistance with Ro-adapter (option)
  • TRMS leakage and load currents (option)
  • First fault leakage current (ISFL)

Specifications

Continuity
200 mA (2-wire)0.00 Ω ... 1999 Ω; ±⁠(3 % of r. + 3 digits) up to 19.99 Ω
200 mA (4-wire)0.00 Ω ... 1999 Ω
7 mA (no RCD tripping)0.00 Ω ... 1999 Ω; ±⁠(5 % of r. + 3 digits)
Insulation resistance
Test voltages 50 / 100 / 250 / 500 / 1000 / 2500 V0.00 MΩ ... 19.99 GΩ (2500 V); ±⁠(5 % of r. + 3 digits) up to 19.99 MΩ
DAR, PI0.01 ... 100.0
Varistor test0 V ... 1000 V (DC), 0 V ... 625 V (AC); ±⁠(3 % of r. + 3 digits)
RCD
Contact voltage Uc0.00 V ... 99.9 V; (-0 %/+15 %) of r.
Trip-out time0.0 ms ... max. time; ±1 ms up to 40.0 ms, ±3 ms above
Trip-out current (ramp)0.2xI∆N ... 2.2xI∆N depending on RCD type (AC, A, F, B, B+, MI, EV)
Impedance
Line (L-L, L-N) and loop (L-PE) impedance, 2- and 4-wire0.00 Ω ... 9.99 kΩ; ±⁠(3 % of r. + 3 digits) up to 99.9 Ω
Voltage
TRMS voltage / frequency0 ... 550 V, ±⁠(2 % of r. + 2 digits) / 0.00 Hz ... 499.9 Hz, ±⁠(0.2 % of r. + 1 digits)
Current
TRMS current with clampsA 1018: 0.0 mA ... 19.99 A; A 1391 AC/DC: 0.00 A ... 299.9 A
Earth resistance
3-wire0.00 Ω ... 9999 Ω; ±⁠(5 % of r. + 5 digits)
2 clamps0.00 Ω ... 39.9 Ω; ±⁠(10 % of r. + 10 digits) up to 19.99 Ω
Specific earth resistance (with Ro-adapter)0.0 Ωm ... 9999 kΩm
Power
P, S, Q / power factor0.00 W ... 99.9 kW / -1.00 ... 1.00
Harmonics
Voltage / current harmonics, THD0.1 V ... 500 V / 0.00 A ... 199.9 A; THD 0.1 % ... 99.9 %
IT systems
First fault leakage current ISFL0.0 mA ... 19.9 mA; ±⁠(5 % of r. + 3 digits)
IMD testThreshold insulation resistance 5 ... 640 kΩ, indicative, up to 128 steps
Illuminance
Type B / type C sensor (option)0.01 lux ... 19.99 klux; ±⁠(5 % of r. + 2 digits) with type B
Discharging time
Discharging time / peak voltage0.0 s ... 10.0 s / 0 V ... 550 V
General
Power supply7.2 V (4400 mAh Li-Ion battery pack)
Overvoltage category600 V CAT III; 300 V CAT IV
DisplayColour TFT display, 4.3 inch, 480 x 272 pixels
CommunicationBT, USB, RS232
Weight / size1.78 kg / 252 x 111 x 165 mm
Supplied with
MI 3155 Standard set (ST)Instrument MI 3155 EurotestXD; 5200 mAh battery pack; Power supply adapter 12 V / 3 A; Plug commander, 1.5 m; Test lead, 4-wire, 1.5 m; Test lead, 3-wire, 1.5 m; Test lead, 2-wire, 2,5 kV, 1.5 m; Test probe, 4 pcs (black, blue, green, red); Crocodile clip, 6 pcs (black – 2 pcs, blue – 1 piece, green – 1 piece, red – 2 pcs); Earth set 20 m; USB cable; Soft carrying bag; Soft carrying neck belt; Calibration certificate; Short instruction manual; Instruction manual; Metrel ES Manager BASIC Licence