Metrel MI 3100 SE EurotestEASI Multifunction Installation Tester

Brand
Metrel
Model number
MI 3100 SE

Easy-to-use multifunction installation tester: insulation to 1000 V, 200 mA and 7 mA continuity, line / loop impedance, RCD incl. type B, TRMS voltage, phase sequence and 3-wire earth resistance.

Price and availability on request

Request a quote

Sent with the product details: Metrel MI 3100 SE EurotestEASI Multifunction Installation Tester.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Insulation resistance with DC voltage from 50 V to 1000 V
  • Continuity of PE conductors with 200 mA test current with polarity change
  • Continuity of PE conductors with 7 mA test current without RCD tripping
  • Line impedance
  • Loop impedance
  • Loop impedance with Trip Lock RCD function
  • TRMS voltage and frequency
  • Phase sequence
  • RCD testing (general and selective, type AC, A, F)
  • Earth resistance (3-wire method)
  • Auto TT (U, Zln, Zs, Uc)
  • Auto TN/RCD (U, Zln, Zs, Rpe)
  • Auto TN (U, Zln, Zlpe, Rpe)
  • Built-in help screens for referencing on site
  • Built-in fuse tables for automatic evaluation of the line / loop impedance result
  • On-line voltage monitoring: monitors all 3 voltages in real-time
  • Polarity swap: automatic polarity reversal on continuity test
  • Trip Lock function: loop impedance test without tripping the RCD
  • Built-in charger unit has a built-in charging circuit and comes complete with a set of rechargeable NiMH batteries
  • RCD auto: automated RCD testing procedure
  • Bluetooth communication with PC, Android tablets and smart phones via optional BT dongle
  • PC SW EuroLink PRO for downloading of test results and report creation

Specifications

Continuity
200 mA (2-wire)0.00 Ω ... 1999 Ω; ±⁠(3 % of r. + 3 digits) up to 19.99 Ω
7 mA (2-wire)0.00 Ω ... 1999 Ω; ±⁠(5 % of r. + 5 digits)
Insulation resistance
Test voltages 50 / 100 / 250 / 500 / 1000 V0.00 MΩ ... 999 MΩ; ±⁠(5 % of r. + 3 digits) up to 19.99 MΩ
RCD
Contact voltage / trip-out time0.00 V ... 99.9 V / 0.0 ms ... max. time
Trip-out current0.2xI∆N ... 2.2xI∆N (AC, A, B types)
Impedance
Line and loop impedance0.00 Ω ... 9.99 kΩ; ±⁠(5 % of r. + 5 digits) up to 99.9 Ω
Voltage
TRMS voltage / frequency0 ... 550 V / 0.00 Hz ... 499.9 Hz
Earth resistance
3-wire0.00 Ω ... 9999 Ω; ±⁠(5 % of r. + 5 digits)
General
Power supply9 VDC (6x1.5 V battery or accu, size AA)
Overvoltage categoryCAT II / 1000 VDC; CAT III / 600 V; CAT IV / 300 V
CommunicationBT, USB, RS232
Weight / size1.3 kg / 230 x 103 x 115 mm
Supplied with
MI 3100 SE Standard setInstrument MI 3100 SE; EurotestEASI; Schuko-plug test cable, 1.5 m; Test lead, 3 x 1.5 m; Test probe, 3 pcs (blue, black, green); Crocodile clip, 3 pcs (blue, black, green); Power supply adapter + 6 NiMH rechargeable batteries, size AA; RS232 - PS/2 cable; USB cable; Soft carrying neck belt; Soft carrying bag; Calibration certificate; Short instruction manual; Instruction manual; PC Software; EuroLink PRO* (SW 0101)