Metrel MI 3110 EurotestIM IT System / Medical Installation Tester

Brand
Metrel
Model number
MI 3110

Tester for IT (isolated) supply systems such as medical locations: first fault leakage current, insulation monitoring device (IMD) test, line impedance, voltage drop, TRMS voltage, frequency and phase rotation.

Price and availability on request

Request a quote

Sent with the product details: Metrel MI 3110 EurotestIM IT System / Medical Installation Tester.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Voltage, frequency and phase sequence
  • Line impedance and prospective short circuit current
  • Voltage drop
  • First fault leakage current (ISFL)
  • Testing of insulation monitoring devices (IMD)
  • AUTO SEQUENCE ®: One single AUTO SEQUENCE ® with programmable limits and sub-tests ensuring Safety on all PASS bar-rier parameters
  • Voltage monitor: IT System recognizing, Voltage Range and Voltage Balance
  • ISFL test: ISFL Single Fault Leakage current from Phase 1 and Phase 2 to PE. Fuse Trip-out Ability Evaluation, Line Impedance and Ipsc Prospective Short Circuit Current
  • IMD control: IMD Insulation / ELM Earth Leakage / RCM Residual Current Monitor Devices Control
  • IMD adjust: Alarm Trigger or Trip-Out Check and Adjust

Specifications

IT systems
First fault leakage current (ISFL)0.0 mA ... 19.9 mA; ±⁠(5 % of reading + 3 digits); measuring resistance 390 Ω
IMD test insulation resistance5 kΩ ... 640 kΩ, 5 kΩ steps; indicative values, up to 128 steps
IMD test current0.0 mA ... 19.9 mA (calculated value)
Nominal voltage ranges93 V ≤ UL1-L2 < 134 V / 185 V ≤ UL1-L2 < 266 V
Impedance
Line impedance (EN 61557-3)0.00 Ω ... 99.9 Ω; ±⁠(5 % of reading + 5 digits)
Voltage drop0.0 ... 99.9 %
Voltage
Voltage0 V ... 550 V; ±⁠(2 % of reading + 2 digits)
Frequency10.0 Hz ... 500.0 Hz; ±⁠(0.2 % of reading + 1 digit)
Phase rotation100 V ... 550 V; 1.2.3 or 3.2.1
General
Power supply9 VDC (6x1.5 V battery or accu, size AA)
Operation20 h
Display128 x 64 dots matrix display with backlight
CommunicationRS232 (PS/2), USB (type B)
Overvoltage categoryCAT III / 600 V; CAT IV / 300 V
Protection degreecase IP 40
Dimensions / weight230 mm x 103 mm x 115 mm / 1.1 kg
Supplied with
MI 3110 Standard setInstrument EurotestIM; Soft carrying bag; Mains measuring cable; Test lead, 3 x 1.5 m; Test probe, 3 pcs; Crocodile clip, 3 pcs; Set of carrying straps; RS232-PS/2 cable; USB cable; Set of NiMH battery cells; Power supply adapter; Calibration certificate; Short instruction manual; Instruction manual; PC Software; EuroLink PRO* (SW 0101)

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.