Rishabh Xmer 74W(45) Wound Primary Square Current Transformer
- Brand
- Rishabh
- Model number
- Xmer 74W(45)
Rish Xmer 74W(45) square wound primary CT in UL 94V-0 polycarbonate: primary 1 A to 60 A / 5 A, classes 0.2, 0.5, 1.0, wire sealable terminal covers.
Price and availability on request
Key features
- Square polycarbonate case, UL 94V-0
- M5 terminals (1.5 Nm)
- Wire sealable terminal covers
- Classes 0.2 / 0.2S for laboratory and power measurement, 0.5 / 0.5S for kWh, 1 for general measurement, 3 for indicating instruments
Specifications
| Primary current | 1 A to 60 A (5 A secondary; 1 A on request) |
|---|---|
| Burden by class | VA by class 0.2 / 0.5 / 1.0, secondary 5 A: 1 A 1.5/5/10; 5 A 1.5/5/10; 10 A 1.5/5/10; 15 A 1.5/5/10; 20 A 1.5/5/10; 25 A 1.5/5/10; 30 A 1.5/5/10; 40 A 1.5/5/10; 50 A 1.5/5/10; 60 A 1.5/5/10 |
| Test voltage | 3 kV 50 Hz, 1 min (wound type) |
|---|---|
| Rated short-time thermal current | 40 x In |
| Instrument security factor | 5, 10, 15, 20, 30 (depends on VA burden) |
| Highest voltage for equipment | 720 V maximum |
| Rated frequency | 50 Hz / 60 Hz |
| Rated continuous thermal current | 120% of Ipr |
| Rated dynamic current | 2.5 x Ith |
| Applicable standard | IEC 61869-1&2 / IEC 60044-1, BS 3938, IS 16227-1&2 |
|---|
| Case | Unfilled polycarbonate, flame retardant, UL 94V-0 |
|---|---|
| Insulation class | E (120 °C max.) |
| Ambient temperature | -25 °C to +40 °C |
|---|---|
| Storage temperature | -50 °C to +80 °C |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.