Specifications

Rating
Primary current75 A to 600 A / 100 mA
Burden1 to 7.5 VA; class 1 or 0.5
Burden (class 1 / class 0.5)75 A 1/- VA; 80 A 1.5/- VA; 100 A 2.5/1 VA; 120 A 2.5/1 VA; 125 A 2.5/1 VA; 150 A 3.75/2.5 VA; 200 A 5/2.5 VA; 250 A 5/5 VA; 300 A 5/5 VA; 400 A 6.25/5 VA; 500 A 6.25/5 VA; 600 A 7.5/5 VA
Standards
Applicable standardIEC 61869-1&2 / IEC 60044-1, BS 3938, IS 16227-1&2
Electrical
Highest voltage / test voltage0.72 kV / 3 kV, 50 Hz, 1 minute
Rated short-time thermal current40 x In
Design
CasePolycarbonate, UL94V-0
General
Operating temperature-25 °C to +40 °C
Ordering
Order code prefixXJ53