Rishabh 1P RJ12 62-40(40) Single Phase RJ12 Current Transformer, 100 mA Output

Brand
Rishabh
Model number
1P RJ12 62-40(40)

Single phase square CT 62-40(40) with 100 mA secondary on an RJ12 socket and cable for Rishabh RJ12 meters: 100 A to 800 A primary, class 1 or 0.5, open-circuit protected.

Price and availability on request

Request a quote

Sent with the product details: Rishabh 1P RJ12 62-40(40) Single Phase RJ12 Current Transformer, 100 mA Output.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • RJ12 socket and connection cable (2 m standard) for fast, error free wiring to the meter
  • Bus bar, wall or universal DIN rail mounting
  • Sealing cap for tamper proof connection
  • Open-circuit protection

Specifications

Rating
Primary current100 A to 800 A / 100 mA
Burden1.5 to 10 VA; class 1 or 0.5
Burden (class 1 / class 0.5)100 A 1.5/- VA; 120 A 1.5/- VA; 125 A 1.5/- VA; 150 A 2.5/- VA; 200 A 3.75/1.5 VA; 250 A 5/2.5 VA; 300 A 5/5 VA; 400 A 5/5 VA; 500 A 7.5/5 VA; 600 A 10/7.5 VA; 750 A 10/10 VA; 800 A 10/10 VA
Standards
Applicable standardIEC 61869-1&2 / IEC 60044-1, BS 3938, IS 16227-1&2
Electrical
Highest voltage / test voltage0.72 kV / 3 kV, 50 Hz, 1 minute
Rated short-time thermal current40 x In
Design
CasePolycarbonate, UL94V-0
General
Operating temperature-25 °C to +40 °C
Ordering
Order code prefixXJ64

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.