Rishabh Xmer 130/100(50) Window (Ring) Type Square Current Transformer

Brand
Rishabh
Model number
Xmer 130/100(50)

Rish Xmer 130/100(50) square window CT in UL 94V-0 polycarbonate: primary 600 A to 3000 A / 5 A, classes 0.2S/0.5S, 0.2, 0.5, 1.0, wire sealable terminal covers.

Price and availability on request

Request a quote

Sent with the product details: Rishabh Xmer 130/100(50) Window (Ring) Type Square Current Transformer.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Square polycarbonate case, UL 94V-0
  • Two connections on each side: M4 screws with self lifting clamp straps
  • Wire sealable terminal covers
  • Classes 0.2 / 0.2S for laboratory and power measurement, 0.5 / 0.5S for kWh, 1 for general measurement, 3 for indicating instruments

Specifications

Rating
Primary current600 A to 3000 A (5 A secondary; 1 A on request)
Burden by classVA by class 0.2S/0.5S / 0.2 / 0.5 / 1.0, secondary 5 A: 600 A 2.5/2.5/5/10; 750 A 3.75/5/10/10; 800 A 5/7.5/10/10; 1000 A 7.5/10/15/15; 1200 A 10/10/15/15; 1250 A 10/10/15/15; 1500 A 10/15/15/15; 1600 A 10/15/15/15; 2000 A 10/15/15/15; 2500 A 10/15/15/15; 3000 A 12.5/15/15/15
Electrical
Test voltage4 kV 50 Hz, 1 min
Rated short-time thermal current60 x In
Instrument security factor5, 10, 15, 20, 30 (depends on VA burden)
Highest voltage for equipment720 V maximum
Rated frequency50 Hz / 60 Hz
Rated continuous thermal current120% of Ipr
Rated dynamic current2.5 x Ith
Standards
Applicable standardIEC 61869-1&2 / IEC 60044-1, BS 3938, IS 16227-1&2
Design
CaseUnfilled polycarbonate, flame retardant, UL 94V-0
Insulation classE (120 °C max.)
General
Ambient temperature-25 °C to +40 °C
Storage temperature-50 °C to +80 °C

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.