Epoxy resin cast protection CT LTRC-5 (165/115(40)), class 5P with accuracy limit factor 5 or 10, 5 A or 1 A secondary, transparent terminal cover, wall mounting.
Price and availability on request
Key features
- Epoxy resin cast ring type protection CT
- Transparent cover with IP20 protection to terminals
- Engraved terminal marking; self lifting terminal clamps
- Wall mounting
Specifications
| Secondary 5 A | 1250/5 2.5 VA 5P5; 1500/5 3.75 VA 5P5; 1600/5 5 VA 5P5 |
|---|---|
| Secondary 1 A | 1250/1 7.5 VA 5P5; 1500/1 7.5 VA 5P5; 1600/1 10 VA 5P5; 1250/1 1.75 VA 5P10; 1500/1 2.5 VA 5P10 |
| Class | 5P, accuracy limit factor 5 and 10; burden 1 VA to 45 VA |
| Primary current (series) | 100 A to 5000 A; secondary 5 A or 1 A |
| Applicable standard | IEC 61869-1 & 2 |
|---|
| Rated insulation level / test voltage | 0.72 / 3 kV; 3 kV 50 Hz, 1 minute |
|---|---|
| Rated short time thermal current | 60 x In for 1 s (max. 40 kA for 1 s) |
| Operating frequency | 50 / 60 Hz |
| Ambient temperature | -20 °C to 45 °C |
|---|---|
| Storage temperature | -50 °C to 80 °C |
| Order code prefix | XRC5 |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.