Three channel transducer: up to 3 AC current (to 10 A) or voltage (to 750 V) inputs converted to 3 isolated-from-supply DC current or voltage outputs; class 0.5, AC or DC auxiliary.
Price and availability on request
Key features
- Up to 3 AC current or AC voltage inputs, average measuring, calibrated to RMS for sine wave
- Three DC current (load independent) or DC voltage outputs
- Low power consumption: smaller CTs and VTs can be used
- Isolation 3.7 kV between input / output and supply, 500 V between channels
- Top-hat rail or wall / panel mounting; SMD construction
Specifications
| Basic accuracy | Class 0.5 (DIN / IEC 688-1); linearity 0.2% |
|---|---|
| Response time | < 300 ms |
| Ranges | 0…20 mA or 0…15 V |
|---|
| Auxiliary | 110 or 230 V AC ±15%, 85…230 V AC/DC or 24…60 V AC/DC; approx. 8 VA |
|---|
| Operating temperature | -25 to +55 °C |
|---|---|
| Storage temperature | -40 to +70 °C |
| Housing | Carrying rail housing E16, Lexan 940, IP 40 |
| Weight | Approx. 0.9 kg |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.