Metrel MD 9070 Insulation / Continuity Digital Multimeter

Brand
Metrel
Model number
MD 9070

TRMS multimeter with built-in insulation tester: 50 V to 1000 V insulation up to 25.0 GΩ, 200 mA earth continuity, TRMS and VFD AC voltage, DC voltage, resistance, diode and frequency.

Price and availability on request

Request a quote

Sent with the product details: Metrel MD 9070 Insulation / Continuity Digital Multimeter.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • TRMS measurement
  • Insulation resistance measurement
  • Earth continuity measurement
  • Resistance measurement
  • Diode test
  • Mains supply frequency measurement
  • Frequency of digital signals measurement
  • TRMS: accurate readings on sinusoidal and non-sinusoidal signals
  • VFD: feature makes the instrument capable of measuring the true values in accordance with frequency
  • Auto-ranging: user can switch between auto and manual ranging
  • Relative zero mode: relative function for comparing the difference between signals or removing background noise
  • MAX/MIN: recording of maximum, minimum and average values
  • Data Hold: data hold feature freezes the display for later view
  • PI/DAR: feature
  • Safety: CAT IV / 600 V and CAT III / 1000 V overvoltage protection
  • Backlight: working in dark conditions

Specifications

Insulation
Insulation resistance at 50 / 100 / 250 / 500 / 1000 V3.000 MΩ ... 25.0 GΩ (1000 V); ±⁠(1.5% of reading + 5 digits)
Continuity
Earth continuity test0.015 Ω ... 2.199 Ω at Itest > 200 mA; 0.15 Ω ... 21.99 Ω at Itest > 90 mA; ±⁠(1.5% of reading + 3 digits)
Measurement
TRMS AC voltage (50 Hz ~ 5 kHz)6.000 V ... 1000 V; from ±⁠(1.0% of reading + 3 digits)
VFD AC voltage (10 Hz ~ 440 Hz)600.0 V
DC voltage6.000 V ... 1000 V; from ±⁠(0.2% of reading + 3 digits)
Ohms600.0 Ω ... 60.00 MΩ; from ±⁠(0.9% of reading + 2 digits)
Frequency10 Hz ... 20 kHz; ±⁠(0.02% of reading + 4 digits)
General
Power supplyFour alkaline AA batteries (IEC LR6)
Overvoltage categoryCAT IV / 600 V and CAT III / 1000 V
Dimensions / weight208 x 103 x 64.5 mm / 635 g with holster
Supplied with
MD 9070 Standard setMultimeter; MD 9070 with rubber holster; Test lead with probe, 2 pcs; Insulated crocodile clip, 2 pcs; Insulation/Continuity test lead with probe, 1 pcs; 1,5 V AA battery (IEC LR6), 4 pcs; User manual

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.