Masibus 9000Ex-31 / 9000Ex-32 Smart Current Driver
- Brand
- Masibus
- Model number
- 9000Ex-31 / 9000Ex-32
- Category
- Signal Conditioners
Masibus 9000Ex-31 / 9000Ex-32 smart current driver: input Current, output Current. For used in industrial automation, control of valves positioner in hazardous area.
Price and availability on request
Key features
- Intrinsically safe Associated Device
- Line fault detection (LFD)
- Compact DIN-Rail mount design of 17.6mm width
- High KV 3 port isolation
- High Accuracy, low drift, low temperature effect
- Low power dissipation
- Bi-Directional HART communication between the hazardous and non-hazardous area
Specifications
| Input Type | Current |
|---|---|
| Input Range | 4 to 20mA |
| No. of channel | One |
| Voltage Drop | Approx. 6 V at 20 mA |
| Temperature Coefficient | ≤50 ppm/°C |
| CMRR | ≥ 100 dB |
| NMRR | ≥ 70 dB |
| Output Type | Current |
|---|---|
| Output Range | 4 to 20mA |
| Response Time | ≤100ms |
| Output Load Resistance | 100 Ω to 650Ω @20mA |
| Line Fault Detection (LFD) | Field wiring open circuit or ≤50 Ω (Short Circuit) then the input current ≤1.2 mA (Short Circuit LFD is available with 9000Ex-31) |
| Communication Supported | HART pass supported |
| Voltage | 20 to 35 VDC |
|---|---|
| Power Consumption (20mA signal) | ≤1W@24V |
| Power Dissipation (20mA signal) | ≤0.74W@24V |
| Power ON status LED | Red |
| Terminal Block | UL, CSA standard |
|---|---|
| Terminal Cable Size | 2.5mm2 |
| Enclosure Material | PA66 |
| IP Rating | IP20 |
| Dimension (in mm) | 17.6(W)x108(H)x114(D) mm |
| Weight | ≤ 150 g |
| Terminals OP+ to OP- | Uo=28V Io=91mA Po=0.65W Um=250V rms |
|---|---|
| Certificate Report No. | KLPL/Ex/25-025X |
| PESO Approval No. | A/P/HQ/GA/104/5532 |
| Ex Standards Complied | IS/IEC 60079-0:2017 IS/IEC 60079-11:2023 For Details, Please refer Operational Manual |
| Operating Temperature | -20 to 60 °C |
|---|---|
| Storage Temperature | -20° to 70°C |
| Relative Humidity | 30 to 95% RH (Non-Condensing) |
| Protection | Conformal Coating on PCB |
| Applications | Used for I/P Converter, control valve and other field devices exposed to explosive atmosphere, Transmitting control signals to transmitter measuring Temperature, Pressure or Flow, Used in industrial automation, Control of Valves Positioner in Hazardous area, Monitoring and Controlling operation in potential explosive environment, Prevents electrical noise, ground loops, and voltage spike |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.