Masibus 9000Ex-1/Ex-2 Signal Isolator

Brand
Masibus
Model number
9000Ex-1/Ex-2

Masibus 9000Ex-1/Ex-2 signal isolator: input Curr / ent, output Current. For safety barrier for analog current signals, isolation of process field signals.

Price and availability on request

Request a quote

Sent with the product details: Masibus 9000Ex-1/Ex-2 Signal Isolator.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Intrinsically safe Associated Device
  • Compact DIN-Rail mount design of 17.6mm width
  • 2W transmitter input with HART Pass
  • High KV 3 port isolation of each channel
  • High Accuracy, low drift, low temperature effect
  • Input and Output well protected
  • Fast response suits all applications
  • Low power dissipation

Specifications

Hazardous-area Input
Input typeCurr / ent
Input Range4 to 20mA
Input Impedance≤ 30Ω
Temperature Coefficient≤ 50 ppm/°C ≥
CMRR≥ 100 dB
NMRR≥ 70 dB
No. of IO channels9000Ex-1: One 9000Ex-2: Two
Location of TransmitterZone 0, IIC, T4-6 hazardous area if suitably certified Div. 1, Group A hazardous location
Transmitter Power SupplyOpen circuit voltage: ≥24VDC Available voltage: ≥ 23VDC @ 4mA, ≥ 16VDC @ 20mA
Communications SupportedHART pass supported in both channels* *HART Pass supported with 2W transmitter only
Safe-area Output
Output TypeCurrent
Output Range4 to 20mA
Response Time≤ 50µS
Output Load Resistance≤ 450Ω@20mA
Power Supply
Voltage20 to 35 VDC
Power Consumption (20mA Signal) Power Dissipation9000Ex-1: ≤1.3W @ 24VDC 9000Ex-2: ≤2.5W @ 24VDC Or 9000Ex-1: ≤0.8W @ 24VDC
(20mA Signal)9000Ex-2: ≤1.5W @ 24VDC
Power ON status LEDRed
Isolation (Withstanding voltage)
Between Power to Inputs and OutputsGalvanic Isolation of 2KVAC for 1 minute
Between Inputs to OutputsGalvanic Isolation of 2KVAC for 1 minute
Between Input to InputGalvanic Isolation of 2KVAC for 1 minute
Between Output to OutputGalvanic Isolation of 2KVAC for 1 minute Insulation resistance: >200MΩ@1000V DC between All Ports.
Physical
Mounting TypeDIN Rail (35 mm)
Terminal BlockUL, CSA standard
Terminal Cable Size2.5mm2
Enclosure MaterialPA66
IP RatingIP20
Dimension (in mm)17.6(W)x108(H)x114(D) mm
Weight≤ 150 g
Environmental
Operating Temperature-20 to 60 °C
Storage Temperature-20° to 70 °C
Relative Humidity30 to 95% RH (Non-Condensing)
ProtectionConformal Coating on PCB
Safety Description (Each Channel)
Terminals TPS to IP+ / IP-Uo=28V Io=93mA Po=651mW Um = 253V rms or dc
Terminals IP+ to IP-Simple apparatus ≤1.5V, ≤0.1A and ≤25mW; can be connected without further certification into any IS loop with an open-circuit voltage <28V
Certificate Report No.KLPL/Ex/23-78X, Issue No.00
PESO Approval No.A/P/HQ/GA/104/5522
Ex Standards CompliedIS/IEC 60079-0:2017 IS/IEC 60079-11:2011 For Details, Please refer Operational Manual
Product
ApplicationsEnergising 2-WIre Transmitter located in Hazardous Area, Safety barrier for analog current signals, Isolation of process field signals, Distribution of signals in Automation Panels, Impedance matching of transmitters and receiver instruments

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.