Fluke 1555 FC 10 kV Insulation Tester
- Brand
- Fluke
- Model number
- 1555 FC
- Category
- Insulation Resistance Testers
10 kV insulation tester for switchgear, motors, generators and cables, with Fluke Connect remote operation.
Price and availability on request
Key features
- Quickly configure, start and stop tests on the 1555 remotely, a safe distance away from any operating, energized equipment, using Fluke Connect and a smart phone
- Real time trending gives you easy-to-see visual cues, rather than hard to read, rapidly changing values
- Report creation using Fluke Connect desktop saves time and makes test results easier to understand
- Fluke Connect saves test results to the cloud for analysis and preventive maintenance
Specifications
| 250 V, Range | < 250 kΩ, 250 kΩ to 5 GΩ; 5 GΩ to 50 GΩ; > 50 GΩ |
|---|---|
| 250 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| 500 V, Range | < 500 kΩ; 500 kΩ to 10 GΩ; 10 GΩ to 100 GΩ; > 100 GΩ |
| 500 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| 1000 V, Range | < 1 MΩ; 1 MΩ to 20 GΩ; 20 GΩ to 200 GΩ; > 200 GΩ |
| 1000 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| 2500 V, Range | < 2.5 MΩ; 2.5 MΩ to 50 GΩ; 50 GΩ to 500 GΩ; > 500 GΩ |
| 2500 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| 5000 V, Range | < 5 MΩ; 5 MΩ to 100 GΩ; 100 GΩ to 1 TΩ; > 1 TΩ |
| 5000 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| 10000 V, Range | < 10 MΩ; 10 MΩ to 200 GΩ; 200 GΩ to 2 TΩ; > 2 TΩ |
| 10000 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| Bar graph range | 0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555) |
| Insulation test voltage accuracy | -0%, +10% at 1 mA load current |
| Induced AC mains current rejection | 2 mA maximum |
| Charging rate for capacitive load | 5 seconds per μF |
| Discharge rate for capacitive load | 1.5 s/μF |
| Leakage current measurement, Range | 1 nA to 2 mA |
| Leakage current measurement, Accuracy | ±(5% + 2 nA) |
| Capacitance measurement, Range | 0.01 μF to 15.00 μF |
| Capacitance measurement, Accuracy | ±(15% rdg + 0.03 μF) |
| Timer, Range | 0 to 99 minutes |
| Timer, Resolution setting | 1 minute |
| Timer, Resolution indication | 1 second |
| Live circuit warning, Warning range | 30 V to 660 V AC/DC, 50/60 Hz |
| Live circuit warning, Voltage accuracy | ±(15% + 2 V) |
| Software specifications | FlukeView Forms basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8. |
| Display | 75 x 105 mm |
|---|---|
| Power | 12 V lead-acid rechargeable battery, Yuasa NP2.8-12 |
| Charger Input (AC) | 85 V to 250 V AC 50/60 Hz 20 VA |
| Dimensions | 269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in) |
| Weight | 3.7 kg (8.2 lb) |
| Temperature (operating) | -20°C to 50°C (-4°F to 122°F) |
| Temperature (storage) | -20°C to 65°C (-4°F to 149°F) |
| Humidity | 80% to 31°C decreasing linearly to 50% at 50°C |
| Altitude | 2000 m |
| Enclosure sealing | IP40 |
| Input overload protection | 1000 V AC |
| Safety compliance | IEC 61010-1: Overvoltage category II, Pollution Degree 2.; IEC 61010-2-030: Measurement 600V CAT IV; 1000V CAT III; IEC 61557-1, IEC 61557-2 |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.
About the 1555 FC
The Fluke 1555 FC tests insulation up to 10 kV on high-voltage equipment such as switchgear, motors, generators and cables. It can be operated remotely through the Fluke Connect app, with real-time trending on the phone and easy data collection.