Fluke 1550C FC KIT 5 kV Insulation Tester Kit
- Brand
- Fluke
- Model number
- 1550C FC KIT
- Category
- Insulation Resistance Testers
Fluke 1550C 5 kV insulation tester kit with IP67 hard case and calibration certificate; Fluke Connect remote testing.
Price and availability on request
Key features
- Quickly configure, start and stop tests on the 1550C remotely, a safe distance away from any operating, energized equipment, using Fluke Connect and a smart phone
- Real time trending gives you easy-to-see visual cues, rather than hard to read, rapidly changing values
- Report creation using Fluke Connect desktop saves time and makes test results easier to understand
- Fluke Connect saves test results to the cloud for analysis and preventive maintenance
Specifications
| 250 V, Range | < 250 kΩ, 250 kΩ to 5 GΩ; 5 GΩ to 50 GΩ; > 50 GΩ |
|---|---|
| 250 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| 500 V, Range | < 500 kΩ; 500 kΩ to 10 GΩ; 10 GΩ to 100 GΩ; > 100 GΩ |
| 500 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| 1000 V, Range | < 1 MΩ; 1 MΩ to 20 GΩ; 20 GΩ to 200 GΩ; > 200 GΩ |
| 1000 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| 2500 V, Range | < 2.5 MΩ; 2.5 MΩ to 50 GΩ; 50 GΩ to 500 GΩ; > 500 GΩ |
| 2500 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| 5000 V, Range | < 5 MΩ; 5 MΩ to 100 GΩ; 100 GΩ to 1 TΩ; > 1 TΩ |
| 5000 V, Accuracy (± reading) | Unspecified; 5%; 20%; Unspecified |
| Bar graph range | 0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555) |
| Insulation test voltage accuracy | -0%, +10% at 1 mA load current |
| Induced AC mains current rejection | 2 mA maximum |
| Charging rate for capacitive load | 5 seconds per μF |
| Discharge rate for capacitive load | 1.5 s/μF |
| Leakage current measurement, Range | 1 nA to 2 mA |
| Leakage current measurement, Accuracy | ±(20% + 2 nA) |
| Capacitance measurement, Range | 0.01 μF to 15.00 μF |
| Capacitance measurement, Accuracy | ±(15% rdg + 0.03 μF) |
| Timer, Range | 0 to 99 minutes |
| Timer, Resolution setting | 1 minute |
| Timer, Resolution indication | 1 second |
| Live circuit warning, Warning range | 30 V to 660 V AC/DC, 50/60 Hz |
| Live circuit warning, Voltage accuracy | ±(15% + 2 V) |
| Software specifications | FlukeView Forms basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8. |
| Display | 75 x 105 mm |
|---|---|
| Power | 12 V lead-acid rechargeable battery, Yuasa NP2.8-12 |
| Charger Input (AC) | 85 V to 250 V AC 50/60 Hz 20 VA |
| Dimensions | 269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in) |
| Weight | 3.7 kg (8.2 lb) |
| Temperature (operating) | -20°C to 50°C (-4°F to 122°F) |
| Temperature (storage) | -20°C to 65°C (-4°F to 149°F) |
| Humidity | 80% to 31°C decreasing linearly to 50% at 50°C |
| Altitude | 2000 m |
| Enclosure sealing | IP40 |
| Input overload protection | 1000 V AC |
| Safety compliance | IEC 61010-1: Overvoltage category II, Pollution Degree 2.; IEC 61010-2-030: Measurement 600V CAT IV; 1000V CAT III; IEC 61557-1, IEC 61557-2 |
| Contents | Test cables with alligator clips (red, black, green); Infrared adapter with interface cable; AC power cord; IP67 hard case; Certificate of calibration; English manual; User's manual on CD-ROM; Quick reference card |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.
About the 1550C FC KIT
This kit supplies the Fluke 1550C 5 kV digital insulation tester in an IP67 hard case with a calibration certificate. Tests can be run remotely through the Fluke Connect app, with real-time trending on the phone.