CIE/7080 MOT Transformer Oil Test Set 0-80kV, Motor Operated

Brand
CIE
Model number
CIE/7080 MOT

Oil breakdown voltage (BDV) test set to IS 6792:1992 for transformer and switchgear oil: 0-80 kV, 800 VA, cast resin HV transformer, motor operated version, brass electrodes with 2.5 / 4 mm gap and interlocked chamber.

Price and availability on request

Request a quote

Sent with the product details: CIE/7080 MOT Transformer Oil Test Set 0-80kV, Motor Operated.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Continuously Variable Output
  • Digital kV Display
  • Memory Breakdown Voltage
  • Cast Resin H.V. Transformer
  • Adjustable Oil Cell
  • Smooth Voltage Regulation
  • Zero Start Interlock
  • Chamber Safety Interlock
  • IS 6792:1992 Compliant
  • Both analog and digital display models available.
  • Zero Start Interlock: Prevents energizing unless regulator is at zero position.
  • Overload Protection: Automatic tripping in case of overload or breakdown of oil sample.
  • Transparent Safety Chamber: Interlocked transparent cover ensures safe operation and prevents accidental contact.
  • Precision Oil Test Cell: Non-absorbent cell with adjustable brass electrodes & gap gauge as per IS 6792:1992.

Specifications

Specifications
Applicable StandardIS 6792:1992
Output VoltageContinuously Variable (Model Dependent)
Transformer TypeCast Resin High Voltage Transformer with Centre Point Grounded
Voltage RegulationVariable Autotransformer for smooth and continuous control
MeteringAnalog or Digital kV Display (As per model)
Test CellNon-absorbent insulating material
Electrode TypeTwo Brass Spherical Electrodes (Ø 12.5 – 13 mm)
Electrode GapAdjustable: 2.5 mm / 4 mm
Input Supply230V AC ±10%, 50Hz, Single Phase
Available VersionsManual Operated / Motor Operated
DutyIntermittent (5 min ON / 10 min OFF)
Ranges
Output voltage0 – 80 kV AC
Capacity800 VA
OperationMotor operated
Accessories
Supplied withInstruction manual and calibration certificate
Options
Available on orderSet housed in 2 units; Capacity doubled, i.e. 20mA instead of 10mA (0-50 KV to 0-80 KV oil test sets only); Digital meter; Magnetic stirrer; Other duty cycle and capacity on special enquiry
Applications
Ideal forTransformer Manufacturing, Power Utilities, Testing Laboratories, Industrial Plants, Switchgear Industry, Electrical Maintenance, Power Distribution, Quality Control

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.