Phoenix Contact TRIO3-PS/3AC/48DC/20 TRIO3-PS/3AC/48DC/20 Power Supply
- Brand
- Phoenix Contact
- Model number
- TRIO3-PS/3AC/48DC/20
- Category
- DIN-Rail Power Supplies
Primary-switched power supply unit TRIO POWER, Push-in connection, DIN rail mounting, input: 3-phase, output: 48 V DC / 20 A, adjustable from 40 V DC ... 56 V DC
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Output 48 V DC, 20 A (960 W)
- Input 3x 400 V AC ... 500 V AC
- Efficiency typ. 96.1 % (3x 400 V AC)
- Width 90 mm
- Operating temperature -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K)
- Degree of protection IP20
Specifications
| Supply system configuration | Star network (TN, TT, IT (PE)) |
|---|---|
| Nominal input voltage range | 3x 400 V AC ... 500 V AC |
| Input voltage range | 3x 400 V AC ... 500 V AC -20 % ... +10 %; 2x 400 V AC ... 500 V AC ±10 % |
| Typical national grid voltage | 3x 400 V AC; 3x 480 V AC |
| Voltage type of supply voltage | AC |
| Inrush current | < 21 A (25 °C) |
| Inrush current integral (I2t) | < 0.94 A2s |
| Frequency range (fN) | 50 Hz ... 60 Hz |
| Mains buffering time | typ. 34 ms (3x 400 V AC); typ. 34 ms (3x 480 V AC) |
| Current consumption | 3x 1.5 A (3x 400 V AC); 3x 1.2 A (3x 500 V AC); 2x 2.6 A (2x 400 V AC); 2x 2.1 A (2x 500 V AC) |
| Protective circuit | Transient protection; Varistor |
| Power factor | 0.94 (3x 480 V AC) |
| Device mains fuse | 6.3 A internal (device protection) |
| Recommended breaker for input protection | 3x 6 A ... 20 A (Characteristic B, C, D, K or comparable) |
| Discharge current to PE | < 3.5 mA |
| Efficiency | typ. 96.1 % (3x 400 V AC); typ. 96.3 % (3x 480 V AC) |
|---|---|
| Nominal output voltage | 48 V DC |
| Setting range of the output voltage (USet) | 40 V DC ... 56 V DC (> 48 V DC, constant capacity restricted) |
| Nominal output current (IN) | 20 A |
| Dynamic Boost (IDyn.Boost) | max. 30 A (5 s) |
| Short-circuit-proof | yes |
| No-load proof | yes |
| Derating | 60 °C ... 70 °C |
| Crest factor | typ. 1.56 (3x 400 V AC); typ. 1.57 (3x 480 V AC) |
| Output power (PN) | 960 W |
| Output power (PDyn. Boost) | max. 1440 W (5 s) |
| Connection in parallel | yes, for increased efficiency and redundancy |
| Connection in series | yes, for increased output voltage (observe SELV limit) |
| Feedback voltage resistance | ≤ 60 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 60 V DC |
| Residual ripple | typ. 50 mVPP (with nominal values) |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %); < 3 % (change in load, dynamic 10 % ... 90 %); < 0.1 % (change in input voltage ±10 %) |
| Rise time | ≤ 1 s (UOut = 10 % ... 90 %) |
| Minimum no-load power dissipation | < 0.3 W (3x 400 V AC) |
| Maximum no-load power dissipation | < 0.26 W (3x 480 V AC) |
| Minimum nominal load power dissipation | < 43.21 W (3x 400 V AC) |
| Power loss nominal load max. | < 35.65 W (3x 480 V AC) |
| Integrated fuse protection | no |
| Fuse protection (secondary side) | electronic |
| Position | 1.x |
|---|
| Position marking | 1.1 (L1), 1.2 (L2), 1.3 (L3), 1.4 (); 2.1, 2.2 (+), 2.3, 2.4, 2.5 (-); 3.1 (13), 3.2 (14) |
|---|
| Connection method | Push-in connection |
|---|---|
| rigid (Terminal block) | 0.2 mm² ... 4 mm²; 0.2 mm² ... 10 mm²; 0.2 mm² ... 1.5 mm² |
| rigid (recommended) | 1.5 mm² (recommended); 4 mm² (recommended); 0.5 mm² (recommended) |
| flexible (Klemme) | 0.2 mm² ... 2.5 mm²; 0.2 mm² ... 6 mm²; 0.2 mm² ... 1.5 mm² |
| flexible (empfohlen) | 1.5 mm² (recommended); 4 mm² (recommended); 0.5 mm² (recommended) |
| flexible with ferrule without plastic sleeve (Terminal block) | 0.25 mm² ... 2.5 mm²; 0.25 mm² ... 6 mm² (Cu); 0.25 mm² ... 1.5 mm² (Cu) |
| flexible with ferrule without plastic sleeve (recommended) | 1.5 mm² (recommended); 4 mm² (recommended); 0.5 mm² (recommended) |
| flexible with ferrule with plastic sleeve (Terminal block) | 0.25 mm² ... 2.5 mm²; 0.25 mm² ... 6 mm²; 0.25 mm² ... 0.75 mm² |
| flexible with ferrule with plastic sleeve (recommended) | 1.5 mm² (recommended); 4 mm² (recommended); 0.5 mm² (recommended) |
| AWG (Terminal block) | 24 ... 12 (Cu); 24 ... 8 (Cu); 24 ... 16 (Cu) |
| AWG (recommended) | 16 (recommended); 12 (recommended); 20 (recommended) |
| Stripping length (starr/flexibel) | 10 mm (Rigid/flexible/ferrule); 12 mm (Rigid/flexible/ferrule) |
| Position | 2.x |
|---|
| Position | 3.x |
|---|
| Types of signaling | DC OK LED - signal state operation (UN = 48 V DC, IOut = IN) |
|---|---|
| Function | Visual operating state display |
| Color | red, yellow, green (multicolor LED) |
| LED off | Supply voltage input AC not present (Off) |
| LED on (green), DC OK | UOut > 36 V DC and IOut < 0.9 x IN (On (green), DC OK) |
| LED on (yellow), IOut > 90 % | UOut > 36 V DC and IOut > 0.9 x IN (On (yellow), IOut > 90% ) |
| LED on (red), ISHORT | UOut < 36 V DC and IOut > 0.9 x IN (On (red), ISHORT) |
| LED on (flashing red) OVP | UOUT > OVP (Over voltage protection) (on (flashing red)) |
| Position | 3.x |
|---|---|
| Type of signaling | DC OK switch contact - signal state operation (UN = 48 V DC, IOut = IN) |
| Position marking | 3.1 (13), 3.2 (14) |
| Function | Operating state forwarding |
| Switch contact (floating) | OptoMOS |
| Switching voltage | max. 60 V DC (SELV) |
| Current carrying capacity | max. 50 mA |
| State condition (Contact closed) | UOut > 36 V DC and IOut < 0.9 x IN (Contact closed) |
| State condition (Contact open) | UOut < 36 V DC or IOut > 0.9 x IN (averaging over 60 s) (Contact open) |
| Number of phases | 3 |
|---|---|
| Insulation voltage input/output | 3 kV AC (type test); 3.1 kV DC (routine test) |
| Product type | Power supply |
|---|---|
| Product family | TRIO POWER |
| MTBF (IEC 61709, SN 29500) | > 1100000 h (25 °C); > 660000 h (40 °C); > 270000 h (60 °C) |
| Environmental protection directive | RoHS Directive 2011/65/EU; WEEE; Reach |
| Protection class | I |
|---|---|
| Overvoltage category (EN 61010-1) | III (≤ 2000 m); II (≤ 5000 m) |
| Overvoltage category (EN 61010-2-201) | III (≤ 2000 m); II (≤ 5000 m) |
| Degree of pollution | 2 |
| Width | 90 mm |
|---|---|
| Height | 135 mm |
| Depth | 167 mm |
| Depth (Device depth (DIN rail mounting)) | 160 mm (Device depth (DIN rail mounting)) |
| Installation distance right/left | 0 mm / 0 mm |
|---|---|
| Installation distance top/bottom | 50 mm / 50 mm |
| Mounting type | DIN rail mounting |
|---|---|
| Assembly note | alignable - horizontally 0 mm, vertically 50 mm |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Flammability rating according to UL 94 | V0 (Housing, terminal blocks) |
|---|---|
| Hood version | Polycarbonate |
| Side element version | Aluminum |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Ambient temperature (start-up type tested) | -40 °C |
| Maximum altitude (Maximum) | ≤ 5000 m |
| Maximum altitude (Output power derating) | > 2000 m (Derating - 10%/1000 m) |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Shock (operation) | 18 ms, 30g, per spatial direction (IEC 60068-2-27) |
| Vibration (operation) | 10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6); 50 Hz ... 150 Hz, 2.3g, 90 min. |
| Temp code | T4 (-25 ... +70 °C; > 60 °C, Derating - 2,5 %/K) |
| Standard designation | Safety of power supply units up to 1100 V (insulation distances) |
|---|---|
| Standards/specifications | DIN EN 61558-2-16 |
| Standard designation | Electrical safety |
|---|---|
| Standards/specifications | IEC 61010-2-201 (SELV) |
| Standard designation | Safety for equipment for measurement, control, and laboratory use |
|---|---|
| Standards/specifications | IEC 61010-1 |
| Standard designation | Safety extra-low voltage |
|---|---|
| Standards/specifications | IEC 61010-1 (SELV) |
| Standard designation | Protective extra-low voltage |
|---|---|
| Standards/specifications | IEC 61010-2-201 (PELV) |
| Standard designation | Safe isolation |
|---|---|
| Standards/specifications | IEC 61558-2-16; IEC 61010-2-201 |
| Standard designation | Limitation of harmonic line currents |
|---|---|
| Standards/specifications | EN 61000-3-2 |
| Standard designation | Mains variation/undervoltage |
|---|---|
| Standards/specifications | SEMI F47; EN 61000-4-11 |
| Identification | UL/C-UL Listed UL 61010-1; UL/C-UL Listed UL 61010-2-201 |
|---|
| Identification | PROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS; (EN) This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only.(FR) Cet appareil convient uniquement pour une utilisation en atmosphères explosibles de classe I, division 2, groupes A, B, C et D ou en atmosphères non explosibles.; (EN) WARNING - Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
Model numbers in this series (1)
Send us the complete code you need and we will quote it.
1362784
About the TRIO3-PS/3AC/48DC/20
TRIO POWER power supply for DIN-rail mounting with standard functionality. Primary-switched power supply unit TRIO POWER, Push-in connection, DIN rail mounting, input: 3-phase, output: 48 V DC / 20 A, adjustable from 40 V DC ... 56 V DC Order no. 1362784.