Phoenix Contact QUINT-PS/1AC/24DC/5/CO QUINT-PS/1AC/24DC/5/CO Power Supply, with Protective Coating
- Brand
- Phoenix Contact
- Model number
- QUINT-PS/1AC/24DC/5/CO
- Category
- DIN-Rail Power Supplies
Please use the following item for new projects: 2904616 QUINT4-PS/1AC/24DC/10/+. Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 24 V DC / 5 A…
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Output 24 V DC ±1 %, 5 A (-25 °C ... 60 °C, UOUT = 24 V DC)
- Input 100 V AC ... 240 V AC
- Efficiency typ. 88.3 % (120 V AC)
- Width 40 mm
- Operating temperature -40 °C ... 70 °C (> 60 °C Derating - 2,5 %/K)
- Degree of protection IP20
Specifications
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| Input voltage range | 85 V AC ... 264 V AC |
| Electric strength, max. | 300 V AC |
| Voltage type of supply voltage | AC |
| Inrush current | < 15 A |
| Inrush current integral (I2t) | < 1 A2s |
| Inrush current limitation | 15 A |
| AC frequency range | 45 Hz ... 65 Hz |
| Frequency range DC | 0 Hz |
| Mains buffering time | typ. 55 ms (120 V AC); typ. 55 ms (230 V AC) |
| Current consumption | 1.5 A (100 V AC); 0.6 A (240 V AC) |
| Nominal power consumption | 141 VA |
| Protective circuit | Transient surge protection; Varistor |
| Typical response time | < 0.15 s |
| Input fuse | 5 A (slow-blow, internal) |
| Permissible backup fuse | B6 B10 B16 AC- |
| Recommended breaker for input protection | 6 A ... 16 A (AC - Characteristics B, C, D, K) |
| Discharge current to PE | < 3.5 mA |
| Nominal input voltage range | 110 V DC ... 250 V DC |
|---|---|
| Input voltage range | 110 V DC ... 250 V DC -18 % ... +64 % (UL 508 - ≤ 250 V DC) |
| Voltage type of supply voltage | DC |
| Current consumption | 1.3 A (110 V DC); 0.55 A (250 V DC) |
| Efficiency | typ. 88.3 % (120 V AC); typ. 90 % (230 V AC) |
|---|---|
| Nominal output voltage | 24 V DC ±1 % |
| Setting range of the output voltage (USet) | 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity) |
| Nominal output current (IN) | 5 A (-25 °C ... 60 °C, UOUT = 24 V DC) |
| POWER BOOST (IBoost) | 7.5 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC ) |
| Selective Fuse Breaking (ISFB) | 30 A (12 ms) |
| Magnetic circuit breaker tripping | B2 / B4 / C2 |
| Derating | 60 °C ... 70 °C (2.5 %/K) |
| Feedback voltage resistance | ≤ 35 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 32 V DC |
| Control deviation | < 1 % (change in load, static 10 % ... 90 %); < 2 % (change in load, dynamic 10 % ... 90 %); < 0.1 % (change in input voltage ±10 %) |
| Residual ripple | < 40 mVPP (with nominal values) |
| Output power | 120 W; 180 W |
| Maximum no-load power dissipation | 3 W |
| Power loss nominal load max. | 15 W |
| Rise time | < 0.1 s (UOUT (10 % ... 90 %)) |
| Connection in parallel | yes, for redundancy and increased capacity |
| Connection in series | yes |
| Fuse protection (secondary side) | electronic; thermal-magnetic; thermal |
| Output description | UOUT > 0.9 x UN - High signal |
|---|---|
| Switching voltage range | 18 V DC ... 24 V DC |
| Maximum inrush current | 20 mA (short-circuit-proof) |
| Continuous load current | ≤ 20 mA |
| Output description | Relay contact, UOUT > 0.9 x UN - Contact closed |
|---|---|
| Maximum switching voltage | 30 V AC; 24 V DC |
| Maximum inrush current | 0.5 A (ATEX/IECEx - Ohmic loads only); 1 A (ATEX/IECEx - Ohmic loads only) |
| Continuous load current | 1 A |
| Output description | IOUT < IN - High signal |
|---|---|
| Switching voltage range | 18 V DC ... 24 V DC |
| Output voltage | + 24 V DC |
| Maximum inrush current | 20 mA (short-circuit-proof) |
| Continuous load current | ≤ 20 mA |
| Connection method | Screw connection |
|---|---|
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Conductor cross-section AWG min. | 20 |
| Conductor cross-section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Connection method | Screw connection |
|---|---|
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Conductor cross-section AWG min. | 20 |
| Conductor cross-section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Conductor cross-section, rigid min. | 0.2 mm² |
|---|---|
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Conductor cross-section AWG min. | 20 |
| Conductor cross-section AWG max. | 12 |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Types of signaling | LED; Active switching output; Relay contact |
|---|
| Status display | UOUT > 0.9 x UN - "DC OK" LED green |
|---|---|
| Note on status display | UOUT < 0.9 x UN - Flashing "DC OK" LED; IOUT < IN - LED ON; LED flashing |
| Color | green |
| Status display | UOUT > 0.9 x UN - "DC OK" LED green |
|---|---|
| Note on status display | UOUT < 0.9 x UN - Flashing "DC OK" LED; LED flashing |
| Color | green |
| Status display | IOUT > IN - LED "BOOST" yellow |
|---|---|
| Color | yellow |
| Number of phases | 1 |
|---|---|
| Insulation voltage input/output | 4 kV AC (type test); 2 kV AC (routine test) |
| Insulation voltage output / PE | 850 V DC (routine test) |
| Insulation voltage input / PE | 3.5 kV AC (type test); 2 kV AC (routine test) |
| Product type | Power supply |
|---|---|
| Product family | QUINT POWER |
| MTBF (IEC 61709, SN 29500) | > 1134000 h (25 °C); > 635000 h (40 °C) |
| Protection class | I |
|---|---|
| Overvoltage category (EN 61010-1) | II (≤ 5000 m) |
| Overvoltage category (EN 62477-1) | III (≤ 2000 m) |
| Degree of pollution | 2 |
| Width | 40 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Installation distance right/left | 5 mm / 5 mm |
|---|---|
| Installation distance top/bottom | 50 mm / 50 mm |
| Width | 122 mm |
|---|---|
| Height | 130 mm |
| Depth | 43 mm |
| Mounting type | DIN rail mounting |
|---|---|
| Assembly note | alignable - PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable - PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| With protective coating | yes |
| Housing material | Metal |
|---|---|
| Hood version | Galvanized sheet steel, free from chrome (VI) |
| Side element version | Aluminum |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 70 °C (> 60 °C Derating - 2,5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 5000 m |
| Climatic class | 3K22 (in accordance with EN 60721-3-3) |
| Max. permissible relative humidity (operation) | 100 % (at 25 °C, non-condensing) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6); 15 Hz ... 150 Hz, 2.3g, 90 min. |
| Temp code | T4 (-40 ... +60 °C) |
| Rail applications | EN 50121-4; EN 50121-3-2; EN 50124-1; EN 50155 |
|---|---|
| HART FSK Physical Layer Test Specification Compliance | Output voltage UOut compliant |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Standard - Electrical safety | IEC 61010-2-201 (SELV) |
| Explosive atmosphere | EN 60079-0; EN 60079-7; EN 60079-15 |
| Standard - Equipment safety | BG (design tested) |
| Standard - Safe isolation | IEC 61010-2-201 |
| Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47-0706 Compliance Certificate |
| DeviceNet approval | DeviceNet™ Power Supply Conformance Tested |
| Standard designation | Fire protection in rail vehicles |
|---|---|
| Standards/specifications | EN 45545-2 (HL3) |
| Standard designation | Safety extra-low voltage |
|---|---|
| Standards/specifications | IEC 61010-1 (SELV) |
| Standard designation | Protective extra-low voltage |
|---|---|
| Standards/specifications | IEC 61010-2-201 (PELV) |
| CSA | CAN/CSA-C22.2 No. 60950-1-07; CSA-C22.2 No. 107.1-01 |
|---|---|
| Shipbuilding approval | DNV (EMC A) |
| SIQ | CB-Scheme (IEC 62368-1, IEC 61010-1, IEC 61010-2-201) |
| UL approvals | UL/C-UL listed UL 508; UL/C-UL Recognized UL 60950-1; UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
| DeviceNet approval | DeviceNet™ Power Supply Conformance Tested |
| Identification | Ex ec nC IIC T4 Gc |
|---|---|
| Certificate | DNV 19.0188 X |
| Identification | II 3 G Ex ec nC IIC T4 Gc |
|---|---|
| Certificate | TÜV 11 ATEX 555674 X |
| Identification | Ex ec nC IIC T4 Gc |
|---|---|
| Certificate | IECEx TUN 11.0002X |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
Model numbers in this series (2)
Send us the complete code you need and we will quote it.
2320908QUINT-PS/1AC/24DC/ 5/CO
About the QUINT-PS/1AC/24DC/5/CO
QUINT POWER power supply for DIN-rail mounting with maximum functionality. Please use the following item for new projects: 2904616 QUINT4-PS/1AC/24DC/10/+. Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 24 V DC / 5 A, adjustable from 18 V DC ... 29.5 V DC Order no. 2320908.