Phoenix Contact TRIO3-PS/3AC/24DC/40 TRIO3-PS/3AC/24DC/40 Power Supply

Model number
TRIO3-PS/3AC/24DC/40

Primary-switched power supply unit TRIO POWER, Push-in connection, DIN rail mounting, input: 3-phase, output: 24 V DC / 40 A, adjustable from 24 V DC ... 28 V DC

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: Phoenix Contact TRIO3-PS/3AC/24DC/40 TRIO3-PS/3AC/24DC/40 Power Supply.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Output 24 V DC, 40 A (960 W)
  • Input 3x 400 V AC ... 500 V AC
  • Efficiency typ. 95.4 % (3x 400 V AC)
  • Width 90 mm
  • Operating temperature -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K)
  • Degree of protection IP20

Specifications

Input data - AC operation
Supply system configurationStar network (TN, TT, IT (PE))
Nominal input voltage range3x 400 V AC ... 500 V AC
Input voltage range3x 400 V AC ... 500 V AC -20 % ... +10 %; 2x 400 V AC ... 500 V AC ±10 %
Typical national grid voltage3x 400 V AC; 3x 480 V AC
Voltage type of supply voltageAC
Inrush current< 21 A (25 °C)
Inrush current integral (I2t)< 0.77 A2s
Frequency range (fN)50 Hz ... 60 Hz ±10 %
Mains buffering timetyp. 21 ms (3x 400 V AC); typ. 21 ms (3x 480 V AC)
Current consumption3x 1.5 A (3x 400 V AC); 3x 1.2 A (3x 500 V AC); 2x 2.6 A (2x 400 V AC); 2x 2.1 A (2x 500 V AC)
Protective circuitTransient protection; Varistor
Power factor0.94 (3x 480 V AC)
Device mains fuse6.3 A internal (device protection)
Recommended breaker for input protection3x 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE< 3.5 mA
Output data
Efficiencytyp. 95.4 % (3x 400 V AC); typ. 95.8 % (3x 480 V AC)
Nominal output voltage24 V DC
Setting range of the output voltage (USet)24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)40 A
Dynamic Boost (IDyn.Boost)max. 60 A (5 s)
Short-circuit-proofyes
No-load proofyes
Derating60 °C ... 70 °C
Crest factortyp. 1.54 (3x 400 V AC); typ. 1,53 (3x 480 V AC)
Output power (PN)960 W
Output power (PDyn. Boost)max. 1440 W (5 s)
Connection in parallelyes, for increasing power and redundancy with diode
Connection in seriesyes, for increased output voltage (observe SELV limit)
Feedback voltage resistance≤ 35 V DC
Protection against overvoltage at the output (OVP)≤ 35 V DC
Residual rippletyp. 13 mVPP (with nominal values)
Control deviation< 1 % (change in load, static 10 % ... 90 %); < 3 % (change in load, dynamic 10 % ... 90 %); < 0.1 % (change in input voltage ±10 %)
Rise time≤ 1 s (UOut = 10 % ... 90 %)
Minimum no-load power dissipation< 1.37 W (3x 400 V AC)
Maximum no-load power dissipation< 0.77 W (3x 480 V AC)
Minimum nominal load power dissipation< 45.75 W (3x 400 V AC)
Power loss nominal load max.< 42.52 W (3x 480 V AC)
Integrated fuse protectionno
Fuse protection (secondary side)electronic
Connection data - Input
Position1.x
Connection data - Connection technology - Positions
Position marking1.1 (L1), 1.2 (L2), 1.3 (L3), 1.4 (); 2.1, 2.2 (+), 2.3, 2.4, 2.5 (-); 3.1 (13), 3.2 (14)
Connection data - Conductor connection
Connection methodPush-in connection
rigid (Terminal block)0.2 mm² ... 4 mm²; 0.75 mm² ... 16 mm²; 0.2 mm² ... 1.5 mm²
rigid (recommended)1.5 mm² (recommended); 10 mm² (recommended); 0.5 mm² (recommended)
flexible (Klemme)0.2 mm² ... 2.5 mm²; 0.75 mm² ... 16 mm²; 0.2 mm² ... 1.5 mm²
flexible (empfohlen)1.5 mm² (recommended); 10 mm² (recommended); 0.5 mm² (recommended)
flexible with ferrule without plastic sleeve (Terminal block)0.25 mm² ... 2.5 mm²; 0.75 mm² ... 16 mm² (Cu); 0.25 mm² ... 1.5 mm² (Cu)
flexible with ferrule without plastic sleeve (recommended)1.5 mm² (recommended); 10 mm² (recommended); 0.5 mm² (recommended)
flexible with ferrule with plastic sleeve (Terminal block)0.25 mm² ... 2.5 mm²; 0.75 mm² ... 10 mm²; 0.25 mm² ... 0.75 mm²
flexible with ferrule with plastic sleeve (recommended)1.5 mm² (recommended); 10 mm² (recommended); 0.5 mm² (recommended)
AWG (Terminal block)24 ... 12 (Cu); 20 ... 4 (Cu); 24 ... 16 (Cu)
AWG (recommended)16 (recommended); 8 (recommended); 20 (recommended)
Stripping length (starr/flexibel)10 mm (Rigid/flexible/ferrule); 18 mm (Rigid/flexible/ferrule)
Connection data - Output
Position2.x
Connection data - Signal
Position3.x
Signaling - LED signaling
Types of signalingLED DC OK - signal state operation (UN = 24 V DC, IOut = IN)
FunctionVisual operating state display
Colorred, yellow, green (multicolor LED)
LED offSupply voltage input AC not present (Off)
LED on (green), DC OKUOut > 21 V DC and IOut < 0.9 x IN (On (green), DC OK)
LED on (yellow), IOut > 90 %UOut > 21 V DC and IOut > 0.9 x IN (On (yellow), IOut > 90% )
LED on (red), ISHORTUOut < 21 V DC and IOut > 0.9 x IN (On (red), ISHORT)
LED on (flashing red) OVPUOUT > OVP (Over voltage protection) (on (flashing red))
Signaling - Signal output DC OK
Position3.x
Type of signalingDC OK switch contact - signal state operation (UN = 24 V DC, IOut = IN)
Position marking3.1 (13), 3.2 (14)
FunctionOperating state forwarding
Switch contact (floating)OptoMOS
Switching voltagemax. 30 V DC (SELV)
Current carrying capacitymax. 100 mA
State condition (Contact closed)UOut > 21 V DC and IOut < 0.9 x IN (Contact closed)
State condition (Contact open)UOut < 21 V DC or IOut > 0.9 x IN (averaging over 60 s) (Contact open)
Electrical properties
Number of phases3
Insulation voltage input/output5.3 kV DC (type test); 3.1 kV DC (routine test)
Product properties
Product typePower supply
Product familyTRIO POWER
MTBF (IEC 61709, SN 29500)> 1200000 h (25 °C); > 660000 h (40 °C); > 265000 h (60 °C)
Environmental protection directiveRoHS Directive 2011/65/EU; WEEE; Reach
Product properties - Insulation characteristics
Protection classI
Overvoltage category (EN 61010-1)III (≤ 2000 m); II (≤ 5000 m)
Overvoltage category (EN 61010-2-201)III (≤ 2000 m); II (≤ 5000 m)
Overvoltage category (EN 62368-1)II (≤ 2000 m); II (≤ 5000 m)
Degree of pollution2
Dimensions - Item dimensions
Width90 mm
Height135 mm
Depth167 mm
Depth (Device depth (DIN rail mounting))160 mm (Device depth (DIN rail mounting))
Dimensions - Installation dimensions
Installation distance right/left0 mm / 0 mm
Installation distance top/bottom50 mm / 50 mm
Mounting
Mounting typeDIN rail mounting
Assembly notealignable - horizontally 0 mm, vertically 50 mm
Mounting positionhorizontal DIN rail NS 35, EN 60715
With protective coatingno
Material specifications
Flammability rating according to UL 94V0 (Housing, terminal blocks)
Hood versionPolycarbonate
Side element versionAluminum
Environmental and real-life conditions - Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-40 °C
Maximum altitude (Maximum)≤ 5000 m
Maximum altitude (Output power derating)> 2000 m (Derating - 10%/1000 m)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock (operation)18 ms, 30g, per spatial direction (IEC 60068-2-27)
Vibration (operation)10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6); 50 Hz ... 150 Hz, 2.3g, 90 min.
Temp codeT4 (-25 ... +70 °C; > 60 °C, Derating - 2,5 %/K)
Standards and regulations - Safety of power supply units up to 1100 V (insulatio
Standard designationSafety of power supply units up to 1100 V (insulation distances)
Standards/specificationsDIN EN 61558-2-16
Standards and regulations - Electrical safety
Standard designationElectrical safety
Standards/specificationsIEC 61010-2-201 (SELV)
Standards and regulations - Safety for measurement, control, and laboratory equi
Standard designationSafety for equipment for measurement, control, and laboratory use
Standards/specificationsIEC 61010-1
Standards and regulations - Safety extra-low voltage
Standard designationSafety extra-low voltage
Standards/specificationsIEC 61010-1 (SELV)
Standards and regulations - Protective extra-low voltage
Standard designationProtective extra-low voltage
Standards/specificationsIEC 61010-2-201 (PELV)
Standards and regulations - Safe isolation
Standard designationSafe isolation
Standards/specificationsIEC 61558-2-16; IEC 61010-2-201
Standards and regulations - Limitation of harmonic line currents
Standard designationLimitation of harmonic line currents
Standards/specificationsEN 61000-3-2
Standards and regulations - Mains variation/undervoltage
Standard designationMains variation/undervoltage
Standards/specificationsSEMI F47; EN 61000-4-11
Approvals - UL
IdentificationUL/C-UL Listed UL 61010-1; UL/C-UL Listed UL 61010-2-201
Approvals - ANSI/UL 121201
IdentificationPROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS; (EN)  This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only.(FR)  Cet appareil convient uniquement pour une utilisation en atmosphères explosibles de classe I, division 2, groupes A, B, C et D ou en atmosphères non explosibles.; (EN)  WARNING - Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

Model numbers in this series (1)

Send us the complete code you need and we will quote it.

  • 1159045

About the TRIO3-PS/3AC/24DC/40

TRIO POWER power supply for DIN-rail mounting with standard functionality. Primary-switched power supply unit TRIO POWER, Push-in connection, DIN rail mounting, input: 3-phase, output: 24 V DC / 40 A, adjustable from 24 V DC ... 28 V DC Order no. 1159045.