Phoenix Contact TRIO-PS-2G/230AC-400DC/48DC/5 TRIO-PS-2G/230AC-400DC/48DC/5 Power Supply

Model number
TRIO-PS-2G/230AC-400DC/48DC/5

Primary-switched TRIO power supply for DIN rail mounting, input: 230 V AC/400 V DC, output: 48.5 V DC / 5 A, dynamic boost, tool-free fast-connection technology for rigid and flexible conductors with ferrule

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: Phoenix Contact TRIO-PS-2G/230AC-400DC/48DC/5 TRIO-PS-2G/230AC-400DC/48DC/5 Power Supply.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Output 48.5 V DC ±1 %, 5 A
  • Input 220 V AC ... 240 V AC
  • Efficiency typ. 92.5 % (230 V AC)
  • Width 42 mm
  • Operating temperature -25 °C ... 70 °C (>60°C derating - 1.6%/K)
  • Degree of protection IP20

Specifications

Input data - AC operation
Supply system configurationStar network (TN, TT, IT (PE))
Nominal input voltage range220 V AC ... 240 V AC
Input voltage range220 V AC ... 240 V AC -15 % ... +10 %
Switch-on voltagetyp. 70 V AC
Shut-down voltagetyp. 50 V AC
Electric strength, max.≤ 300 V AC 15 s
Typical national grid voltage230 V AC
Voltage type of supply voltageAC
Inrush current integral (I2t)< 0.3 A2s
Inrush current limitation< 13.5 A (after 1 ms)
AC frequency range50 Hz ... 60 Hz ±10 %
Mains buffering time> 20 ms (190 V AC); > 20 ms (230 V AC)
Current consumption1.3 A (230 V AC)
Nominal power consumption285.7 VA
Protective circuitTransient surge protection; Varistor
Power factor> 0.9 (230 V AC)
Input fuse3.15 A (internal (device protection))
Recommended breaker for input protection4 A ... 16 A (Characteristic B, C, Z)
Discharge current to PE< 3.5 mA; < 1.7 mA (264 V AC, 60 Hz)
Input data - DC operation
Nominal input voltage range220 V DC ... 400 V DC
Input voltage range220 V DC ... 400 V DC -15 % ... +5 %
Derating< 99 V DC (2 %/V)
Switch-on voltagetyp. 95 V DC
Shut-down voltagetyp. 50 V DC
Electric strength, max.≤ 420 V DC
Voltage type of supply voltageDC
Mains buffering time> 20 ms (185 V DC); > 25 ms (400 V DC)
Current consumption1.3 A (220 V DC); 0.7 A (400 V DC)
Output data
Efficiencytyp. 92.5 % (230 V AC); typ. 94 % (400 V DC)
Output characteristicU/I with dynamic load reserve
Nominal output voltage48.5 V DC ±1 %
Nominal output current (IN)5 A
Dynamic Boost (IDyn.Boost)7.5 A (5 s)
Derating> 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance≤ 60 V DC
Protection against overvoltage at the output (OVP)≤ 58 V DC
Control deviation< 1.5 % (change in load, static 10 % ... 90 %); < 4 % (Dynamic load change 10 % ... 90 %, 10 Hz); < 0.1 % (change in input voltage ±10 %)
Residual ripple< 20 mVPP (with nominal values)
Short-circuit-proofyes
No-load proofyes
Output power240 W; 360 W (5 s)
Peak switching voltages nominal load< 15 mVPP
Maximum no-load power dissipationtyp. 4 W (230 V AC); typ. 4 W (400 V DC)
Power loss nominal load max.typ. 20 W (230 V AC); typ. 15 W (400 V DC)
Short-circuit current< 7 A DC (permanent)
Rise time20 ms (UOUT (10 % ... 90 %))
Connection in parallelyes, for redundancy and increased capacity
Fuse protection (secondary side)electronic
Output data - Signal - DC OK
Continuous load current100 mA
Output data - Signal relay 13/14
Defaultclosed
Digital30 V AC 30 V DC 100 mA
Connection data - Input
Connection methodPush-in connection
Conductor cross-section, rigid min.0.2 mm²
Conductor cross-section, rigid max.4 mm²
Conductor cross-section flexible min.0.2 mm²
Conductor cross-section flexible max.2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.1.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.2.5 mm²
Conductor cross-section AWG min.24
Conductor cross-section AWG max.12
Connection data - Output
Connection methodPush-in connection
Conductor cross-section, rigid min.0.2 mm²
Conductor cross-section, rigid max.4 mm²
Conductor cross-section flexible min.0.2 mm²
Conductor cross-section flexible max.2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.1.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.2.5 mm²
Conductor cross-section AWG min.24
Conductor cross-section AWG max.12
Connection data - Signal
Connection methodPush-in connection
Conductor cross-section, rigid min.0.2 mm²
Conductor cross-section, rigid max.0.75 mm²
Conductor cross-section flexible min.0.2 mm²
Conductor cross-section flexible max.1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.1 mm²
Conductor cross-section AWG min.24
Conductor cross-section AWG max.18
Signaling
Types of signalingFloating signal contact
Signaling - Signal output - LED status indicator
Signalization designationDC OK
Status displayLED
Colorgreen
DC OKUOUT > 0.7 x UN (UN = 48 V DC)
13/14UOUT > 0.7 x UN (UN = 48 V DC)
Electrical properties
Number of phases1
Insulation voltage input/output5.1 kV AC (type test); 3.1 kV AC (routine test)
Product properties
Product typePower supply
Product familyTRIO POWER
MTBF (IEC 61709, SN 29500)> 2220000 h (25 °C); > 1280000 h (40 °C); > 560000 h (60 °C); > 2220000 h (25 °C); > 1280000 h (40 °C); > 560000 h (60 °C)
Product properties - Insulation characteristics
Protection classI (in closed control cabinet)
Overvoltage category (EN 61010-1)II (≤ 2000 m)
Degree of pollution2
Dimensions
Width42 mm
Height130 mm
Depth160 mm
Dimensions - Installation dimensions
Installation distance right/left0 mm / 0 mm
Installation distance top/bottom50 mm / 50 mm
Mounting
Mounting typeDIN rail mounting
Assembly notealignable - horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
Mounting positionhorizontal DIN rail NS 35, EN 60715
With protective coatingno
Material specifications
Flammability rating according to UL 94 (housing / terminal blocks)V0
Housing materialMetal
Type of housingAluminum (AlMg3)
Hood versionPolycarbonate
Environmental and real-life conditions - Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (>60°C derating - 1.6%/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-40 °C
Maximum altitude≤ 2000 m
Climatic class3K3 (EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock20 m/s² (2g), 11 ms, ± 100 Schocks (DIN EN 50125-3, DIN EN 60068-2-27)
Vibration (operation)5 Hz ... 2 kHz, 2.3 m/s² (0.23g) (RMS) 5 h (DIN EN 50125-3, DIN EN 60068-2-64)
Standards and regulations
Rail applicationsEN 50121-3-2; EN 50121-4; EN 50124-1; EN 50125-3; IEC 62236-3-2; IEC 62236-4; IEC 62236-5
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard - Electrical safetyEN 61010-1; VDE 0805 (SELV)
Standard – Safety extra-low voltageIEC 61010-1 (SELV); IEC 61010-2-201 (PELV)
Standard - Safe isolationIEC 61010-2-201; IEC 61558-2-16
Standard - Safety of power supply units up to 1100 V (insulation distances)DIN EN 61558-2-16
Approvals
UL approvalsUL 61010-1; UL 61010-2-201
Approvals - Conformity/Approvals
SIL in accordance with IEC 615080

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

Model numbers in this series (1)

Send us the complete code you need and we will quote it.

  • 1157806

About the TRIO-PS-2G/230AC-400DC/48DC/5

TRIO POWER power supply for DIN-rail mounting with standard functionality. Primary-switched TRIO power supply for DIN rail mounting, input: 230 V AC/400 V DC, output: 48.5 V DC / 5 A, dynamic boost, tool-free fast-connection technology for rigid and flexible conductors with ferrule Order no. 1157806.