Phoenix Contact QUINT4-PS/3AC/24DC/5 QUINT4-PS/3AC/24DC/5 Power Supply

Model number
QUINT4-PS/3AC/24DC/5

Primary-switched QUINT POWER power supply with selectable output characteristic curve, SFB (Selective Fuse Breaking) Technology, and NFC interface, input: 3-phase, output: 24 V DC/5 A. Product is being prepared for compliance with the Cyber…

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: Phoenix Contact QUINT4-PS/3AC/24DC/5 QUINT4-PS/3AC/24DC/5 Power Supply.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Output 24 V DC, 5 A
  • Input 3x 400 V AC ... 500 V AC
  • Efficiency typ. 89 % (400 V AC)
  • Width 36 mm
  • Operating temperature -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K)
  • Degree of protection IP20

Specifications

Input data
Control input (configurable) RemOutput power ON/OFF (SLEEP MODE)
DefaultOutput power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
Input data - AC operation
Network typeStar network
Nominal input voltage range3x 400 V AC ... 500 V AC; 2x 400 V AC ... 500 V AC
Input voltage range3x 400 V AC ... 500 V AC -20 % ... +10 %; 2x 400 V AC ... 500 V AC -10 % ... +10 %
Typical national grid voltage400 V AC; 480 V AC
Voltage type of supply voltageAC
Inrush currenttyp. 11 A (at 25 °C)
Inrush current integral (I2t)< 0.2 A2s
Inrush current limitation11 A (after 1 ms)
AC frequency range50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN)50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering timetyp. 34 ms (3x 400 V AC); typ. 50 ms (3x 480 V AC)
Current consumption3x 0.53 A (400 V AC); 3x 0.44 A (480 V AC); 2x 0.9 A (400 V AC); 2x 0.66 A (480 V AC); 3x 0.45 A (500 V AC); 2x 0.8 A (500 V AC)
Nominal power consumption283 VA
Protective circuitTransient surge protection; Varistor, gas-filled surge arrester
Power factor0.48
Switch-on time< 500 ms
Typical response time300 ms (from SLEEP MODE)
Input fuse2 A (slow-blow, internal)
Recommended breaker for input protection3x 6 A (Characteristic B, C or comparable)
Recommended fuse for input protection≥ 300 V AC
Discharge current to PE< 3.5 mA; 1 mA (550 V AC, 60 Hz)
Input data - DC operation
Nominal input voltage range± 300 V DC
Input voltage range± 260 V DC ... 300 V DC -25 % ... +30 %; 520 V DC ... 600 V DC -25 % ... +30 % (mid-point earthed)
Voltage type of supply voltageDC
Inrush current limitation≤ 11 A (after 1 ms)
Frequency range (fN)0 Hz (DC)
Current consumption0.3 A (±300 V DC)
Recommended breaker for input protection1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
Recommended fuse for input protection≥ 1000 V DC
Output data
Efficiencytyp. 89 % (400 V AC); typ. 87.5 % (480 V AC)
Output characteristicU/I Advanced; Smart HICCUP; FUSE MODE
Nominal output voltage24 V DC
Setting range of the output voltage (USet)24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (IN)5 A
Static Boost (IStat.Boost)6.25 A
Dynamic Boost (IDyn.Boost)10 A (5 s)
Selective Fuse Breaking (ISFB)30 A (15 ms)
Magnetic circuit breaker trippingA1 ... A4 / B2 / C1 ... C2 / Z1 ... Z4
Derating> 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance≤ 35 V DC
Protection against overvoltage at the output (OVP)≤ 32 V DC
Control deviation< 0.5 % (Static load change 10 % ... 90 %); < 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)); < 0.25 % (change in input voltage ±10 %)
Residual ripple< 30 mVPP (with nominal values)
Short-circuit-proofyes
No-load proofyes
Output power120 W; 150 W; 240 W
Apparent power212 VA (400 V, UOUT = 24 V, IOUT = stat. Boost); 221 VA (480 V, UOUT = 24 V, IOUT = stat. Boost)
Maximum no-load power dissipation< 3 W (400 V AC); < 4 W (480 V AC)
Power loss nominal load max.< 15 W (400 V AC); < 17 W (480 V AC)
Power dissipation SLEEP MODE< 3 W (400 V AC); < 4 W (480 V AC)
Crest factortyp. 3.6 (400 V AC); typ. 3.8 (480 V AC)
Rise time50 ms (UOut = 10 % ... 90 %)
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesyes
Fuse protection (secondary side)electronic; thermal-magnetic; thermal
Output data - Signal
Signal ground SGndReference potential for Out1, Out2, and Rem
Output data - Signal Out 1 (configurable)
Digital24 V DC 20 mA
Default24 V DC 20 mA 24 V DC for UOut > 0.9 x USet
Output data - Signal Out 2 (configurable)
Digital24 V DC 20 mA
Analog4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Default24 V DC 20 mA 24 V DC for POut < PN
Output data - Signal relay 13/14 (configurable)
Defaultclosed (Uout > 0.9 USet)
Digital24 V DC 1 A; 30 V AC/DC 0.5 A
Connection data - Input
Connection methodScrew connection
Conductor cross-section, rigid min.0.2 mm²
Conductor cross-section, rigid max.6 mm²
Conductor cross-section flexible min.0.2 mm²
Conductor cross-section flexible max.4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.4 mm²
Conductor cross-section AWG min.24
Conductor cross-section AWG max.10
Stripping length8 mm
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm
Connection data - Output
Connection methodScrew connection
Conductor cross-section, rigid min.0.2 mm²
Conductor cross-section, rigid max.2.5 mm²
Conductor cross-section flexible min.0.2 mm²
Conductor cross-section flexible max.2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.2.5 mm²
Conductor cross-section AWG min.24
Conductor cross-section AWG max.14
Stripping length6.5 mm
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm
Connection data - Signal
Connection methodPush-in connection
Conductor cross-section, rigid min.0.2 mm²
Conductor cross-section, rigid max.1 mm²
Conductor cross-section flexible min.0.2 mm²
Conductor cross-section flexible max.1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.1.5 mm²
Conductor cross-section AWG min.24
Conductor cross-section AWG max.16
Stripping length8 mm
Signaling
Types of signalingLED; Floating signal contact; Active signal output Out1 (digital, configurable); Active signal output Out2 (analog, configurable); Remote contact; Signal ground SGnd
Signaling - Signal output
Signal optionOutput current; Output voltage; Output power; UIN input voltage OK; Operating hours; Early warning of high temperatures; OVP voltage limitation active; Phase monitoring
POut> 100 % (LED lights up yellow, output power > 120 W); > 75 % (LED lights up green, output power > 90 W); > 50 % (LED lights up green, output power > 60 W)
UOut> 0.9 x USet (LED lights up green); < 0.9 x USet (LED flashes green)
Electrical properties
Number of phases3
Insulation voltage input/output4 kV AC (type test); 2.4 kV AC (routine test)
Insulation voltage output / PE0.5 kV DC (type test); 0.5 kV DC (routine test)
Insulation voltage input / PE3.5 kV AC (type test); 2.4 kV AC (routine test)
Switching frequency85.00 kHz ... 107.00 kHz (Auxiliary converter stage); 45.00 kHz ... 200.00 kHz (Main converter stage)
Product properties
Product typePower supply
Product familyQUINT POWER
MTBF (IEC 61709, SN 29500)> 1560000 h (25 °C); > 914000 h (40 °C); > 413000 h (60 °C)
Environmental protection directiveRoHS Directive 2011/65/EU; WEEE; Reach
Product properties - Insulation characteristics
Protection classI
Overvoltage category (EN 61010-1)II (≤ 5000 m)
Overvoltage category (EN 62477-1)III (≤ 2000 m)
Degree of pollution2
Dimensions
Width36 mm
Height130 mm
Depth125 mm
Dimensions - Installation dimensions
Installation distance right/left5 mm / 5 mm
Installation distance top/bottom50 mm / 50 mm
Dimensions - Alternative assembly
Width122 mm
Height130 mm
Depth39 mm
Mounting
Mounting typeDIN rail mounting
Assembly notealignable - PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable - PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting positionhorizontal DIN rail NS 35, EN 60715
With protective coatingno
Material specifications
Flammability rating according to UL 94 (housing / terminal blocks)V0
Housing materialMetal
Hood versionStainless steel X6Cr17
Side element versionAluminum
Environmental and real-life conditions - Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-40 °C
Maximum altitude≤ 5000 m (> 2000 m, observe derating)
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
Temp codeT4 (-25 ... +70 °C; > 60 °C, Derating - 2,5 %/K)
Standards and regulations
Rail applicationsEN 50121-3-2; EN 50121-4; EN 50121-5; IEC 62236-3-2; IEC 62236-4; IEC 62236-5
HART FSK Physical Layer Test Specification ComplianceOutput voltage UOut compliant
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard - Electrical safetyIEC 61010-2-201 (SELV)
Standard – Safety extra-low voltageIEC 61010-1 (SELV); IEC 61010-2-201 (PELV)
Standard - Safe isolationIEC 61558-2-16; IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory useIEC 61010-1
Standard - Safety of transformersEN 61558-2-16
Standard - power supply devices for low voltage with DC outputEN 61204-3
Battery chargingDIN 41773-1
Approval - requirement of the semiconductor industry with regard to mains voltage dipsSEMI F47-0706, EN 61000-4-11
Approvals
CSACAN/CSA-C22.2 No. 60950-1-07; CSA-C22.2 No. 107.1-01
Shipbuilding approvalDNV GL, PRS, BV, LR, ABS
SIQBG (type approved)
UL approvalsUL Listed UL 508; UL/C-UL Recognized UL 60950-1; UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

Model numbers in this series (1)

Send us the complete code you need and we will quote it.

  • 2904620

About the QUINT4-PS/3AC/24DC/5

QUINT POWER power supply for DIN-rail mounting with maximum functionality. Primary-switched QUINT POWER power supply with selectable output characteristic curve, SFB (Selective Fuse Breaking) Technology, and NFC interface, input: 3-phase, output: 24 V DC/5 A. Product is being prepared for compliance with the Cyber Resilience Act (CRA). Order no. 2904620.