Phoenix Contact QUINT4-PS/24-48DC/48DC/2/PT QUINT4-PS/24-48DC/48DC/2/PT DC/DC Converter
- Brand
- Phoenix Contact
- Model number
- QUINT4-PS/24-48DC/48DC/2/PT
- Category
- DIN-Rail Power Supplies
Primary-switched DC/DC converter, QUINT POWER DIN rail mounting, input: 24 V DC - 48 V DC, output: 48 V DC / 2 A
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Output 48 V DC, 2 A (96 W)
- Input 24 V DC ... 48 V DC
- Efficiency typ. 90.1 % (24 V DC)
- Width 45 mm
- Operating temperature -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K)
- Degree of protection IP20
Specifications
| Nominal input voltage range | 24 V DC ... 48 V DC |
|---|---|
| Input voltage range | 24 V DC ... 48 V DC -10 % ... +25 % |
| Wide-range input | yes |
| Electric strength, max. | 60 V DC (60 s) |
| Inrush current | typ. 8 A |
| Inrush current integral (I2t) | typ. 0.1 A2s |
| Inrush current limitation | 8 A |
| Mains buffering time | typ. 13 ms (24 V DC); typ. 18 ms (48 V DC); > 20 ms (24 V DC / 48 V DC, at 50% load) |
| Current consumption | typ. 5.6 A (24 V DC); typ. 2.7 A (48 V DC) |
| Switch-on time | < 1 s |
| Input fuse | 15 A (slow-blow, internal) |
| Recommended breaker for input protection | 10 A ... 16 A (Characteristic B, C, D, K or comparable) |
| Efficiency | typ. 90.1 % (24 V DC); typ. 91.9 % (48 V DC) |
|---|---|
| Output characteristic | U/I Advanced |
| Nominal output voltage | 48 V DC |
| Setting range of the output voltage (USet) | 48 V DC ... 56 V DC (> 48 V constant capacity) |
| Nominal output current (IN) | 2 A |
| Static Boost (IStat.Boost) | 2.5 A |
| Dynamic Boost (IDyn.Boost) | 4 A (4.9 s) |
| Short-circuit-proof | yes |
| No-load proof | yes |
| Derating | > 60 °C (2.5%/K of POut nom.) |
| Output power (PN) | 96 W |
| Output power (PStat. Boost) | 120 W |
| Output power (PDyn. Boost) | 192 W |
| Feedback voltage resistance | ≤ 65 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 60 V DC |
| Residual ripple | < 20 mVPP |
| Control deviation static | < 1 % (change in load, static 10 % ... 90 %) |
| Control deviation dynamic | < 1 % (change in load, static 10 % ... 90 %) |
| Control deviation Input voltage change | < 1 % (change in load, static 10 % ... 90 %) |
| Rise time | < 1 s (UOUT (10 % ... 90 %)) |
| Connection in series | yes |
| Maximum no-load power dissipation | < 2.5 W |
| Power loss nominal load max. | < 7.5 W |
| Connection in parallel | yes, for redundancy and increased capacity |
| Fuse protection (secondary side) | electronic |
| Position | 1.x |
|---|
| Connection method | Push-in connection |
|---|---|
| rigid | 0.5 mm² ... 2.5 mm²; 0.2 mm² ... 2.5 mm² |
| flexible | 0.5 mm² ... 2.5 mm²; 0.2 mm² ... 2.5 mm² |
| rigid (AWG) | 20 ... 14; 24 ... 14 |
| Stripping length | 10 mm |
| Position | 2.x |
|---|
| Position | 3.x |
|---|
| Signal threshold | > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting); > 0.9 x USet (LED lights up green); < 0.9 x USet (LED flashes green) |
|---|
| Digital | 0 V DC; 24 V DC; 22 mA |
|---|---|
| Default | 24 V DC; 22 mA; 24 V DC for UOut > 0.9 x USet |
| Number of phases | 1.00 |
|---|---|
| Insulation voltage input/output | 3.1 kV DC (type test); 1.2 kV DC (routine test) |
| Switching frequency | 30.00 kHz ... 40.00 kHz (Auxiliary converter stage); 90.00 kHz ... 110.00 kHz (Main converter stage) |
| Product type | DC/DC converters |
|---|---|
| Product family | QUINT POWER |
| MTBF (IEC 61709, SN 29500) | > 1775000 h (25 °C); > 1058000 h (40 °C); > 488000 h (60 °C) |
| Protection class | II |
|---|---|
| Overvoltage category (EN 61010-1) | II (≤ 5000 m) |
| Overvoltage category (EN 62477-1) | III (≤ 2000 m) |
| Degree of pollution | 2 |
| Width | 45 mm |
|---|---|
| Height | 106 mm |
| Depth | 90 mm |
| Width | 90 mm |
|---|---|
| Height | 106 mm |
| Depth | 45 mm |
| Installation distance right/left (active) | 15 mm / 15 mm (POut ≥50% ) |
|---|---|
| Installation distance right/left (passive) | 5 mm / 5 mm (POut ≥50% ) |
| Installation distance right/left (active, passive) | 0 mm / 0 mm (POut ≤50 %) |
| Installation distance top/bottom (active) | 30 mm / 30 mm (POut ≥50% ) |
| Installation distance top/bottom (passive) | 30 mm / 30 mm (POut ≥50% ) |
| Installation distance top/bottom (active, passive) | 30 mm / 30 mm (POut ≤50 %) |
| Mounting type | DIN rail mounting |
|---|---|
| Assembly note | alignable - PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable - PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| With protective coating | no |
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
|---|---|
| Housing material | Plastic |
| Type of housing | Polycarbonate (PC), UL 94 V0 |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Ambient temperature (start-up type tested) | -40 °C |
| Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) |
| Climatic class | 3K22 (in accordance with EN 60721-3-3) |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz - 2.3 g 90 Min. (in accordance with IEC 60068-2-6) |
| Temp code | T4A (-25 ... +70 °C; > 60 °C, Derating - 2,5 %/K) |
| Standard designation | Electrical safety (of control and regulation devices) |
|---|---|
| Standards/specifications | IEC 61010-1 |
| Standard designation | Protective extra-low voltage |
|---|---|
| Standards/specifications | IEC 61010-1 (SELV) |
| Standard designation | Mains variation/undervoltage |
|---|---|
| Standards/specifications | EN 61000-4-29 |
| Standard designation | Railway applications |
|---|---|
| Standards/specifications | EN 50121-3-2; EN 50121-4; IEC 62236-3-2; IEC 62236-4 |
| Identification | UL Listed UL 61010-1; CAN/CSA C22.2 No. 61010-1-12; UL Listed UL 61010-2-201; CAN/CSA C22.2 No. 61010-2-201-18; UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
|---|
| Identification | CB scheme (IEC 61010-1, IEC 61010-2-201) |
|---|
| Identification | DNV GL |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
Model numbers in this series (1)
Send us the complete code you need and we will quote it.
1098676
About the QUINT4-PS/24-48DC/48DC/2/PT
QUINT POWER power supply for DIN-rail mounting with maximum functionality. Primary-switched DC/DC converter, QUINT POWER DIN rail mounting, input: 24 V DC - 48 V DC, output: 48 V DC / 2 A Order no. 1098676.