Phoenix Contact QUINT4-PS/1AC/24DC/5 QUINT4-PS/1AC/24DC/5 Power Supply
- Brand
- Phoenix Contact
- Model number
- QUINT4-PS/1AC/24DC/5
- Category
- DIN-Rail Power Supplies
Primary-switched QUINT POWER power supply with selectable output characteristic curve, SFB (Selective Fuse Breaking) Technology, and NFC interface, input: 1-phase, output: 24 V DC/5 A. Product is being prepared for compliance with the Cyber…
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Output 24 V DC, 5 A
- Input 100 V AC ... 240 V AC
- Efficiency typ. 88.8 % (120 V AC)
- Width 36 mm
- Operating temperature -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K)
- Degree of protection IP20
Specifications
| Control input (configurable) Rem | Output power ON/OFF (SLEEP MODE) |
|---|---|
| Default | Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd) |
| Supply system configuration | Star network |
|---|---|
| Nominal input voltage range | 100 V AC ... 240 V AC |
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
| Derating | < 100 V AC (1 %/V) |
| Electric strength, max. | 300 V AC 60 s |
| Typical national grid voltage | 120 V AC; 230 V AC |
| Voltage type of supply voltage | AC |
| Inrush current | typ. 14 A (at 25 °C) |
| Inrush current integral (I2t) | < 0.3 A2s |
| Inrush current limitation | 14 A (after 1 ms) |
| AC frequency range | 50 Hz ... 60 Hz -10 % ... +10 % |
| Frequency range (fN) | 50 Hz ... 60 Hz -10 % ... +10 %; 16.7 Hz (acc. to EN 50163) |
| Mains buffering time | typ. 24 ms (120 V AC); typ. 32 ms (230 V AC) |
| Current consumption | 1.7 A (100 V AC); 1.5 A (120 V AC); 0.9 A (230 V AC); 0.8 A (240 V AC) |
| Nominal power consumption | 163 VA |
| Protective circuit | Transient surge protection; Varistor, gas-filled surge arrester |
| Power factor | 0.82 |
| Switch-on time | < 500 ms |
| Typical response time | 300 ms (from SLEEP MODE) |
| Input fuse | 6.3 A (slow-blow, internal) |
| Recommended breaker for input protection | 6 A ... 16 A (Characteristic B, C, D, K or comparable) |
| Discharge current to PE | < 3.5 mA; 1.1 mA (264 V AC, 60 Hz) |
| Nominal input voltage range | 110 V DC ... 250 V DC |
|---|---|
| Input voltage range | 110 V DC ... 250 V DC -18 % ... +40 % |
| Derating | < 110 V DC (1 %/V) |
| Voltage type of supply voltage | DC |
| Current consumption | 1.6 A (110 V DC); 0.7 A (250 V DC) |
| Efficiency | typ. 88.8 % (120 V AC); typ. 89.2 % (230 V AC) |
|---|---|
| Output characteristic | U/I Advanced; Smart HICCUP; FUSE MODE |
| Nominal output voltage | 24 V DC |
| Setting range of the output voltage (USet) | 24 V DC ... 29.5 V DC (constant capacity) |
| Nominal output current (IN) | 5 A |
| Static Boost (IStat.Boost) | 6.25 A |
| Dynamic Boost (IDyn.Boost) | 10 A (5 s) |
| Selective Fuse Breaking (ISFB) | 30 A (15 ms) |
| Magnetic circuit breaker tripping | A1 ... A4 / B2 / C1 ... C2 / Z1 ... Z4 |
| Derating | > 60 °C ... 70 °C (2.5 %/K) |
| Feedback voltage resistance | ≤ 35 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 32 V DC |
| Control deviation | < 0.5 % (Static load change 10 % ... 90 %); < 4 % (Dynamic load change 10 % ... 90 %, (10 Hz)); < 0.25 % (change in input voltage ±10 %) |
| Residual ripple | < 30 mVPP (with nominal values) |
| Short-circuit-proof | yes |
| No-load proof | yes |
| Output power | 120 W; 150 W; 240 W |
| Apparent power | 180 VA (120 V, UOUT = 24 V, IOUT = stat. Boost); 198 VA (230 V, UOUT = 24 V, IOUT = stat. Boost) |
| Maximum no-load power dissipation | < 3 W (120 V AC); < 3 W (230 V AC) |
| Power loss nominal load max. | < 17 W (120 V AC); < 16 W (230 V AC) |
| Power dissipation SLEEP MODE | < 3 W (120 V AC); < 3 W (230 V AC) |
| Crest factor | typ. 1.55 (120 V AC); typ. 1.78 (230 V AC) |
| Rise time | 50 ms (UOut = 10 % ... 90 %) |
| Connection in parallel | yes, for redundancy and increased capacity |
| Connection in series | yes |
| Fuse protection (secondary side) | electronic; thermal-magnetic; thermal |
| Signal ground SGnd | Reference potential for Out1, Out2, and Rem |
|---|
| Digital | 24 V DC 20 mA |
|---|---|
| Default | 24 V DC 20 mA 24 V DC for UOut > 0.9 x USet |
| Digital | 24 V DC 20 mA |
|---|---|
| Analog | 4 mA ... 20 mA ±5 % (Load ≤400 Ω) |
| Default | 24 V DC 20 mA 24 V DC for POut < PN |
| Default | closed (Uout > 0.9 USet) |
|---|---|
| Digital | 24 V DC 1 A; 30 V AC/DC 0.5 A |
| Connection method | Screw connection |
|---|---|
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.25 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 2.5 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.25 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 2.5 mm² |
| Conductor cross-section AWG min. | 24 |
| Conductor cross-section AWG max. | 14 |
| Stripping length | 6.5 mm |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Connection method | Screw connection |
|---|---|
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.25 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 2.5 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.25 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 2.5 mm² |
| Conductor cross-section AWG min. | 24 |
| Conductor cross-section AWG max. | 14 |
| Stripping length | 6.5 mm |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Connection method | Push-in connection |
|---|---|
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 1.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 1.5 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, min. | 0.2 mm² |
| Single conductor/flexible terminal point with ferrule with plastic sleeve, max. | 0.75 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, min. | 0.2 mm² |
| Single conductor/flexible terminal point with ferrule without plastic sleeve, max. | 1.5 mm² |
| Conductor cross-section AWG min. | 24 |
| Conductor cross-section AWG max. | 16 |
| Stripping length | 8 mm |
| Types of signaling | LED; Floating signal contact; Active signal output Out1 (digital, configurable); Active signal output Out2 (analog, configurable); Remote contact; Signal ground SGnd |
|---|
| Signal option | Output current; Output voltage; Output power; UIN input voltage OK; Operating hours; Early warning of high temperatures; OVP voltage limitation active |
|---|---|
| POut | > 100 % (LED lights up yellow, output power > 120 W); > 75 % (LED lights up green, output power > 90 W); > 50 % (LED lights up green, output power > 60 W) |
| UOut | > 0.9 x USet (LED lights up green); < 0.9 x USet (LED flashes green) |
| Number of phases | 1 |
|---|---|
| Insulation voltage input/output | 4 kV AC (type test); 2 kV AC (routine test) |
| Insulation voltage output / PE | 0.5 kV DC (type test); 0.5 kV DC (routine test) |
| Insulation voltage input / PE | 3.5 kV AC (type test); 2.4 kV AC (routine test) |
| Switching frequency | 90.00 kHz ... 110.00 kHz (Auxiliary converter stage); 50.00 kHz ... 235.00 kHz (Main converter stage); 55.00 kHz ... 625.00 kHz (PFC stage) |
| Product type | Power supply |
|---|---|
| Product family | QUINT POWER |
| MTBF (IEC 61709, SN 29500) | > 1532000 h (25 °C); > 930000 h (40 °C); > 431000 h (60 °C) |
| Environmental protection directive | RoHS Directive 2011/65/EU; WEEE; Reach |
| Protection class | I |
|---|---|
| Overvoltage category (EN 61010-1) | II (≤ 5000 m) |
| Overvoltage category (EN 62477-1) | III (≤ 2000 m) |
| Degree of pollution | 2 |
| Width | 36 mm |
|---|---|
| Height | 130 mm |
| Depth | 125 mm |
| Installation distance right/left | 5 mm / 5 mm |
|---|---|
| Installation distance top/bottom | 50 mm / 50 mm |
| Width | 122 mm |
|---|---|
| Height | 130 mm |
| Depth | 39 mm |
| Mounting type | DIN rail mounting |
|---|---|
| Assembly note | alignable - PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm verticallyalignable - PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| With protective coating | no |
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
|---|---|
| Housing material | Metal |
| Hood version | Stainless steel X6Cr17 |
| Side element version | Aluminum |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Ambient temperature (start-up type tested) | -40 °C |
| Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) |
| Climatic class | 3K22 (in accordance with EN 60721-3-3) |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | 5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) |
| Temp code | T4 (-25 ... +70 °C; > 60 °C, Derating - 2,5 %/K) |
| Rail applications | EN 50121-3-2; EN 50121-4; EN 50121-5; EN 50163; IEC 62236-3-2; IEC 62236-4; IEC 62236-5 |
|---|---|
| HART FSK Physical Layer Test Specification Compliance | Output voltage UOut compliant |
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Standard - Electrical safety | IEC 61010-2-201 (SELV) |
| Standard – Safety extra-low voltage | IEC 61010-1 (SELV); IEC 61010-2-201 (PELV) |
| Standard - Safe isolation | IEC 61558-2-16; IEC 61010-2-201 |
| Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
| Standard - Safety of transformers | EN 61558-2-16 |
| Standard - power supply devices for low voltage with DC output | EN 61204-3 |
| Battery charging | DIN 41773-1 |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47-0706, EN 61000-4-11 |
| CSA | CAN/CSA-C22.2 No. 60950-1-07; CSA-C22.2 No. 107.1-01 |
|---|---|
| Shipbuilding approval | DNV, PRS, BV, LR, ABS, NK |
| SIQ | BG (type approved); CB-Scheme (IEC 61010-1, IEC 61010-2-201, IEC 60950-1) |
| UL approvals | UL Listed UL 508; UL/C-UL Recognized UL 60950-1; UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
Model numbers in this series (1)
Send us the complete code you need and we will quote it.
2904600
About the QUINT4-PS/1AC/24DC/5
QUINT POWER power supply for DIN-rail mounting with maximum functionality. Primary-switched QUINT POWER power supply with selectable output characteristic curve, SFB (Selective Fuse Breaking) Technology, and NFC interface, input: 1-phase, output: 24 V DC/5 A. Product is being prepared for compliance with the Cyber Resilience Act (CRA). Order no. 2904600.