Phoenix Contact QUINT4-PS/1AC/12DC/2.5/PT QUINT4-PS/1AC/12DC/2.5/PT Power Supply
- Brand
- Phoenix Contact
- Model number
- QUINT4-PS/1AC/12DC/2.5/PT
- Category
- DIN-Rail Power Supplies
Primary-switched power supply unit QUINT POWER, Push-in connection, DIN rail mounting, input: 1-phase, output: 12 V DC / 2.5 A, adjustable from 12 V DC ... 15 V DC
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Output 12 V DC, 2.5 A
- Efficiency typ. 89.5 % (120 V AC)
- Width 22.5 mm
- Operating temperature -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K)
- Degree of protection IP20
Specifications
| Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
|---|---|
| Electric strength, max. | 300 V AC 60 s |
| Typical national grid voltage | 120 V AC; 230 V AC |
| Voltage type of supply voltage | AC |
| Inrush current | typ. 11.3 A (at 25 °C) |
| Inrush current integral (I2t) | < 0.1 A2s |
| Inrush current limitation | < 11.3 A |
| Frequency range (fN) | 50 Hz ... 60 Hz -10 % ... +10 %; 16.7 Hz (acc. to EN 50163) |
| Mains buffering time | typ. 54 ms (120 V AC); typ. 54 ms (230 V AC) |
| Current consumption | 0.44 A (100 V AC); 0.35 A (120 V AC); 0.19 A (230 V AC); 0.2 A (240 V AC) |
| Nominal power consumption | 32.8 VA |
| Protective circuit | Transient surge protection; Varistor |
| Typical response time | 500 ms |
| Input fuse | 3.15 A (slow-blow, internal) |
| Recommended breaker for input protection | 6 A ... 16 A (Characteristic B, C or comparable) |
| Discharge current to PE | < 0.25 mA (264 V AC, 60 Hz); < 0.16 mA |
| Input voltage range | 110 V DC ... 250 V DC -20 % ... +40 % |
|---|---|
| Voltage type of supply voltage | DC |
| Current consumption | 0.4 A (110 V DC); 0.17 A (250 V DC) |
| Efficiency | typ. 89.5 % (120 V AC); typ. 90.9 % (230 V AC) |
|---|---|
| Nominal output voltage | 12 V DC |
| Setting range of the output voltage (USet) | 12 V DC ... 15 V DC (constant capacity) |
| Nominal output current (IN) | 2.5 A |
| Static Boost (IStat.Boost) | 3.125 A (≤ 40 °C) |
| Dynamic Boost (IDyn.Boost) | 4.5 A (≤ 60 °C (5 s)) |
| Feedback voltage resistance | ≤ 25 V DC |
| Protection against overvoltage at the output (OVP) | ≤ 18 V DC |
| Control deviation | < 0.2 % (Static load change 10 % ... 90 %); < 2 % (Dynamic load change 10 % ... 90 %, (10 Hz)); < 0.1 % (change in input voltage ±10 %) |
| Residual ripple | < 30 mVPP (with nominal values) |
| Short-circuit-proof | yes |
| No-load proof | yes |
| Output power | 30 W; 38 W; 54 W |
| Maximum no-load power dissipation | < 0.4 W (230 V AC); < 0.5 W (120 V AC) |
| Power loss nominal load max. | < 3.5 W (120 V AC); < 3 W (230 V AC) |
| Crest factor | typ. 1.89 (120 V AC); typ. 1.97 (230 V AC) |
| Rise time | 50 ms (UOut = 10 % ... 90 %) |
| Connection in parallel | yes, for redundancy and increased capacity |
| Connection in series | yes |
| Fuse protection (secondary side) | electronic |
| Digital | 0 V DC 12 V DC 24 mA |
|---|---|
| Default | 12 V DC 24 mA 12 V DC for UOut > 0.9 x USet |
| Connection method | Push-in connection |
|---|---|
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
| Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
| Conductor cross-section AWG min. | 24 |
| Conductor cross-section AWG max. | 14 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
|---|---|
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
| Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
| Conductor cross-section AWG min. | 24 |
| Conductor cross-section AWG max. | 14 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
|---|---|
| Conductor cross-section, rigid min. | 0.2 mm² |
| Conductor cross-section, rigid max. | 2.5 mm² |
| Conductor cross-section flexible min. | 0.2 mm² |
| Conductor cross-section flexible max. | 2.5 mm² |
| Single conductor/terminal point, stranded, with ferrule, min. | 0.25 mm² |
| Single conductor/terminal point, stranded, with ferrule, max. | 2.5 mm² |
| Conductor cross-section AWG min. | 24 |
| Conductor cross-section AWG max. | 14 |
| Stripping length | 10 mm |
| Types of signaling | LED |
|---|
| POut | > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting) |
|---|---|
| UOut | > 0.9 x USet (LED lights up green); < 0.9 x USet (LED flashes green) |
| Number of phases | 1 |
|---|---|
| Insulation voltage input/output | 4 kV AC (type test); 3 kV AC (routine test) |
| Switching frequency | 4.00 kHz ... 70.00 kHz (Auxiliary converter stage); 80.00 kHz ... 190.00 kHz (Main converter stage); 30.00 kHz ... 150.00 kHz (PFC stage) |
| Product type | Power supply |
|---|---|
| Product family | QUINT POWER |
| MTBF (IEC 61709, SN 29500) | > 1848000 h (25 °C); > 1060000 h (40 °C); > 459000 h (60 °C) |
| Protection class | II |
|---|---|
| Overvoltage category (EN 61010-1) | II (≤ 5000 m) |
| Overvoltage category (EN 62477-1) | III (≤ 2000 m) |
| Degree of pollution | 2 |
| Width | 22.5 mm |
|---|---|
| Height | 106 mm |
| Depth | 90 mm |
| Installation distance right/left (active) | 15 mm / 15 mm (POut ≥50% ) |
|---|---|
| Installation distance right/left (passive) | 5 mm / 5 mm (POut ≥50% ) |
| Installation distance right/left (active, passive) | 0 mm / 0 mm (POut ≤50 %) |
| Installation distance top/bottom (active) | 30 mm / 30 mm (POut ≥50% ) |
| Installation distance top/bottom (passive) | 30 mm / 30 mm (POut ≥50% ) |
| Installation distance top/bottom (active, passive) | 30 mm / 30 mm (POut ≤50 %) |
| Mounting type | DIN rail mounting |
|---|---|
| With protective coating | no |
| Flammability rating according to UL 94 (housing / terminal blocks) | V0 |
|---|---|
| Housing material | Plastic |
| Type of housing | Polycarbonate |
| Hood version | Polycarbonate |
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C Derating - 2,5 %/K) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 5000 m (> 2000 m, observe derating) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz - 2.3 g 90 Min. (in accordance with IEC 60068-2-6) |
| Temp code | T4 (-25 ... +70 °C; > 60 °C, Derating - 2,5 %/K) |
| Rail applications | EN 50121-3-2; EN 50121-4; EN 50121-5; IEC 62236-3-2; IEC 62236-4; IEC 62236-5 |
|---|---|
| Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
| Standard – Safety extra-low voltage | IEC 61010-1 (SELV); IEC 61010-2-201 (PELV) |
| Standard - Safe isolation | IEC 61558-2-16; IEC 61010-2-201 |
| Standard - safety for equipment for measurement, control, and laboratory use | IEC 61010-1; IEC 61010-2-201 (SELV) |
| Standard - Safety of transformers | EN 61558-2-16 |
| SIQ | CB-Scheme (IEC 61010-1, IEC 61010-2-201) |
|---|---|
| UL approvals | UL Listed UL 61010-1; UL Listed UL 61010-2-201; UL 1310 Class 2 Power Units; UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
Model numbers in this series (1)
Send us the complete code you need and we will quote it.
2904605
About the QUINT4-PS/1AC/12DC/2.5/PT
QUINT POWER power supply for DIN-rail mounting with maximum functionality. Primary-switched power supply unit QUINT POWER, Push-in connection, DIN rail mounting, input: 1-phase, output: 12 V DC / 2.5 A, adjustable from 12 V DC ... 15 V DC Order no. 2904605.