Scope T&M MAG D Step-Up Transformer for CT Excitation and Demagnetisation

Model number
MAG D

Test set for plotting excitation curves and knee points of instrument transformers; also demagnetises cores and runs VT turns-ratio tests.

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: Scope T&M MAG D Step-Up Transformer for CT Excitation and Demagnetisation.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Quick excitation curve plotting and CT knee-point testing
  • Transformer core demagnetisation
  • VT turns-ratio testing
  • Built-in voltmeter and ammeter
  • Separate HV and LV outputs with online switching
  • Two-hand control, Variac zero interlock, thermal cut-off

Specifications

Electrical
HV output (20/21)0-2200 V AC, 0.5 A continuous / 1 A for 35 s, 10 min off
HV output (30/31)0-3000 V AC, 0.4 A continuous / 0.8 A for 35 s, 10 min off
HV output (50/51)0-5000 V AC, 0.3 A continuous / 0.6 A for 35 s, 10 min off
LV output0-250 V AC, 8 A continuous
Mains input230 V ±15%, 50 Hz ±10%
General
Voltmeter HV0-2200 / 0-3000 / 0-5000 V AC; LV 0-250 V AC
Ammeter HV0-1.5 A / 0-1 A / 0-0.5 A; LV 0-10 A
Environment
Operating temperature0 to 50 °C, up to 95% RH non-condensing
Physical
Dimensionsapprox. 450 x 500 x 590 mm
Weight46 kg

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details