Kusam Meco TW2S Current Loop Isolating Supply Transmitter, Dual Input and Dual Output

Model number
TW2S

Two-channel loop supply isolator: powers two 2-wire 4 – 20 mA transmitters (24 V) and gives two isolated DC outputs, ±0.1%, DIN rail.

Price and availability on request

Request a quote

Sent with the product details: Kusam Meco TW2S Current Loop Isolating Supply Transmitter, Dual Input and Dual Output.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Downloads

Key features

  • Isolates and converts DC signals for PLC, SCADA and control circuits
  • Input and output chosen when ordering; DIP-switch selectable for standard signals
  • Fire-retardant polycarbonate case, DIN rail or wall mounting

Specifications

Model
Accuracy±0.1% of rated output
Inputs2 × DC 4 – 20 mA, 2-wire, external DC 24 V loop supply
Outputs2, each DC 0 – 10 mA, 0 – 20 mA, 4 – 20 mA, 0 – 5 V, 1 – 5 V or 0 – 10 V
Input impedance≤ 50 Ω
Loop supplyDC 22 – 28 V (without load)
Aux. power codesC DC 22 – 72 V; F AC/DC 85 – 265 V
General
Insulation resistance> 100 MΩ / DC 500 V
Linearity and repeatability≤ 0.1% typical
Stability≤ 0.2% / year
Output loadDC current mode > 750 Ω at 20 mA; DC voltage mode 10 mA maximum
Common mode rejection> 120 dB, DC to 60 Hz
Adjust rangeSpan and zero ±10%
Response time≤ 400 ms
Ripple≤ 0.1% rms of rated output
Temperature coefficient≤ 100 ppm / °C from 0 – 60 °C; ≤ 50 ppm at 25 °C ± 5 °C
Operating conditions−5 °C – +55 °C, 20 – 95% RH non-condensing
Storage temperature−10 °C – +70 °C
Aux. powerAC/DC 85 – 265 V or 22 – 72 V; effect ≤ 0.03% / V
HousingNon-combustible PC, UL 94 V-0
MountingDIN rail or wall
Dimensions27 mm (W) × 119 mm (H) × 72 mm (L)
CE conformityEMI EN 61000-6-4; EMS EN 61000-6-2; LVD EN 61010-1

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.