Kusam Meco TAT Thermocouple Alarm Setter Transmitter with Display
- Brand
- Kusam Meco
- Model number
- TAT
- Category
- Signal Conditioners
Thermocouple transmitter with LED display and 2 alarm set points: K, E, J, T, R, S or B input to an isolated DC output (mA or V), 27 mm DIN rail housing.
Price and availability on request
Downloads
- Datasheet: Kusam Meco TAT PDF, 492 KB
Key features
- Isolates and converts DC signals for PLC, SCADA and control circuits
- Input and output chosen when ordering; DIP-switch selectable for standard signals
- Fire-retardant polycarbonate case, DIN rail or wall mounting
- LED display
- Two alarm outputs
Specifications
| Accuracy | ±0.2% of rated output |
|---|---|
| Input | K −270 – 1370 °C; E −270 – 800 °C; J −210 – 700 °C; T −210 – 400 °C; R 0 – 1700 °C; S 0 – 1700 °C; B 0 – 1750 °C |
| Alarm | 2 alarm set points, or none |
| Output | DC 0 – 10 mA, 0 – 20 mA, 4 – 20 mA, 0 – 5 V, 1 – 5 V or 0 – 10 V, or none |
| Input impedance | Voltage input ≥ 1 MΩ; current input ≤ 50 Ω |
| Input protection | ≥ 2 V DC inputs: ≤ 300 V rms continuous; ≤ 2 V DC inputs: ≤ 150 V rms continuous; ≤ 20 mA DC inputs: ≤ 150 mA continuous |
| Aux. power codes | C DC 22 – 72 V; F AC/DC 85 – 265 V (AC and DC) |
| Insulation resistance | > 100 MΩ / DC 500 V |
|---|---|
| Linearity and repeatability | ≤ 0.1% typical |
| Stability | ≤ 0.2% / year |
| Output load | DC current mode > 750 Ω at 20 mA; DC voltage mode 10 mA maximum |
| Common mode rejection | > 120 dB, DC to 60 Hz |
| Adjust range | Span and zero ±10% |
| Response time | ≤ 400 ms |
| Ripple | ≤ 0.1% rms of rated output |
| Temperature coefficient | ≤ 100 ppm / °C from 0 – 60 °C; ≤ 50 ppm at 25 °C ± 5 °C |
| Operating conditions | −5 °C – +55 °C, 20 – 95% RH non-condensing |
| Storage temperature | −10 °C – +70 °C |
| Aux. power | AC/DC 85 – 265 V or 22 – 72 V; effect ≤ 0.03% / V |
| Housing | Non-combustible PC, UL 94 V-0 |
| Mounting | DIN rail or wall |
| Dimensions | 27 mm (W) × 119 mm (H) × 72 mm (L) |
| CE conformity | EMI EN 61000-6-4; EMS EN 61000-6-2; LVD EN 61010-1 |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.