Delta PMT-5V350W1AM 5V 60A 300W Panel Mount Power Supply, PMT Series
- Brand
- Delta
- Model number
- PMT-5V350W1AM
PMT panel mount power supply with 5V 60A output (300W) from 90-132Vac or 180-264Vac. Aluminium case and fan cooling, operating -20 to +70 °C.
Price and availability on request
Key features
- AC input range selectable by switch
- Full Aluminum casing for light weight and corrosion resistant handling
- Built-in automatic fan speed control circuit
- Wide operating temperature range from -20°C to +70°C and cold start at -40°C
- MTBF > 700,000 hrs as per Telcordia SR-332
- Short Circuit / Overvoltage / Overload / Over Temperature Protections
Specifications
| Series | PMT Series |
|---|---|
| Mounting | Panel mount |
| Output Current | 60A |
|---|---|
| Output Voltage | 5V |
| Output Voltage Adjustment Range | 4.50-5.50Vdc |
| Output Power | 300W |
| Line Regulation | ± 0.5% typ |
| Load Regulation | ± 2.5% typ |
| PARD | < 150mVpp |
| Start-up Time | < 1000ms @ nominal input (100% load) |
| Hold-up Time | > 16ms @ 115Vac, / > 20 ms @ 230Vac |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 1000mVpp @ 10-50% load and 50-100% load |
| Start-up with Capacitive Loads | 8,000µF Max |
| Nominal Input Voltage | 100-120Vac, 200-240Vac (Selectable by Switch) |
|---|---|
| Input Voltage Range | 90-132Vac, 180-264Vac (Selectable by Switch) |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| Input Current | < 7.00A @ 115Vac, / < 4.00A @ 230Vac |
| Efficiency at 100% load | > 76.0% @ 230Vac |
| Inrush Current | < 40A @ 115Vac, / < 60A @ 230Vac |
| Leakage Current | < 3.5mA @ 240Vac |
| Case Chassis / Cover | Aluminium |
|---|---|
| Cooling System | Forced Cooling |
| Unit Weight | 0.81 kg (1.79 lb) |
| Dimensions | 215 x 115 x 50 mm / 8.46” x 4.53” x 1.97” |
| Vibration (Operating) | IEC 60068-2-6, Sine Wave: 10Hz to 150Hz @ 25m/S? (2.5G peak); 90 min per axis for all X, Y, Z direction |
|---|---|
| Operating Temperature | -20°C to +70°C |
| Storage Temperature | -40°C to +85°C |
| Power De-rating | > 50°C de-rate power by 4% /°C / > 60°C de-rate power by 1% /°C / < 100Vac de-rate power by 3%/V, / < 200Vac de-rate power by 1.5%/V |
| Operating Humidity | 5 to 95% RH (Non-Condensing) |
| Shock Test (Non-Operating) | IEC60068-2-27, Half Sine: 50G for a duration of 11ms, 3 times per direction, 18 times in total |
| Vibration (Non-Operating) | IEC 60068-2-6, Random: 5Hz to 500Hz @ 2.09Grms peak; 20 min per axis for all X, Y, Z direction |
| Operating Altitude | 0 to 5,000 Meters (0 to 16,400 ft) |
| Pollution Degree | 2 |
| Over Voltage Category | II |
| Overvoltage | < 5.75~7.50V, SELV Output, Latch Mode |
|---|---|
| Overload / Overcurrent | > 105~175% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery) |
| Over Temperature | Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Short Circuit | Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Protection Against Shock | Class I with Primary Earth connection |
| MTBF | > 700,000 hrs. as per Telcordia SR-332 |
|---|
| Electrical Safety | UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File no. E131881), CB scheme to IEC 60950-1 |
|---|---|
| Galvanic Isolation | Input to Output: 3.0KVac / Input to Ground: 1.5KVac / Output to Ground: 0.5KVac |
| Safety Entry Low Voltage | SELV (EN 60950-1) |
| Material and Parts | RoHS Directive 2011/65/EU Compliant |
| Emission | CISPR32, EN55032, FCC Title 47: Class A (Test with Delta EMI filter P/N: 10DKAW5) |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.