Delta IMA-S1000-24 24V 42A 1000W Enclosed Power Supply, IMA Series
- Brand
- Delta
- Model number
- IMA-S1000-24
IMA enclosed power supply with 24V 42A output (1000W) from 80-275Vac or 120-300Vdc. Fan cooling, operating -20 to +70 °C.
Price and availability on request
Specifications
| Series | IMA Series |
|---|---|
| Mounting | Enclosed |
| Output Current | 42A |
|---|---|
| Output Voltage | 24V |
| Output Voltage Adjustment Range | 19.2-28.8V |
| Output Power | 1000W |
| PARD | < 150 mV |
| Start-up Time | < 2.5 s (@ AC OFF to ON, max. load) / < 150 ms (@ REMOTE OFF to ON, max. load) |
| Hold-up Time | 20 msec nominal |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | < 5% |
| Nominal Input Voltage | 100-240Vac |
|---|---|
| Input Voltage Range | 80-275Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| DC Input Voltage Range | 120-300Vdc |
| Input Current | 15A @ 80Vac / 9.5A @ 120Vdc |
| Efficiency at 100% load | 92% @ 115Vac / 94% @ 230Vac |
| Inrush Current | < 20A |
| Power Factor at 100% load | 0.9 (typical) |
| Cooling System | 2 fans with variable speed control |
|---|---|
| Unit Weight | 1.6 kg (3.53 lb) |
| Dimensions | 209.5 x 127 x 40 mm / 8.25” x 5.00” x 1.57” |
| Operating Temperature | -20°C to +70°C |
|---|---|
| Storage Temperature | -40°C to +85°C |
| Power De-rating | When AC input voltage is < 90 Vac, the output power will be reduced by 20 W per 1 V. |
| Operating Humidity | < 95% (non-condensing) |
| Shock Test (Non-Operating) | IEC 60068-2-27 compliant, 50 g, 11 msec, 3 shocks for each direction |
| Vibration (Non-Operating) | IEC 60068-2-6 compliant, 2.09 Grms, 5 Hz to 500 Hz, 20 minutes per side (3 planes) |
| Overvoltage | YES, latch mode / 30V to 35V |
|---|---|
| Overload / Overcurrent | YES, at 108% to 140% of nominal output current; auto recovery |
| Over Temperature | YES, auto recovery |
| Short Circuit | YES, auto recovery |
| MTBF | 500,000 hours (Telecordia SR-332, Issue 3, 25 °C, 90% confidence level) |
|---|
| Electrical Safety | IEC 62368-1 (2014) Edition 2 / UL 60950-1/CSA 22.2 No 60950-1, Edition 2 / CCC: GB17625.1-2012; GB4943.1-2011; GB/T9254-2008 |
|---|---|
| Medical Safety | IEC 60601-1(2005), EN60601-1(2006) / ANSI/AAMI ES 60601-1(2005) / CAN/CSA C22.2 No. 60601-1 (2008) |
| Galvanic Isolation | Input to Output (Reinforced): 4000 Vac; 2 x MOPP / Input to Case (Basic): 1500 Vac; 1 x MOPP / Output to Case (Basic): 1500 Vac; 1 x MOPP |
| Emission | EN 55011, EN 55022 and FCC, Class B |
|---|---|
| Harmonic Current Emissions | EN 61000-3-2, Class A |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.