Delta PMT-48V350W2BNJ 48V 7.3A 350.4W Panel Mount Power Supply, PMT2 ECO (High Line) Series
- Brand
- Delta
- Model number
- PMT-48V350W2BNJ
PMT2 ECO (High Line) panel mount power supply with 48V 7.3A output (350.4W) from 180-264 Vac. Aluminium and steel case and fan cooling, operating -40 to +70 °C.
Price and availability on request
Key features
- High line nominal input voltage 200-240 Vac
- Low profile design: 30 mm height
- Wide operating temperature range of -40°C ~70°C
- High MTBF > 700,000 hrs per Telcordia SR-332
Specifications
| Series | PMT2 ECO (High Line) Series |
|---|---|
| Mounting | Panel mount |
| Output Current | 7.3A |
|---|---|
| Output Voltage | 48V |
| Output Voltage Adjustment Range | 43.2-52.8 Vdc |
| Output Power | 350.4W |
| Line Regulation | ± 0.5% typ. @ 180-264 Vac |
| Load Regulation | ± 0.5% typ. @ 180-264 Vac |
| PARD | < 200 mVpp @ 0°C to 70°C / 600 mVpp typ. @ -30°C to 0°C |
| Start-up Time | 1500 ms typ. @ 230 Vac |
| Hold-up Time | 20 ms typ. @ 230 Vac |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 10% @ 230 Vac input, 10-100% load (Slew Rate: 2.5 A/μS, 50% duty cycle @ 5 Hz & 10 KHz) |
| Start-up with Capacitive Loads | 2,000µF Max |
| Rise Time | 30 ms typ. @ 230 Vac |
| Nominal Input Voltage | 200-240 Vac |
|---|---|
| Input Voltage Range | 180-264 Vac |
| Nominal Input Frequency | 50-60 Hz |
| Input Frequency Range | 47-63Hz |
| Input Current | 3.4 A typ. @ 230 Vac |
| Efficiency at 100% load | 87.0% typ. |
| Inrush Current | 60 A typ. @ 230 Vac |
| Leakage Current | < 0.75 mA @ 240 Vac |
| Case Chassis / Cover | SGCC / Aluminium |
|---|---|
| Indicator | Green LED (DC OK) |
| Cooling System | Force Cooling |
| Input Terminal | M3.5 x 9 Pins (Rated 300 V / 20 A) |
| Wire | AWG 18-12 / Current rating can refer to page 6 “Wire AWG Table” |
| Unit Weight | 0.833 kg (1.84 lb) |
| Dimensions | 215 x 115 x 30 mm / 8.46” x 4.53” x 1.18” |
| Vibration (Operating) | IEC 60068-2-6, Sine Wave: 20 Hz to 500 Hz (5G); 10 min per cycle, 60 min for each axis (X, Y,Z) |
|---|---|
| Shock Test (Operating) | IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11 ms, 3 shock for each 3 directions |
| Operating Temperature | -40°C to +70°C |
| Storage Temperature | -40°C to +85°C |
| Power De-rating | > 50°C de-rate power by 2% / °C |
| Operating Humidity | 20 to 90% RH (Non-Condensing) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 50G for a duration of 11 ms, 3 shocks for each 3 directions |
| Vibration (Non-Operating) | IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09G); 20 min per axis for all X, Y, Z direction |
| Operating Altitude | 0 to 5,000 Meters (16,400 ft.) |
| Pollution Degree | 3 |
| Over Voltage Category | II (Compliance to EN 62477-1 OVC III with 2000 meters altitude) |
| Overvoltage | 52.8 V-64.8 V / SELV Output, Latch Mode |
|---|---|
| Overload / Overcurrent | 110-175% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Over Temperature | Latch Mode |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Protection Against Shock | Class I with Primary Earth connection |
| MTBF | > 700,000 hrs as per Telcordia SR-332 (I/P: 230Vac, O/P: 100% Load, Ta: 25°C) |
|---|---|
| Expected Cap Life Time | 10 years (230Vac, 50% load @ 40°C) |
| Electrical Safety | CB scheme: IEC 62368-1 / CQC: GB 4943.1 / BIS: IS 13252 (Part 1) |
|---|---|
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU / This power supply does not comply with the harmonic current emission requirements specified in EN61000-3-2. Please ensure it is not used in applications where compliance with this standard is required. |
| Galvanic Isolation | Input to Output: 3.0 KVac / Input to Ground: 2.0 KVac / Output to Ground: 0.5 KVac |
| Safety Entry Low Voltage | SELV |
| Emission | (CE & RE) / CISPR 32, EN 55032, Class A |
|---|---|
| Immunity | EN 55035 |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.