Delta PMT-48V200W2BM 48V 0-4.4A 211.2W Panel Mount Power Supply, PMT2 Series
- Brand
- Delta
- Model number
- PMT-48V200W2BM
PMT2 panel mount power supply with 48V 0-4.4A output (211.2W) from 90-132 Vac or 180-264 Vac. Aluminium and steel case and convection cooling, operating -40 to +70 °C. With household appliance approvals.
Price and availability on request
Key features
- Household appliance approvals for pollution degree 3 to IEC/EN/BS EN 60335-1, IEC/EN/BS EN 61558-1 and IEC/EN/BS EN 61558-2-16
- AC input voltage range selectable by switch (90-132Vac, 180-264Vac)
- No load power consumption < 0.5W
- Low profile design: 30mm height
- Over voltage category III
- Wide operating temp -40°C ~70°C (Support -40°C cold start)
- Conforms to harmonic current IEC/EN/BS EN 61000-3-2, Class A
- High MTBF > 700,000 hrs per Telcordia SR-332
Specifications
| Series | PMT2 Series |
|---|---|
| Mounting | Panel mount |
| Output Current | 0-4.4A |
|---|---|
| Output Voltage | 48V |
| Output Voltage Adjustment Range | 43.2-52.8 Vdc |
| Output Power | 211.2W |
| Line Regulation | ± 0.5% typ. @ 100-132 Vac, / 180-264 Vac (Selectable by Switch) |
| Load Regulation | ± 0.5% typ. @ 100-132 Vac, 180-264 Vac (Selectable by Switch) |
| PARD | < 200 mVpp @ 0°C to 70°C, / 600 mVpp typ. @ -30°C to 0°C |
| Start-up Time | 500 ms typ. @ 115 Vac & 230 Vac |
| Hold-up Time | 30 ms typ. @ 115 Vac & 230 Vac |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 10% @ 115 & 230 Vac input, 10-100% load / (Slew Rate: 2.5 A / μS, 50% duty cycle @ 5 Hz & 10 KHz) |
| Start-up with Capacitive Loads | 2,000 µF Max |
| Rise Time | 30 ms typ. @ 115 Vac & 230 Vac |
| Nominal Input Voltage | 100-120 Vac, 200-240 Vac (Selectable by Switch) |
|---|---|
| Input Voltage Range | 90-132 Vac, 180-264 Vac (Selectable by Switch) |
| Nominal Input Frequency | 50-60 Hz |
| Input Frequency Range | 47-63Hz |
| Input Current | 4 A typ. @ 115 Vac, / 2.2 A typ. @ 230 Vac |
| Efficiency at 100% load | 91% typ. @230 Vac |
| Inrush Current | 60 A typ. @ 230 Vac |
| Leakage Current | < 0.5 mA @ 240 Vac / 50 Hz |
| Case Chassis / Cover | Aluminum / SGCC |
|---|---|
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Noise Sound Pressure Level (SPL) | < 25 dBA |
| Wire | AWG 18-12 |
| Unit Weight | 0.42 kg (0.93 lb) |
| Dimensions | 159 x 97 x 30 mm / 6.26” x 3.82” x 1.18” |
| Vibration (Operating) | IEC 60068-2-6, Sine Wave: 20 Hz to 500 Hz (5 G); 10 min per cycle, 60min for each axis (X, Y,Z) |
|---|---|
| Shock Test (Operating) | IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11ms, 3 shock for each 3 directions. |
| Operating Temperature | -40°C to +70°C |
| Storage Temperature | -40°C to +85°C |
| Power De-rating | > 50°C de-rate power by 2% / °C / < 100 Vac de-rate power by 2% / V / (80% load @ 90 Vac) |
| Operating Humidity | 20 to 90% RH (Non-Condensing) |
| Shock Test (Non-Operating) | IEC 60068-2-27, Half Sine Wave: 50G for a duration of 11ms, 3 shocks for each 3 directions |
| Vibration (Non-Operating) | IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction |
| Operating Altitude | 0 to 5,000 Meters (0 to 16,400 ft) |
| Pollution Degree | 3 |
| Over Voltage Category | II (Compliance to EN 62477-1 OVC III with 2000 meters altitude) |
| Overvoltage | 52.8 V - 64.8 V SELV Output, Latch Mode |
|---|---|
| Overload / Overcurrent | 110-175% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) |
| Over Temperature | Latch Mode |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Protection Against Shock | Class I with Protection Earth connection |
| MTBF | > 700,000 hrs as per Telcordia SR-332 I/P: 230 Vac, O/P: 100% Load, Ta: 25°C) |
|---|---|
| Expected Cap Life Time | 10 years (230 Vac, 50% load @ 40°C) |
| Electrical Safety | PMT-48V200W2BR: / TUV Bauart: EN 62368-1,EN 60335-1, EN 61558-1/-2-16 / cULus: UL 62368-1, and CAN/CSA C22.2 No. 62368-1 / CB scheme: IEC 62368-1, IEC 60950-1, IEC 60335-1, IEC 61558-1/-2-16 / KC: K 60950-1 / EAC: TP TC 004/2011 / BSMI: CNS 14336-1 / BIS: IS 13252 (Part 1) / CCC: GB4943.1 / / PMT-48V200W2BM: / cULus: UL 62368-1, and CAN/CSA C22.2 No. 62368-1 / CB scheme: IEC 62368-1, IEC 60950-1 / EAC: TP TC 004/2011 / CQC: GB 4943.1 |
|---|---|
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU / This power supply does not comply with the harmonic current emission requirements specified in BS EN/EN61000-3-2. Please ensure it is not used in applications where compliance with this standard is required. |
| Galvanic Isolation | Input to Output: 4.0 KVac / Input to Ground: 2.0 KVac / Output to Ground: 1.25 KVac |
| Safety Entry Low Voltage | SELV |
| UKCA | In conformance with Electromagnetic Compatibility Regulations 2016 and Electrical Equipment (Safety) Regulations 2016 |
| Emission | (CE & RE) / CISPR 32, EN/BS EN 55032, EN/BS EN 61000-6-4, KN32, AS/NZS CISPR 32 / Compliance to EN/BS EN 55014-1, FCC Title 47, EN/BS EN 61000-6-3 : Class B |
|---|---|
| Immunity | EN/BS EN 55035, KN35, EN/BS EN 61000-6-2 & Compliance to EN/BS EN 55014-2,EN/BS EN 61000-6-1 |
| Harmonic Current Emissions | IEC/EN/ BS EN 61000-3-2 Class A |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.