Delta PMC-24V600W1RW 24V 25A 600W Panel Mount Power Supply, PMC Series
- Brand
- Delta
- Model number
- PMC-24V600W1RW
PMC panel mount power supply with 24V 25A output (600W) from 85-264Vac. Steel case and fan cooling, operating -20 to +70 °C. With a constant-current mode and conformal-coated boards.
Price and availability on request
Key features
- Universal AC input range
- Active PFC with high PF value
- Meet Surge Immunity IEC 61000-4-5, Level 4 (CM: 4kV, DM: 2kV)
- Wide operating temperature range -20°C to 70°C
- Compact Size
- Conformal coating on PCBA to protect against chemical and dust pollutants
- Built-in constant current circuit for reactive loads
- Design compliance with Japan PSE (DENAN)
Specifications
| Series | PMC Series |
|---|---|
| Mounting | Panel mount |
| Output Current | 25A |
|---|---|
| Output Voltage | 24V |
| Output Voltage Adjustment Range | 21.6-27.6Vdc |
| Output Power | 600W |
| Line Regulation | ± 0.4% typ. (@ 115 & 240Vac input, 100% load) |
| Load Regulation | ± 0.5% typ. (@115 & 240Vac input, 100% load) |
| PARD | < 150mVpp @ 0°C to 70°C, / 180mVpp typ. @ -20°C to 0°C |
| Start-up Time | 500ms typ. @ 230Vac (100% load) |
| Hold-up Time | 20ms typ. @ 115Vac & 230Vac (100% load) |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 5% @ 50-100% load |
| Start-up with Capacitive Loads | 10,000μF Max |
| Rise Time | < 50ms @ 115Vac & 230Vac (100% load) |
| Nominal Input Voltage | 100-240Vac |
|---|---|
| Input Voltage Range | 85-264Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| Input Current | 6A typ. @ 115Vac, 3A typ. @ 230Vac |
| Efficiency at 100% load | 90.0% typ. @ 115Vac, 92.0% typ. @ 230Vac |
| Inrush Current | 40 A typ. @ 230 Vac |
| Power Factor at 100% load | 0.99 typ. @ 100Vac, 0.97 typ. @ 200Vac |
| Leakage Current | < 0.75mA @ 240Vac |
| Case Chassis / Cover | SGCC |
|---|---|
| Cooling System | Built-in Fan |
| Input Terminal | M3.5 x 3 Pins (Rated 300Vac/20A) |
| Output Terminal | M4 x 4 Pins (Rated 300Vac/25A) |
| Signal Terminal | Signal Connector: JST S8B-PHDSS(LF)(SN) / Mating connector: JST PHDR-08VS or equivalent |
| Noise Sound Pressure Level (SPL) | < 60dBA |
| Unit Weight | 1.4 kg (3.09 lb) |
| Dimensions | 190 x 120 x 61 mm / 7.48” x 4.72” x 2.40” |
| Vibration (Operating) | IEC60068‐2‐6, Sine Wave: 10Hz to 55Hz @19.6m/s2(2G peak); / 10min per cycle, 60min per axis for all X,Y,Z direction |
|---|---|
| Shock Test (Operating) | IEC60068‐2‐27, Half Sine Wave: 10G for a duration of 11ms, 3 shocks for each 3 directions |
| Operating Temperature | -20°C to +70°C |
| Storage Temperature | -30°C to +75°C |
| Power De-rating | > 50°C de-rate power by 2.5% / °C / < 110Vac de-rate power by 0.8% / 1V |
| Operating Humidity | 20-95% RH |
| Shock Test (Non-Operating) | IEC60068‐2‐27, Half Sine Wave: 50G for a duration of 11ms, 3 shocks for each 3 directions |
| Vibration (Non-Operating) | IEC60068‐2‐6, Random: 5Hz to 500Hz (2.09Grms); / 20min per axis for all X,Y,Z direction |
| Operating Altitude | 5,000 Meters |
| Pollution Degree | 2 |
| Over Voltage Category | II (Compliance to EN 62477-1 OVC III with 2000 meters altitude) |
| Overvoltage | 27.6-33.6V, SELV Output, Latch-off Mode |
|---|---|
| Overload / Overcurrent | 105~160%; Constant current limit with automatic recovery |
| Over Temperature | Latch-off Mode |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
| Protection Against Shock | Class I with PE connection |
| MTBF | > 700,000 hrs as per Telcordia SR-332 / I/P: 115Vac, O/P: 100% Load, Ta: 25°C) |
|---|---|
| Expected Cap Life Time | 10 years (115 Vac, 50% load @ 40°C) |
| Electrical Safety | TUV Bauart: EN 62368-1 / UL/cUL: UL 62368-1, and CAN/CSA C22.2 No. 62368-1 / CB scheme: IEC 62368-1, IEC 60950-1, IEC 61010-1 / KC: K 60950-1 / CCC: 4943.1 |
|---|---|
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| Galvanic Isolation | Input to Output: 3.0KVac / Input to Ground: 1.8KVac / Output to Ground: 0.5KVac |
| Safety Entry Low Voltage | SELV |
| UKCA | In conformance with Electromagnetic Compatibility Regulations 2016 and Electrical Equipment (Safety) Regulations 2016 |
| Emission | CISPR 32, EN/BS EN 55032 / Compliance to FCC Title 47, VCCI, EN 55011 : Class B |
|---|---|
| Immunity | EN/BS EN 55035, KN35 / Compliance to EN 61000-6-2 |
| Harmonic Current Emissions | IEC/EN/BS EN 61000-3-2 Class A |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 |
| ESD Immunity | IEC 61000-4-2: Level 4 Criteria A / Air Discharge: 15kV / Contact Discharge: 8kV |
| EFT | IEC 61000-4-4: Level 3 Criteria A / 2kV |
| Surge | IEC 61000-4-5: Level 4 Criteria A / Common Mode: 4kV / Differential Mode: 2kV |
| Conducted Immunity | IEC 61000-4-6 : Level 3 Criteria A / 150kHz-80MHz, 10Vrms |
| Magnetic Field | IEC 61000-4-8 : Level 4 Criteria A / 30A/Meter |
| Voltage Dips | IEC 61000-4-11 : / 0% residual; 1 cycle, Criteria B / 40% residual; 10 cycle, Criteria C / 70% residual; 25 cycle, Criteria C |