Delta PMC-24V150W2AA 24V 6.25A 150W Panel Mount Power Supply, PMC Series
- Brand
- Delta
- Model number
- PMC-24V150W2AA
PMC panel mount power supply with 24V 6.25A output (150W) from 180-264Vac or 220-375Vdc. Aluminium case and convection cooling, operating -10 to +70 °C.
Price and availability on request
Key features
- High line AC input range from 180Vac to 264Vac without power de-rating
- Full Aluminum casing for light weight and corrosion resistant handling
- High MTBF > 700,000 hrs. as per Telcordia SR-332
- Overvoltage / Overcurrent / Over Temperature Protections
- Certified according to IEC/EN/UL 62368-1
Specifications
| Series | PMC Series |
|---|---|
| Mounting | Panel mount |
| Output Current | 6.25A |
|---|---|
| Output Voltage | 24V |
| Output Voltage Adjustment Range | 22-28Vdc |
| Output Power | 150W |
| Line Regulation | < 0.5% typ. (@ 85-264Vac input, 100% load) |
| Load Regulation | < 1% typ. (@ 170-264Vac input, 0-100% load) |
| PARD | <100mVpp |
| Start-up Time | < 1000ms @ nominal input (100% load) |
| Hold-up Time | > 20ms @ 230Vac (100% load) |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 5% @ 170-264 Vac input, 0-100% load / (Slew Rate: 0.1 A/μs, 50% duty cycle @ 5 Hz) |
| Start-up with Capacitive Loads | 8,000µF Max |
| Residual Ripple/PARD (20MHz) | <100 mVpp |
| Rise Time | < 30ms @ nominal input (100% load) |
| Nominal Input Voltage | 200-240Vac |
|---|---|
| Input Voltage Range | 180-264Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| Nominal DC Input Voltage | 220-250Vdc |
| DC Input Voltage Range | 220-375Vdc |
| Input Current | < 1.60A @ 230Vac |
| Efficiency at 100% load | > 87.0% @ 230Vac |
| Inrush Current | < 120A @ 230Vac |
| Power Factor at 100% load | Conform to EN61000-3-2, Class A |
| Leakage Current | < 1mA @ 240Vac |
| Case Chassis / Cover | Aluminium |
|---|---|
| Indicator | Green LED (DC OK) |
| Cooling System | Convection |
| Noise Sound Pressure Level (SPL) | <40dBA |
| Input/Output Terminal | M3.5 x 7 Pins (Rated 300V/15A) |
| Wire | AWG 20-14 |
| Unit Weight | 0.50 kg (1.10 lb) |
| Dimensions | 178 x 97 x 38 mm / 7.01” x 3.82” x 1.50” |
| Operating Temperature | -10°C to +70°C |
|---|---|
| Storage Temperature | -25°C to +85°C |
| Power De-rating | > 50°C de-rate power by 2.5% /°C |
| Operating Humidity | < 95% RH |
| Shock Test (Non-Operating) | IEC60068-2-27, 30G (300m/S²) for a duration of 18ms 1 times per direction, 6 times in total |
| Vibration (Non-Operating) | IEC60068-2-6, 10Hz to 500Hz @ 50m/S² (5G peak); 20 min per axis for all X, Y, Z direction |
| Pollution Degree | 2 |
| Overvoltage | < 32V ±10%, SELV output, Hicc-up Mode, Non-Latching (Auto recovery). |
|---|---|
| Overload / Overcurrent | > 120% of rated load current, Hicc-up Mode, Non-Latching (Auto recovery). |
| Over Temperature | < 75°C Ambient Temp@ 100% load, Non-Latching (Auto-recovery). |
| Short Circuit | Hicc-up Mode, Non-Latching (Auto-recovery when the fault is removed). |
| Protection Against Shock | Class I with Primary Earth connection |
| MTBF | > 700,000 hrs. per Telcordia SR-332 |
|---|---|
| Expected Cap Life Time | 10 years (115Vac & 230Vac, 50% load @ 40°C) |
| Electrical Safety | TUV Bauart: EN 62368-1 / UL/cUL recognizedP: UL 60950-1 and CSA C22.2 No. 60950-1, UL 62368-1 and CSA C22.2 No. 62368-1 / CB scheme: IEC 60950-1, IEC 62368-1 / CCC: GB/T9254, GB 17625.1 and GB 4943.1 / 仅适用于海拔 2000m 以下地区安全使用 |
|---|---|
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| Galvanic Isolation | Input to Output: 3.0 KVac / Input to Ground: 1.5 KVac / Output to Ground: 500 Vac |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and / The Electromagnetic Compatibility Regulations 2016 No. 1091 |
| Emission | Generic Standards: CISPR32, EN/BS EN 55032, / FCC Title 47: Class B, GB 9254 |
|---|---|
| Immunity | Generic Standards: EN/BS EN 55024 |
| Harmonic Current Emissions | IEC/EN/BS EN 61000-3-2, Class A |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 |
| Tags | 2 phase |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.