Delta PMC-12V600W1BA 12V 50A 600W Panel Mount Power Supply, PMC Series
- Brand
- Delta
- Model number
- PMC-12V600W1BA
PMC panel mount power supply with 12V 50A output (600W) from 85-264 Vac or 120-375 Vdc. Steel case and fan cooling, operating -20 to +70 °C. With power boost, active PFC and SEMI F47 compliance.
Price and availability on request
Key features
- Universal AC input range
- Built-in active PFC and high efficiency up to 89% @ 230Vac
- Power Boost of 200% for 3 seconds and 150% for 5 seconds
- SEMI F47 compliance at 120Vac
- Meet Surge Immunity IEC 61000-4-5, Level 4 (CM: 4kV, DM: 2kV)
- Built-in fan speed control and fan lock protection
- Wide operating temperature range -20°C to 70°C
- Overvoltage / Overcurrent / Over Temperature / Short Circuit Protections
Specifications
| Series | PMC Series |
|---|---|
| Mounting | Panel mount |
| Output Current | 50A |
|---|---|
| Output Voltage | 12V |
| Output Voltage Adjustment Range | 10.8-13.2 Vdc |
| Output Power | 600W |
| Line Regulation | <48mV (@115-264 Vac input, 100% load) |
| Load Regulation | <100mV (@115-264 Vac input, 0-100% load) |
| PARD | <240 mVpp |
| Start-up Time | <500 ms @ 115 Vac & 230 Vac (100% load) |
| Hold-up Time | <20 ms @ 115 Vac & 230 Vac (100% load) |
| Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 5% @ 115-264 Vac input, 10-100% / Slew Rate: 0.1Aµs, 50% duty cycle @ 5 Hz to 1 kHz) |
| Start-up with Capacitive Loads | 10,000 µF Max |
| Rise Time | <50 ms @ 115 Vac & 230 Vac (100% load) |
| Nominal Input Voltage | 100-240 Vac |
|---|---|
| Input Voltage Range | 85-264 Vac |
| Nominal Input Frequency | 50-60Hz |
| Input Frequency Range | 47-63Hz |
| DC Input Voltage Range | 120-375 Vdc |
| Input Current | <6.50 A @115 Vac, <3.20 A @230 Vac |
| Efficiency at 100% load | >85% @115 Vac, >89% @230 Vac |
| Inrush Current | <10 A @ 115 Vac & <20 A @ 230 Vac |
| Power Factor at 100% load | >0.98 @ 115 Vac, >0.95 @ 230 Vac |
| Case Chassis / Cover | SECC |
|---|---|
| Indicator | Green LED DC OK |
| Cooling System | Forced Cooling (Built-in Fan) |
| Input Terminal | M3.5 x3 Pins (Rated 300V/20A) |
| Output Terminal | M6 x2 Pins (Rated 600V/50A) |
| Noise Sound Pressure Level (SPL) | <52dBA |
| Wire | Input AWG 14-12 / Output AWG 6-4 |
| Unit Weight | 1.51 kg (3.33 lb) |
| Dimensions | 215 x 120 x 61 mm / 8.46” x 4.72” x 2.40” |
| Vibration (Operating) | IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); / displacement of 0.35mm; 20 min per axis for all X,Y,Z |
|---|---|
| Shock Test (Operating) | IEC 60068-2-27, 30G (300m/S² for a duration of 18ms 1 times per direction, / times in total |
| Operating Temperature | -20°C to +70°C |
| Storage Temperature | -40°C to +75°C |
| Power De-rating | > 50°C de-rate power by 2.5% / °C |
| Operating Humidity | 5 to 95% RH |
| Operating Altitude | 0 to 3,000 Meters (9,840 ft.) |
| Pollution Degree | 2 |
| Over Voltage Category | II |
| Overvoltage | <17.6V, SELV Output, Latch Mode |
|---|---|
| Overload / Overcurrent | >150% of rated load current, Hiccup Mode, / Non-Latching (Auto-Recovery) |
| Over Temperature | < 80°C Surrounding Air Temp@ 100% load, Latch Mode |
| Short Circuit | Hiccup Mode, Non-Latching (Auto-recovery when the fault is removed). |
| Protection Against Shock | Class I with PE* connection |
| MTBF | >700,000 hrs. as per Telcordia SR-332 / I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C |
|---|---|
| Expected Cap Life Time | 10 years (115Vac & 230Vac, 50% load @ 40°C |
| Electrical Safety | SIQ Bauart EN60950-1, EN 62368-1 / UL/cUL recognized UL60950-1 and CSA C22.2 No. 60950-1, / UL 62368-1 and CSA C22.2 No. 62368-1 / CB scheme IEC 60950-1, IEC 62368-1 |
|---|---|
| CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
| Galvanic Isolation | Input to Output: 3.0KVac / Input to Ground: 2.0Kvac / Output to Ground: 0.5KVac |
| Safety Entry Low Voltage | SELV (IEC 60950-1) |
| Material and Parts | RoHS Directive 2011/65/EU Compliant |
| UKCA | In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and / The Electromagnetic Compatibility Regulations 2016 No. 1091 |
| Emission | Generic Standards: / CISPR 32, EN/BS EN 55032, CISPR 11, EN/BS EN 55011, FCC Title 47, / VCCI: Calss B |
|---|---|
| Immunity | Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2 |
| Harmonic Current Emissions | IEC/EN/BS EN 61000-3-2, Class A |
| Voltage Fluctuation and Flicker | IEC/EN/BS EN 61000-3-3 |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.