Delta IMA-S1000-24-YYPLI 24V 42A 1000W Enclosed Power Supply, IMA Series

Brand
Delta
Model number
IMA-S1000-24-YYPLI

IMA enclosed power supply with 24V 42A output (1000W) from 80-275Vac or 120-300Vdc. Fan cooling, operating -20 to +70 °C.

Price and availability on request

Request a quote

Sent with the product details: Delta IMA-S1000-24-YYPLI 24V 42A 1000W Enclosed Power Supply, IMA Series.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Specifications

Product
SeriesIMA Series
MountingEnclosed
Output
Output Current42A
Output Voltage24V
Output Voltage Adjustment Range19.2-28.8V
Output Power1000W
PARD< 150 mV
Start-up Time< 2.5 s (@ AC OFF to ON, max. load) / < 150 ms (@ REMOTE OFF to ON, max. load)
Hold-up Time20 msec nominal
Dynamic Response (Overshoot & Undershoot O/P Voltage)< 5%
Input
Nominal Input Voltage100-240Vac
Input Voltage Range80-275Vac
Nominal Input Frequency50-60Hz
Input Frequency Range47-63Hz
DC Input Voltage Range120-300Vdc
Input Current15A @ 80Vac / 9.5A @ 120Vdc
Efficiency at 100% load92% @ 115Vac / 94% @ 230Vac
Inrush Current< 20A
Power Factor at 100% load0.9 (typical)
Mechanical
Cooling System2 fans with variable speed control
Unit Weight1.6 kg (3.53 lb)
Dimensions209.5 x 127 x 40 mm / 8.25” x 5.00” x 1.57”
Environment
Operating Temperature-20°C to +70°C
Storage Temperature-40°C to +85°C
Power De-ratingWhen AC input voltage is < 90 Vac, the output power will be reduced by 20 W per 1 V.
Operating Humidity< 95% (non-condensing)
Shock Test (Non-Operating)IEC 60068-2-27 compliant, 50 g, 11 msec, 3 shocks for each direction
Vibration (Non-Operating)IEC 60068-2-6 compliant, 2.09 Grms, 5 Hz to 500 Hz, 20 minutes per side (3 planes)
Protections
OvervoltageYES, latch mode / 30V to 35V
Overload / OvercurrentYES, at 108% to 140% of nominal output current; auto recovery
Over TemperatureYES, auto recovery
Short CircuitYES, auto recovery
Reliability
MTBF500,000 hours (Telecordia SR-332, Issue 3, 25 °C, 90% confidence level)
Safety
Electrical SafetyIEC 62368-1 (2014) Edition 2 / UL 60950-1/CSA 22.2 No 60950-1, Edition 2 / CCC: GB17625.1-2012; GB4943.1-2011; GB/T9254-2008
Medical SafetyIEC 60601-1(2005), EN60601-1(2006) / ANSI/AAMI ES 60601-1(2005) / CAN/CSA C22.2 No. 60601-1 (2008)
Galvanic IsolationInput to Output (Reinforced): 4000 Vac; 2 x MOPP / Input to Case (Basic): 1500 Vac; 1 x MOPP / Output to Case (Basic): 1500 Vac; 1 x MOPP
EMC
EmissionEN 55011, EN 55022 and FCC, Class B
Harmonic Current EmissionsEN 61000-3-2, Class A

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.