Scope T&M TTRM 102 Single Phase Transformer Turns Ratio Meter
- Brand
- Scope T&M
- Model number
- TTRM 102
- Category
- Transformer Ratio Meters
Portable single-phase turns ratio meter for power, instrument and distribution transformers: ratio, ratio error, phase angle and excitation current.
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Selectable 10 V, 40 V and 100 V AC test voltages
- 5.7 inch touch-screen TFT display; configurable transformer ID
- Automatic OLTC tap changing (raise/lower)
- Date and time stamped results; 50,000 records
- Built-in thermal printer; USB 2.0 export and Ethernet
Specifications
| Channels | single HV and single LV |
|---|---|
| Measurements | ratio, ratio error, phase angle deviation, excitation current |
| Ratio range | 0.8000 to 20000 |
| Phase deviation | ±180°, 0.01° resolution, ±0.05° accuracy |
| Excitation current | 2000 mA max. at 10 V; 500 mA at 40 V; 200 mA at 100 V |
|---|---|
| Power | 110 V ±15% / 60 Hz or 230 V ±15% / 50 Hz, 75 VA |
| Printer | inbuilt thermal, 58 mm roll |
|---|
| Environment | -20 to 55 °C, 95% RH non-condensing |
|---|
| Dimensions | 435 x 315 x 175 mm max. |
|---|---|
| Weight | approx. 10 kg |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details