Schneider Electric PM5560 Power Meter, 2 Ethernet, 63rd Harmonic, 4 DI / 2 DO, Class 0.2S

Model number
PM5560

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.2S accuracy per IEC 62053-22 standard and 128 samples per cycle.

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: Schneider Electric PM5560 Power Meter, 2 Ethernet, 63rd Harmonic, 4 DI / 2 DO, Class 0.2S.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Feature-rich power and energy meters
  • Digital input and output for WAGES monitoring and control relays
  • Modbus RS-485, TCP/ IP, Ethernet IP, BACnet protocols for varied application
  • Identify energy savings opportunties with precision accuracy of Class 0.2S
  • 63rd Hamronic measurement for Power Quality management

Specifications

Technical
Power quality analysisup to the 63rd harmonic
Metering typeMeasured neutral current, Calculated ground current
Device applicationGateway, WAGES metering, Power monitoring, Multi-tariff
Type of measurementCurrent, Voltage, Frequency, Power factor, Energy, Active and reactive power
[Us] rated supply voltage100-300 V DC, 90-528 V AC 45-65 Hz
Network frequency60 Hz, 50 Hz
[In] rated current1 A, 5 A
Type of network3P + N, 3P, 1P + N
Maximum power consumption in VA16 VA at 480 V
Ride-through time35 ms 120 V AC typical, 129 ms 230 V AC typical, 50 ms 125 V DC typical
Display typeBacklit LCD
Display resolution128 x 128 pixels
Sampling rate128 samples/cycle
Measurement current50-10000 mA
Analogue input typeVoltage (impedance 5 MOhm), Current (impedance <= 0.3 mOhm)
Measurement voltage20-400 V AC 45-65 Hz between phase and neutral, 20-828 V AC 45-65 Hz between phases
Frequency measurement range45-65 Hz
Number of inputs4 digital
Measurement accuracyApparent power +/- 0.5 %, Frequency +/- 0.05 %, Active energy +/- 0.2 %, Reactive energy +/- 1 %, Active power +/- 0.2 %, Voltage +/- 0.1 %, Power factor +/- 0.005, Current +/- 0.15 %, Reactive power +/- 1 %
Accuracy classClass 0.2S active energy conforming to IEC 62053-22
Number of outputs2 digital
Information displayedTariff (8)
Communication port protocolModbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V, JBUS, Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V, Ethernet Modbus TCP/IP daisy chain, BACnet IP, DNP3 over ethernet
Communication port supportRS485, ETHERNET
Communication gatewayEthernet/serial
Data recordingEvent logs, Maintenance logs, Min/max of instantaneous values, Data logs, Alarm logs, Time stamping
Memory capacity1.1 MB
Web servicesAlarm notification by e-mail, Diagnostic via predefined web pages, Web server, Real time viewing of data
Ethernet serviceSNTP client, SNMP-Traps
Mounting modeFlush-mounted
Mounting supportFramework
StandardsEN 50470-3, IEC 61557-12:2015, IEC 62053-22:2020, IEC 62053-24, IEC 60529, EN 50470-1, UL 61010-1, ANSI C12.20, IEC 62053-23:2020, IEC 62052-11:2020, IEC 62052-31:2015
Product certificationsCE conforming to IEC 61010-1, CULus conforming to UL 61010-1, BTL
Width96 mm
Depth72 mm
Height96 mm
Net weight450 g
Environment
IP degree of protectionIP54 display - conforming to IEC 60529, IP30 rear - conforming to IEC 60529
Relative humidity5-95 % at 50 °C non-condensing
Pollution degree2
Ambient air temperature for operation-25-70 °C
Ambient air temperature for storage-40-85 °C
Operating altitude<= 3000 m

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

Model numbers in this series (2)

Send us the complete code you need and we will quote it.

  • METSEPM5560
  • 30003008D

About the PM5560

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.2S accuracy per IEC 62053-22 standard and 128 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 63rd Harmonic. Include 1.1 MegaBytes of memory for up to 14 selectable parameters with configurable interval and duration. This meter also feature the direct monitoring of neutral current. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 480 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20 to 690 VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 45 to 65 Hz. Communication protocol are Modbus RTU and ASCII 2 wires with RS485 port support plus Modbus TCP/IP, Ethernet/IP and BACnet/IP based on 10/100 Mbit/s, daisy chain Ethernet with RJ45 port support. The embedded communication capabilities allow the support of the DNP 3.0 protocol, the access to an onboard web server and a Serial to Ethernet gateway. The meter also has four digital inputs with WAGES support and two digital outputs. There are 52 configurable alarms and it supports eight tariff schedules.

Order codes: METSEPM5560, 30003008D.

Frequently asked questions

What is the Schneider Electric PM5560?

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.2S accuracy per IEC 62053-22 standard and 128 samples per cycle.

What is the accuracy of the PM5560?

Measurement accuracy: Apparent power +/- 0.5 %, Frequency +/- 0.05 %, Active energy +/- 0.2 %, Reactive energy +/- 1 %, Active power +/- 0.2 %, Voltage +/- 0.1 %, Power factor +/- 0.005, Current +/- 0.15 %, Reactive power +/- 1 %; Accuracy class: Class 0.2S active energy conforming to IEC 62053-22.

What is the measuring range of the PM5560?

45-65 Hz.

What input does the PM5560 accept?

Voltage (impedance 5 MOhm), Current (impedance <= 0.3 mOhm).

Which model numbers does this page cover?

Besides the PM5560, this page covers METSEPM5560 and 30003008D.