Schneider Electric EM1200 Power and Energy Meter, 96 x 96 mm, LCD, RS485 Modbus, Class 0.5 / 1.0
- Brand
- Schneider Electric
- Model number
- EM1200
- Category
- Power and Energy Meters
Schneider Electric Conzerv EM1200 power and energy meter: LCD display, voltage, frequency, power factor, power and energy, RS485 Modbus RTU, Class 0.5 or 1.0.
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Compact 96 x 96 mm meter for retrofit of analog meters
- Class 1.0 or 0.5 accuracy, chosen when ordering
- Voltage, frequency, power factor, power and energy in one meter
- Run hours, on hours and interruption count
- Auto-scroll through parameter groups and user-set default page
- Setup protected by password
- RS485 Modbus RTU communication
Specifications
| Measurement | True RMS, two quadrant power and energy, 1 s update |
|---|---|
| Accuracy, voltage LN and LL | 1.0 % (Cl 1.0) / 0.5 % (Cl 0.5) of full scale |
| Accuracy, frequency | 0.2 % |
| Accuracy, active power and energy | 1.0 % / 0.5 % |
| Accuracy, apparent power and energy | 1.0 % / 0.5 % |
| Accuracy, reactive power and energy | 2.0 % / 1.0 % |
| Auxiliary supply | 44-277 V AC (50 Hz +/- 5 %) or 44-277 V DC |
|---|---|
| Burden, auxiliary supply | 4 VA max AC, 2 W max DC |
| Voltage inputs (V1, V2, V3, VN) | 110 or 415 V LL nominal, range 80-480 V LL |
|---|---|
| Current inputs (A1, A2, A3) | 50 mA to 6 A (5 mA starting) |
| Burden, voltage and current inputs | < 0.2 VA per phase |
| Overload | 10 A max continuous |
| Display type | Single row backlit LCD |
|---|---|
| Resolution | 3 digits for RMS values, 9 digits for energy |
| Operating temperature | -10 to 60 C |
|---|---|
| Storage temperature | -25 to 70 C |
| Humidity | 5-95 % non-condensing |
| Altitude | up to 2000 m |
| Protection | IP51 front, IP40 body |
| Bezel | 96 x 96 mm |
|---|---|
| Panel cutout | 92 x 92 mm |
| Depth | 82 mm |
| Weight | 400 g approx unpacked |
| Standards | Measurement category III, pollution degree 2, double insulation |
|---|
| RS485 | Modbus RTU, 2 wire |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
Model numbers in this series (2)
Send us the complete code you need and we will quote it.
3000257230002565
About the EM1200
The Conzerv EM1200 is a compact 96 x 96 mm power and energy meter for control panels, switchboards, generator sets, UPS and motor control centres, and for replacing analog meters. It shows volts line-to-line and line-to-neutral, frequency, power factor, W, VA and VAR, kWh, kVAh and kVARh, run hours, on hours and supply interruptions, and passes the readings to a PLC, DCS or energy management system over RS485 Modbus RTU. Class 0.5 or Class 1.0 is chosen when ordering.
Order codes: 30002572 (Class 0.5, RS485), 30002565 (Class 1.0, RS485).
Frequently asked questions
What is the Schneider Electric EM1200?
Schneider Electric Conzerv EM1200 power and energy meter: LCD display, voltage, frequency, power factor, power and energy, RS485 Modbus RTU, Class 0.5 or 1.0.
What is the accuracy of the EM1200?
Accuracy, voltage LN and LL: 1.0 % (Cl 1.0) / 0.5 % (Cl 0.5) of full scale; Accuracy, frequency: 0.2 %; Accuracy, active power and energy: 1.0 % / 0.5 %.
What supply does the EM1200 need?
Auxiliary supply: 44-277 V AC (50 Hz +/- 5 %) or 44-277 V DC; Burden, auxiliary supply: 4 VA max AC, 2 W max DC.
What operating temperature is the EM1200 rated for?
-10 to 60 C.
Which model numbers does this page cover?
Besides the EM1200, this page covers 30002572 and 30002565.