Schneider Electric PM5330 Power Meter, Modbus RS485, 31st Harmonic, 2 DI / 2 DO / 2 Relays, Class 0.5S

Model number
PM5330

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle.

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: Schneider Electric PM5330 Power Meter, Modbus RS485, 31st Harmonic, 2 DI / 2 DO / 2 Relays, Class 0.5S.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Feature-rich power and energy meters
  • Digital input and output for WAGES monitoring and control relays
  • Modbus 485 communication port for remote monitoring
  • Identify energy savings opportunties with precision accuracy of Class 0.5S
  • 31st Hamronic measurement for Power Quality management

Specifications

Technical
Power quality analysisup to the 31st harmonic
Device applicationPower monitoring, Multi-tariff
Type of measurementCurrent, Voltage, Frequency, Power factor, Energy, Active and reactive power
[Us] rated supply voltage90-450 V AC 45-65 Hz, 100-300 V DC
Network frequency50 Hz, 60 Hz
[In] rated current1 A, 5 A
Type of network3P + N, 3P, 1P + N
Maximum power consumption in VA11 VA at 415 V
Ride-through time80 ms 120 V AC typical, 100 ms 230 V AC typical, 100 ms 415 V AC typical, 50 ms 125 V DC typical
Display typeMonochrome graphic LCD
Display resolution128 x 128 pixels
Sampling rate64 samples/cycle
Measurement current5-8500 mA
Analogue input typeVoltage (impedance 5 MOhm), Current (impedance <= 0.3 mOhm)
Measurement voltage35-760 V AC 45-65 Hz between phases, 20-400 V AC 45-65 Hz between phase and neutral
Frequency measurement range45-65 Hz
Number of inputs2 digital
Measurement accuracyActive energy +/- 0.5 %, Reactive energy +/- 2 %, Active power +/- 0.5 %, Apparent power +/- 0.5 %, Frequency +/- 0.05 %, Power factor +/- 0.5, Current +/- 0.5 %, Voltage +/- 0.5 %, Apparent energy +/- 0.5 %, Reactive power +/- 2 %
Accuracy classClass 0.5S active energy conforming to IEC 62053-22
Number of outputs2 relay, 2 digital
Information displayedTariff (4)
Communication port protocolModbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V, JBUS
Communication port supportRS485
Data recordingMaintenance logs, Time stamping, Alarm logs, Data logs, Min/max of instantaneous values, Event logs
Memory capacity256 kB
Mounting modeFlush-mounted
Mounting supportFramework
StandardsUL 61010-1, IEC 62053-22:2020, IEC 61557-12:2015, EN 50470-3, IEC 60529, IEC 62053-24, EN 50470-1, IEC 62053-23:2020, IEC 62052-11:2020, IEC 62052-31:2015
Product certificationsCE conforming to IEC 61010-1, CULus conforming to UL 61010-1
Width96 mm
Depth72 mm
Height96 mm
Net weight430 g
Environment
IP degree of protectionIP54 display - conforming to IEC 60529, IP30 rear - conforming to IEC 60529
Relative humidity5-95 % at 50 °C non-condensing
Pollution degree2
Ambient air temperature for operation-25-70 °C meter
Ambient air temperature for storage-40-85 °C
Operating altitude2000 m CAT III, 3000 m CAT II

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

Model numbers in this series (1)

Send us the complete code you need and we will quote it.

  • METSEPM5330

About the PM5330

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 31st Harmonic. Include 256 kiloBytes of memory for two fixed parameters, active and reactive energy. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has two digital inputs or digital outputs, configurable, and dual relay outputs. There are 35 configurable alarms and it supports four tariff schedules.

Order code: METSEPM5330.

Frequently asked questions

What is the Schneider Electric PM5330?

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle.

What is the accuracy of the PM5330?

Measurement accuracy: Active energy +/- 0.5 %, Reactive energy +/- 2 %, Active power +/- 0.5 %, Apparent power +/- 0.5 %, Frequency +/- 0.05 %, Power factor +/- 0.5, Current +/- 0.5 %, Voltage +/- 0.5 %, Apparent energy +/- 0.5 %, Reactive power +/- 2 %; Accuracy class: Class 0.5S active energy conforming to IEC 62053-22.

What is the measuring range of the PM5330?

45-65 Hz.

What input does the PM5330 accept?

Voltage (impedance 5 MOhm), Current (impedance <= 0.3 mOhm).

Which model numbers does this page cover?

Besides the PM5330, this page covers METSEPM5330.