Schneider Electric PM3250 DIN-Rail Power Meter, RS485
- Brand
- Schneider Electric
- Model number
- PM3250
- Category
- Power and Energy Meters
PM3250 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle.
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Specifications
| Power quality analysis | up to the 15th harmonic |
|---|---|
| Device application | Multi-tariff, Power monitoring, Sub billing |
| Type of measurement | Active and reactive power, Apparent power, Current, Voltage, Energy, Power factor, Frequency, Total current harmonic distortion THD (I), Total voltage harmonic distortion THD (U) |
| Supply voltage | 100-277 V AC 45-65 Hz, 173-480 V AC 45-65 Hz, 100-300 V DC |
| Network frequency | 60 Hz, 50 Hz |
| [In] rated current | 5 A, 1 A |
| Type of network | 1P + N, 3P, 3P + N |
| Power consumption in VA | 5 VA |
| Display type | Backlit LCD |
| Display resolution | 128 x 96 pixels |
| Sampling rate | 32 samples/cycle |
| Measurement current | 0.02-1.2 A, 0.05-6 A |
| Analogue input type | Current 0-5 A, Current 0-1 A |
| Frequency measurement range | 45-65 Hz |
| Number of inputs | 0 |
| Measurement accuracy | Current 0.3 % 0.5-6 A, Current 0.5 % 0.1-1.2 A, Voltage 0.3 % 50-330 V, Voltage 0.3 % 80-570 V |
| Accuracy class | Class 0.5S active energy conforming to IEC 62053-22, Class 1 active energy conforming to IEC 62053-21, Class 2 reactive energy conforming to IEC 62053-23, Class C active energy conforming to EN 50470-3 |
| Number of outputs | 0 |
| Information displayed | Tariff (4) |
| Communication port protocol | Modbus at 9.6-38.4 kbauds |
| Communication port support | RS485 |
| Data recording | Time stamping, Min/max of instantaneous values, 5 alarms |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Width | 90 mm |
| Depth | 70 mm |
| Height | 95 mm |
| Net weight | 0.26 kg |
| Market segment | Residential, Small commercial |
| Overvoltage category | III |
|---|---|
| IP degree of protection | IP40 front panel - conforming to IEC 60529, IP20 body - conforming to IEC 60529 |
| Relative humidity | 5-95 % at 50 °C |
| Pollution degree | 2 |
| Ambient air temperature for operation | -25-70 °C |
| Ambient air temperature for storage | -40-85 °C |
| Operating altitude | < 3000 m |
| Compatibility code | PM3250 |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
Model numbers in this series (1)
Send us the complete code you need and we will quote it.
METSEPM3250
About the PM3250
PM3250 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor, Apparent Power, Total Harmonic Distortion and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 277VAC, 173 to 480VAC and 100 to 300VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase, Single Phase and Neutral or Three Phase configurations. Direct measurement range is 50 to 570VAC, with an external VT 570 to 999000VAC. The range of measurement voltage between Phases is 80 to 570VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 50 to 330VAC at 45 to 65 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter offers event recording with up to 5 alarms.
Order code: METSEPM3250.
Frequently asked questions
What is the Schneider Electric PM3250?
PM3250 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle.
What is the accuracy of the PM3250?
Measurement accuracy: Current 0.3 % 0.5-6 A, Current 0.5 % 0.1-1.2 A, Voltage 0.3 % 50-330 V, Voltage 0.3 % 80-570 V; Accuracy class: Class 0.5S active energy conforming to IEC 62053-22, Class 1 active energy conforming to IEC 62053-21, Class 2 reactive energy conforming to IEC 62053-23, Class C active energy conforming to EN 50470-3.
What is the measuring range of the PM3250?
45-65 Hz.
What input does the PM3250 accept?
Current 0-5 A, Current 0-1 A.
Which model numbers does this page cover?
Besides the PM3250, this page covers METSEPM3250.