Schneider Electric PM3210 DIN-Rail Power Meter, Pulse Output

Model number
PM3210

PM3210 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle.

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: Schneider Electric PM3210 DIN-Rail Power Meter, Pulse Output.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Feature-rich power and energy meters
  • Identify savings opportunities
  • Compact size of 18mm*5 modules width
  • Digital output for remote monitoring
  • Identify energy savings opportunties with precision accuracy of Class 0.5S

Specifications

Technical
Power quality analysisup to the 15th harmonic
Device applicationPower monitoring, Multi-tariff, Sub billing
Type of measurementActive and reactive power, Apparent power, Current, Voltage, Energy, Power factor, Frequency, Total current harmonic distortion THD (I), Total voltage harmonic distortion THD (U)
Supply voltage100-277 V AC 45-65 Hz, 173-480 V AC 45-65 Hz, 100-300 V DC
Network frequency50 Hz, 60 Hz
[In] rated current1 A, 5 A
Type of network3P, 3P + N, 1P + N
Power consumption in VA5 VA
Display typeBacklit LCD
Display resolution128 x 96 pixels
Sampling rate32 samples/cycle
Measurement current0.05-6 A, 0.02-1.2 A
Analogue input typeCurrent 0-5 A, Current 0-1 A
Frequency measurement range45-65 Hz
Number of inputs0
Measurement accuracyCurrent 0.3 % 0.5-6 A, Current 0.5 % 0.1-1.2 A, Voltage 0.3 % 50-330 V, Voltage 0.3 % 80-570 V
Accuracy classClass 0.5S active energy conforming to IEC 62053-22, Class 1 active energy conforming to IEC 62053-21, Class 2 reactive energy conforming to IEC 62053-23, Class C active energy conforming to EN 50470-3
Number of outputs1 pulse
Information displayedTariff (4)
Communication port protocol-
Communication port support-
Data recordingTime stamping, 5 alarms, Min/max of instantaneous values
Mounting modeClip-on
Mounting supportDIN rail
Width90 mm
Depth70 mm
Height95 mm
Net weight0.26 kg
Market segmentResidential, Small commercial
Environment
Overvoltage categoryIII
IP degree of protectionIP40 front panel - conforming to IEC 60529, IP20 body - conforming to IEC 60529
Relative humidity5-95 % at 50 °C
Pollution degree2
Ambient air temperature for operation-25-70 °C
Ambient air temperature for storage-40-85 °C
Operating altitude< 3000 m
Compatibility codePM3210

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

Model numbers in this series (1)

Send us the complete code you need and we will quote it.

  • METSEPM3210

About the PM3210

PM3210 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor, Apparent Power, Total Harmonic Distortion and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 277VAC, 173 to 480VAC and 100 to 300VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase, Single Phase and Neutral or Three Phase configurations. Direct measurement range is 50 to 570VAC, with an external VT 570 to 999000VAC. The range of measurement voltage between Phases is 80 to 570VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 50 to 330VAC at 45 to 65 Hz. This meter has no communication input capability. Support for one digital output. The meter offers event recording with up to 5 alarms.

Order code: METSEPM3210.

Frequently asked questions

What is the Schneider Electric PM3210?

PM3210 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle.

What is the accuracy of the PM3210?

Measurement accuracy: Current 0.3 % 0.5-6 A, Current 0.5 % 0.1-1.2 A, Voltage 0.3 % 50-330 V, Voltage 0.3 % 80-570 V; Accuracy class: Class 0.5S active energy conforming to IEC 62053-22, Class 1 active energy conforming to IEC 62053-21, Class 2 reactive energy conforming to IEC 62053-23, Class C active energy conforming to EN 50470-3.

What is the measuring range of the PM3210?

45-65 Hz.

What input does the PM3210 accept?

Current 0-5 A, Current 0-1 A.

Which model numbers does this page cover?

Besides the PM3210, this page covers METSEPM3210.