Schneider Electric PM1225H Power and Energy Meter, LCD, RS485, Class 0.5 / 1.0
- Brand
- Schneider Electric
- Model number
- PM1225H
- Category
- Power and Energy Meters
The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy.
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Measurement of basic electrical parameters in panel, motor and distribution board
- Aggregation of energy consumption and cost allocation
- Single row LCD, three parameters name and value at one glance
- Password to avoid tampering and cybersecurity to disable communication
Specifications
| Power quality analysis | total harmonic distortion |
|---|---|
| Device application | Energy monitoring |
| Type of measurement | Current, Voltage, Frequency, Power factor, Phase angle, RPM, Peak demand power, Harmonic distortion (I THD & U THD), Active power, Active energy |
| Counter functions | ON hour counting, ON-load hour counting, Power interruption |
| [Us] rated supply voltage | 48-277 V AC/DC |
| Network frequency | 50 Hz, 60 Hz |
| [In] rated current | 1 A, 5 A |
| Type of network | 3P, 2P + N, 1P + N, 3P + N, 2P |
| Maximum power consumption in W | 2 W at 36 V |
| Display type | LCD display |
| Display colour | Monochrome |
| Display digits | 12 digit(s) |
| Communication of data | Reading of measurements, All counters, Revolution speed, Last cleared log, Instantaneous and demand values |
| Sampling rate | 32 samples/cycle |
| Measurement current | 5-6000 mA |
| Signal | Voltage (impedance 5 MOhm)4 x , Current 0.005-10 A (impedance 0.3 MOhm)6 x |
| Frequency measurement range | 45-65 Hz |
| Accuracy class | Class 0.5 active energy conforming to IEC 62053-21, Class 0.5 reactive energy conforming to IEC 62053-24 |
| Demand intervals | 1 s |
| Communication port protocol | Modbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V |
| Communication port support | Screw connector - RS485 |
| Data recording | Energy consumption logs |
| Material | Polycarbonate |
| Mounting mode | Flush-mounted |
| Mounting support | Framework |
| Installation category | III |
| Type of installation | Indoor installation |
| Measurement category | Category III 480 V |
| Electrical insulation class | Class II |
| Standards | IEC 61010-1:ed. 3, UL 61010-1:ed. 3 |
| Product certifications | CE conforming to IEC 61010-1, CULus conforming to UL 61010-1, CULus conforming to CSA C22.2 No 61010-1, C-Tick |
| Width | 96 mm |
| Depth | Outside - 13 mm, Panel - 49 mm |
| Height | 96 mm |
| Net weight | 300 g |
| Overvoltage category | III |
|---|---|
| IP degree of protection | IP51 front - conforming to IEC 60529, IP30 body - conforming to IEC 60529 |
| Relative humidity | 5-95 % at 50 °C |
| Pollution degree | 2 |
| Ambient air temperature for operation | -10-60 °C |
| Ambient air temperature for storage | -20-70 °C |
| Operating altitude | <= 2000 m |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
Model numbers in this series (2)
Send us the complete code you need and we will quote it.
METSEPM1225HCL5METSEPM1225HCL1
About the PM1225H
The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy. The navigation is assured by 4 panel buttons. Configuration and clearing are protected by an user configured password (4 digits). Providing Class 0.5S active energy accuracy per IEC 62053-21 standard, the meter will measure active and reactive energy. Communication protocol is Modbus RTU with RS485 port support. The LCD screen, with a resolution of 128x32 pixels, is used to display the multiple parameter measurement. Mechanical dimensions are 96 mm in width, 96 mm in height and 63 mm in depth, for a product weight of 300 g.
Order codes: METSEPM1225HCL5, METSEPM1225HCL1.
Frequently asked questions
What is the Schneider Electric PM1225H?
The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy.
What is the accuracy of the PM1225H?
Class 0.5 active energy conforming to IEC 62053-21, Class 0.5 reactive energy conforming to IEC 62053-24.
What is the measuring range of the PM1225H?
45-65 Hz.
What supply does the PM1225H need?
48-277 V AC/DC.
Which model numbers does this page cover?
Besides the PM1225H, this page covers METSEPM1225HCL5 and METSEPM1225HCL1.