Schneider Electric PM1225H Power and Energy Meter, LCD, RS485, Class 0.5 / 1.0

Model number
PM1225H

The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy.

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: Schneider Electric PM1225H Power and Energy Meter, LCD, RS485, Class 0.5 / 1.0.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Measurement of basic electrical parameters in panel, motor and distribution board
  • Aggregation of energy consumption and cost allocation
  • Single row LCD, three parameters name and value at one glance
  • Password to avoid tampering and cybersecurity to disable communication

Specifications

Technical
Power quality analysistotal harmonic distortion
Device applicationEnergy monitoring
Type of measurementCurrent, Voltage, Frequency, Power factor, Phase angle, RPM, Peak demand power, Harmonic distortion (I THD & U THD), Active power, Active energy
Counter functionsON hour counting, ON-load hour counting, Power interruption
[Us] rated supply voltage48-277 V AC/DC
Network frequency50 Hz, 60 Hz
[In] rated current1 A, 5 A
Type of network3P, 2P + N, 1P + N, 3P + N, 2P
Maximum power consumption in W2 W at 36 V
Display typeLCD display
Display colourMonochrome
Display digits12 digit(s)
Communication of dataReading of measurements, All counters, Revolution speed, Last cleared log, Instantaneous and demand values
Sampling rate32 samples/cycle
Measurement current5-6000 mA
SignalVoltage (impedance 5 MOhm)4 x , Current 0.005-10 A (impedance 0.3 MOhm)6 x
Frequency measurement range45-65 Hz
Accuracy classClass 0.5 active energy conforming to IEC 62053-21, Class 0.5 reactive energy conforming to IEC 62053-24
Demand intervals1 s
Communication port protocolModbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V
Communication port supportScrew connector - RS485
Data recordingEnergy consumption logs
MaterialPolycarbonate
Mounting modeFlush-mounted
Mounting supportFramework
Installation categoryIII
Type of installationIndoor installation
Measurement categoryCategory III 480 V
Electrical insulation classClass II
StandardsIEC 61010-1:ed. 3, UL 61010-1:ed. 3
Product certificationsCE conforming to IEC 61010-1, CULus conforming to UL 61010-1, CULus conforming to CSA C22.2 No 61010-1, C-Tick
Width96 mm
DepthOutside - 13 mm, Panel - 49 mm
Height96 mm
Net weight300 g
Environment
Overvoltage categoryIII
IP degree of protectionIP51 front - conforming to IEC 60529, IP30 body - conforming to IEC 60529
Relative humidity5-95 % at 50 °C
Pollution degree2
Ambient air temperature for operation-10-60 °C
Ambient air temperature for storage-20-70 °C
Operating altitude<= 2000 m

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

Model numbers in this series (2)

Send us the complete code you need and we will quote it.

  • METSEPM1225HCL5
  • METSEPM1225HCL1

About the PM1225H

The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy. The navigation is assured by 4 panel buttons. Configuration and clearing are protected by an user configured password (4 digits). Providing Class 0.5S active energy accuracy per IEC 62053-21 standard, the meter will measure active and reactive energy. Communication protocol is Modbus RTU with RS485 port support. The LCD screen, with a resolution of 128x32 pixels, is used to display the multiple parameter measurement. Mechanical dimensions are 96 mm in width, 96 mm in height and 63 mm in depth, for a product weight of 300 g.

Order codes: METSEPM1225HCL5, METSEPM1225HCL1.

Frequently asked questions

What is the Schneider Electric PM1225H?

The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy.

What is the accuracy of the PM1225H?

Class 0.5 active energy conforming to IEC 62053-21, Class 0.5 reactive energy conforming to IEC 62053-24.

What is the measuring range of the PM1225H?

45-65 Hz.

What supply does the PM1225H need?

48-277 V AC/DC.

Which model numbers does this page cover?

Besides the PM1225H, this page covers METSEPM1225HCL5 and METSEPM1225HCL1.