Schneider Electric PM1130H Dual Source Power and Energy Meter, LED, RS485, Relay, Class 0.5
- Brand
- Schneider Electric
- Model number
- PM1130H
- Category
- Power and Energy Meters
The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy.
Price and availability on request
We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.
Several models? Add each to your enquiry list and send them as one enquiry.
Key features
- Two energy registers for Utility, Gensen, Solar or Wind
- Relay to control the load in the event of abnormality
- 8 segment alphanumeric LEDs display for measured parameters
- Password to avoid tampering and cybersecurity to disable communication
Specifications
| Power quality analysis | total harmonic distortion |
|---|---|
| Device application | Main or redundant power monitoring, Energy monitoring |
| Type of measurement | Current, Voltage, Frequency, Power factor, Phase angle, RPM, Peak demand power, Harmonic distortion (I THD & U THD), Active power, Active energy |
| Counter functions | Power interruption, ON-load source 1 hour counting, ON-load source 2 hour counting, ON hour counting |
| [Us] rated supply voltage | 60-277 V AC 45-65 Hz, 60-277 V DC |
| Network frequency | 60 Hz, 50 Hz |
| [In] rated current | 5 A, 1 A |
| Type of network | 3P + N, 3P, 2P, 1P + N, 2P + N |
| Maximum power consumption in VA | 6 VA at 240 V between phase and neutral |
| Maximum power consumption in W | 3 W at 240 V |
| Display type | 7 segments LED |
| Display colour | Red |
| Messages display capacity | 3 fields of 4 characters |
| Display digits | 12 digit(s) - 14.2 mm in height |
| Communication of data | Reading of measurements, All counters, Instantaneous and demand values, Last cleared log, Revolution speed |
| Sampling rate | 32 samples/cycle |
| Measurement current | 5-6000 mA |
| Signal | Voltage (impedance 5 MOhm)4 x , Current 0.005-10 A (impedance 0.3 MOhm)6 x |
| Frequency measurement range | 45-65 Hz |
| Accuracy class | Class 2 reactive energy conforming to IEC 62053-23, Class 0.5 active energy conforming to IEC 62053-22 |
| Number of outputs | 1 relay |
| Output voltage | 300 V AC@2 A |
| Demand intervals | 1 s |
| Communication port protocol | Modbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V |
| Communication port support | RS485 |
| Data recording | Energy consumption logs |
| Material | Polycarbonate |
| Mounting mode | Flush-mounted |
| Mounting support | Framework |
| Installation category | III |
| Type of installation | Indoor installation |
| Measurement category | Category III 480 V |
| Electrical insulation class | Class II |
| Standards | IEC 61010-1:ed. 3, UL 61010-1:ed. 3 |
| Product certifications | CE conforming to IEC 61010-1, CULus conforming to UL 61010-1, CULus conforming to CSA C22.2 No 61010-1, C-Tick |
| Width | 96 mm |
| Depth | Outside - 13 mm, Panel - 52 mm |
| Height | 96 mm |
| Net weight | 300 g |
| Overvoltage category | III |
|---|---|
| IP degree of protection | IP51 front - conforming to IEC 60529, IP30 body - conforming to IEC 60529 |
| Relative humidity | 5-95 % at 50 °C |
| Pollution degree | 2 |
| Ambient air temperature for operation | -10-60 °C |
| Ambient air temperature for storage | -20-70 °C |
| Operating altitude | <= 2000 m |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details
Model numbers in this series (1)
Send us the complete code you need and we will quote it.
METSEPM1130HCL05RD
About the PM1130H
The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy. The navigation is assured by 4 panel buttons. Configuration and clearing are protected by an user configured password (4 digits). Providing Class 0.5S active energy accuracy per IEC 62053-21 standard, the meter will measure active and reactive energy. The display has 3 rows 14 mm height, 7 segment 4 digit LED display, multi parameter measurement. Mechanical dimensions are 96 mm in width, 96 mm in height and 63 mm in depth, for a product weight of 300 g.
Order code: METSEPM1130HCL05RD.
Frequently asked questions
What is the Schneider Electric PM1130H?
The EasyLogic PM1000H series basic power and energy meters offer all the measurement capabilities required to monitor an installation. Measured parameters are power, energy (delivered and received), harmonic distortion and selectable demand energy.
What is the accuracy of the PM1130H?
Class 2 reactive energy conforming to IEC 62053-23, Class 0.5 active energy conforming to IEC 62053-22.
What is the measuring range of the PM1130H?
45-65 Hz.
What output does the PM1130H give?
300 V AC@2 A.
Which model numbers does this page cover?