Schneider Electric EM6438H Dual Source Power and Energy Meter, LED, RS485, Class 0.5 / 1.0

Model number
EM6438H

EM6438H include two energy registers separately records consumption for dual source energy accounting. Utility vs Genset, Utility vs Solar, Utility vs Wind, or a combination of any two power sources.

Price and availability on request

We reply by email or phone, Monday to Saturday, 10:30 am to 6:30 pm.

Several models? Add each to your enquiry list and send them as one enquiry.

Request a quote

Sent with the product details: Schneider Electric EM6438H Dual Source Power and Energy Meter, LED, RS485, Class 0.5 / 1.0.

A phone number or an email address is needed, so we can reply.

We use these details only to reply to your enquiry. See our privacy notice.

Key features

  • Comprehensive 3-phase electrical instrumentation
  • Navigation button to have some load managment features
  • Compact and rugged package
  • Energy accounting and balancing
  • Network disabling feature to prevent unauthorized access

Specifications

Technical
Device applicationSolar generation, GenSet, Main or redundant power monitoring, Energy monitoring, Wind generation
Type of measurementPower factor, Phase angle, RPM, Active power, Active energy
Counter functionsAlternate-source hour counting, ON hour counting
[Us] rated supply voltage44-300 V AC 45-65 Hz, 44-300 V DC
Network frequency50 Hz, 60 Hz
[In] rated current5 A, 1 A
Type of network2P, 3P + N, 1P + N, 3P, 2P + N
Maximum power consumption in VA4 VA at 240 V between phase and neutral
Maximum power consumption in W2 W at 240 V
Display type7 segments LED
Display colourRed
Messages display capacity3 fields of 4 characters
Display digits12 digit(s) - 14.2 mm in height
Communication of dataReading of measurements, System power production, All counters, Last cleared log, Revolution speed
Sampling rate32 samples/cycle
Measurement current5-6000 mA
SignalVoltage (impedance 5 MOhm)4 x , Current 0.005-10 A (impedance 0.3 MOhm)6 x
Frequency measurement range45-65 Hz
Measurement accuracyPower factor +/- 0.01, Reactive power +/- 2 %, Reactive energy +/- 2 %, Active power +/- 0.5 %, Apparent power +/- 0.5 %, Active energy +/- 0.5 %, Apparent energy +/- 0.5 %
Accuracy classClass 2 reactive energy conforming to IEC 62053-23, Class 0.5 active energy conforming to IEC 62053-22
Number of outputs0
Demand intervals1 s
Communication port protocolModbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V
Communication port supportScrew terminal block - RS485
MaterialPolycarbonate
Mounting modeFlush-mounted
Mounting supportFramework
Fixing modeBy clamp
Installation categoryIII
Type of installationIndoor installation
Measurement categoryCategory III 35-480 V
Electrical insulation classClass II
StandardsIEC 61010-1:ed. 3, UL 61010-1:ed. 3
Product certificationsCE conforming to IEC 61010-1, CULus conforming to UL 61010-1, CULus conforming to CSA C22.2 No 61010-1, C-Tick
Width96 mm
DepthOutside - 13 mm, Panel - 49 mm
Height96 mm
Net weight300 g
Environment
Overvoltage categoryIII
IP degree of protectionIP51 front - conforming to IEC 60529, IP30 body - conforming to IEC 60529
Relative humidity5-95 % at 50 °C
Pollution degree2
Ambient air temperature for operation-10-60 °C
Ambient air temperature for storage-20-70 °C
Operating altitude<= 2000 m

Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering. Brand names, logos and model names are trademarks of their respective owners, used only to identify the product. Details

Model numbers in this series (2)

Send us the complete code you need and we will quote it.

  • METSEEM6438HCL05RS
  • METSEEM6438HCL10RS

About the EM6438H

EM6438H include two energy registers separately records consumption for dual source energy accounting. Utility vs Genset, Utility vs Solar, Utility vs Wind, or a combination of any two power sources. Form A relay to control the load in the event of abnormality in the electrical circuit including excess consumption of power. Providing Class 0.5S active energy accuracy per IEC 62053-21 standard, the meter will measure active and reactive energy. This meter can be used in billing and load management. Communication protocol is Modbus RTU with RS485 port support. The display has 3 rows 14 mm height, 7 segment 4 digit LED display, multi parameter measurement. Mechanical dimensions are 96 mm in width, 96 mm in height and 62.7 mm in depth ; for 300 g.

Order codes: METSEEM6438HCL05RS, METSEEM6438HCL10RS.

Frequently asked questions

What is the Schneider Electric EM6438H?

EM6438H include two energy registers separately records consumption for dual source energy accounting. Utility vs Genset, Utility vs Solar, Utility vs Wind, or a combination of any two power sources.

What is the accuracy of the EM6438H?

Measurement accuracy: Power factor +/- 0.01, Reactive power +/- 2 %, Reactive energy +/- 2 %, Active power +/- 0.5 %, Apparent power +/- 0.5 %, Active energy +/- 0.5 %, Apparent energy +/- 0.5 %; Accuracy class: Class 2 reactive energy conforming to IEC 62053-23, Class 0.5 active energy conforming to IEC 62053-22.

What is the measuring range of the EM6438H?

45-65 Hz.

What supply does the EM6438H need?

44-300 V AC 45-65 Hz, 44-300 V DC.

Which model numbers does this page cover?

Besides the EM6438H, this page covers METSEEM6438HCL05RS and METSEEM6438HCL10RS.