Proton TT-5 5 AC Controller for Telecom Shelters
- Brand
- Proton
- Model number
- TT-5
- Category
- AC & Pump Controllers
Controller for automatic duty sharing and changeover of air conditioners (Proton TT-5). Runs on 230 V AC 1-phase, LCD display.
Price and availability on request
Key features
- Fully programmable
- Complete protection for A/C from Unhealthy condition
- All set points programmable from keypad
- Password protection for controller
- 16 char. 2 lines LCD display with back light, on controller front panel
- Four key interface for onsite programming
- Separate alarm contacts for A/C fail alarm
- Automatic display of A/C parameters one by one in Run Mode
- Status & Healthy indication by LED on front panel
- Alarm indication by LED on front panel
- Room temperature sensing by precise sensor
- Flexibility in using number of compressors
- Separate outputs for each compressor.Direct display of actual voltage
- Direct display of actual room temperature
- Automatic Timer mode operation if Room sensor fails
- All Faults are Auto resettable
Specifications
| Supply | Single phase 230 VAC, 50 Hz. |
|---|---|
| Display | 16 x 2 LCD Display for Status & Faults. |
| Input | MCB TPN 32Amp, 10KA capacity. |
| Output | 30 Amp single pole contactor for each A/C (230 V AC) |
| Alarm O/P | 5 Nos. Alarm contacts 7 Amp 250VAC. |
| Sensor | NTC Temp sensor 1 No for room temp. (Range 0 - 55°C) |
| Fire Input | Fire alarm input from fire panel |
| Indications | 1) Healthy indication for controller. 2) A/C ON indication for Each A/C. 3) Alarm indications 5 Nos. |
| Dimensions | 330mm(W) X 220 mm (H) X 80 mm (O) |
| Keys - 4 key keypad for settings. | 1) SET Key: To enter into FUNCTION SET Mode/To view the next set pt. 2) Up Arrow Key: To increment the set point 3) Down Arrow Key: To decrement the set point. 4) ENTER Key: To come out of FUNCTION SET Mode/To enter into menu/To accept the password |
| Mounting | Wall mounting |
| Sensing | 1. Inbuilt current sensing for compressor. 2. Temperature Sensing by precise Temp. Sensor. 3. Fire Alarm sensing. |
| Terminals | 1) Separate O/P s for each Compressor. 2) Temperature sensor. 3) Alarm relay o/p. |
| Alarms/ Protections | 1) Over load protection set point user settable. 2) Under load protection set point user settable. 3) High/low temperature alarm set point user settable. |
| Optional features | Multi-tone selection site selectable.; Silent push button can be provide to mute sound.; Extra Potential free relay output contact can be provide.; operating Supply voltage can be from 20V DC to 60V DC. Or 90 to 270VAC. |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.