Multispan CPR-35 Current Protection Relay, Digital DIN Rail
- Brand
- Multispan
- Model number
- CPR-35
- Category
- Protection & Monitoring Relays
Digital DIN-rail relay with programmable over- and under-current trips, one changeover relay and fail-safe or non-fail-safe mode. Single and three-phase versions; 35 mm wide.
Price and availability on request
Key features
- Programmable Over & Under Current
- 1-Relay, 1-C/O
- Fail Safe & Non Fail Safe Mode
- Available in 1Ø and 3Ø
- Size: (H)90mm X (W)35mm X (D)61.5mm
- Supply Voltage: 100 to 270V AC/DC
Specifications
| Primary CT value | 5 to 999 Selectable |
|---|---|
| Secondary current AC | 0.1 to 5 Amp AC |
| Resolution | 0.01A, 0.1A, 1A |
| Display | UPPER : 3-Digit, 7-Seg 0.4”; LOWER : 3-Digit, 7-Seg 0.28” |
|---|---|
| Keys | SET, INC, DEC/ RST |
| Relay | 1 nos. |
|---|---|
| Relay Type | 1 C/O (NO-C-NC) |
| Rating | 5A, 250V AC/30 V DC |
| ACCURACY | Class 1.0 (Standard) |
| Dimension (mm) | 90 (H) x 35 (W) x 61.5 (D) |
|---|---|
| Trip Setting | Under current: 0.00 to 100% of primary C.T value; Over current: 0.00 - 120% of primary C.T value |
| Time parameter | Trip delay time : 0 to 999 sec; Power on time : 0 to 99 sec; Initial time delay : 0 to 99 sec; Recovery time : 0 to 99 sec |
| Supply voltage | 100 to 270V AC/DC, 50-60Hz |
|---|---|
| Power consumption (VA RATING) | 3 VA @ 230V AC MAX |
| Operating Temp. | 0°C to 55°C |
|---|---|
| Relative Humidity | Upto 95% RH; (non-condensing) |
| Typical uses | DG Set Panels, Motor Control Center Panels, Control Panels, Distribution Panels, Process Control |
|---|
| CPR-35-E3-00 | Size(mm) 90 x 35 x 61.5; Network 3Ø; Input 5A to 999A; Output 1R, 1-C/O; Supply 100-270V AC/DC |
|---|---|
| CPR-35-1C-E3-00 | Size(mm) 90 x 35 x 61.5; Network 1Ø; Input 5A to 999A; Output 1R, 1-C/O; Supply 100-270V AC/DC |
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.