8-stage automatic power factor controller with three-CT current sensing (primary 5 to 9999 A), auto, manual and rotation modes for capacitor banks, and an alarm output.
Price and availability on request
Key features
- Current AC(3 CT Sensing)
- Primary CT Ratio: 5 to 9999 Amp Selectable
- Secondary Current Ac: 0.01 To 5.0 Amp (Without CT)
- 8-Stage Available
- Auto/Manual/Rotation Mode
- With Alarm Output
Specifications
| Input voltage AC | 20 to 300V AC (L - N); 35 to 520V AC (L - L) |
|---|---|
| Burden | < 5 VA |
| Frequency | 50/60 Hz; Current AC(3 CT Sensing) |
| Primary CT Ratio | 5 to 9999 Amp Selectable |
| Secondary Current Ac | 0.01 To 5.0 Amp (Without CT) |
| Burden | < 0.4 VA |
| Overload | Upto 6A Continuous |
| Display | Upper: 4 Digit,7 seg,0.60"; Lower: 7 Digit,7 seg,0.38" |
|---|---|
| Key | SET/ENT, INC, DEC, EXIT |
| Size | 144 (H) x 144 (W) x 80 (D) mm |
|---|---|
| Panel Cutout | 137 (H) x 137 (W) mm |
| Operating Mode | Kvar / Intel / Manual |
|---|---|
| Programmable Hysteresis | 0 to 25 KVAr |
| Output Specification | 8 Stage Capacitor Relay |
|---|---|
| Relay Type | (NO-C) |
| Rating | 7A, 250V AC |
| Supply voltage | 100V To 270V AC (L-N) |
|---|---|
| Power consumption (VA RATING) | Approximately 5VA |
| Accuracy | Class 0.5 (Standard) |
|---|
| Operating Temp. | 0°C to 55°C |
|---|---|
| Relative Humidity | Upto 95% RH; (non-condensing) |
| Typical uses | PF Management using 3 CT Method, For 3Ø Balanced Industrial Loads, Energy Monitoring System, DG Set Panels, Process Control, Power Factor Correction Panels, Commercial Buildings |
|---|