Minilec S2 VMR6 Phase Failure Relay
- Brand
- Minilec
- Model number
- S2 VMR6
- Category
- Protection & Monitoring Relays
Minilec S2 VMR6 phase failure relay with 2 CO output, for 415 VAC ± 20% supply. Typical uses: hoist motor control, 3 ph. split AC machines, agricultural pump starters.
Price and availability on request
Key features
- Phase Failure, Phase Sequence
- Fixed Unbalance Settings, Neutral Fail
- Adjustable UV / OV Settings, Auto Reset
- 2 CO Output Relay, SMD Technology
Specifications
| Output Contacts | 2 CO |
|---|---|
| Trip Setting(Volts) | Wherever not specified Contact Rating : 5A @ 230 V AC (resistive) |
| Note | 75% to 95% of 415 VAC ; 105% to 125% ; Wherever not specified Contact Rating : 5A @ 230 V AC (resistive) |
| Power on Delay | 5 Sec. ± 1 Sec. (Fixed) |
| Trip Time Delay | 5 Sec. ± 1 Sec. (Fixed) ; Instant ; Less than 2 Sec. |
| Resetting Mode | Auto Reset |
| Weight | 110 gms. |
| Dimensions (mm) | 90 x 35 x 60 ; 35 mm rail Mounting |
| System | 415 VAC ± 20% |
|---|---|
| Auxiliary | Built-in |
| Phase Sequence | Yes |
|---|---|
| Phase Unbalance | 94 V ± 6 V Ph - Ph (fixed) |
| Under Voltage | 75% to 95% of 415 VAC |
| Over Voltage | 105% to 125% |
| Power on Delay | 5 Sec. ± 1 Sec. (Fixed) |
| UB/ SP/UV/OV | 5 Sec. ± 1 Sec. (Fixed) |
| RP | Instant |
| Neutral Fail | Less than 2 Sec. |
| Resetting Mode | Auto Reset |
| Weight | 110 gms. |
| Overall (L x W x D) | 90 x 35 x 60 |
| Mounting (L x W) | 35 mm rail Mounting |
| Applications | Hoist Motor Control, 3 Ph. Split AC machines, Agricultural Pump Starters, Machine Tools, Valve Actuator Motor, Injection Molding M/c |
|---|
Specifications are from the manufacturer's published information. Confirm critical values with us or the datasheet before ordering.